Datasheet for LT Panel

CLIENT UP JAL NIGAM ISSUED for ENQUIRY

CONSULTANT NA PROJECT NO. 10 M 165

PROJECT O&M of STP Plant and Sewage network at Ghaziabad ITEM TAG -

LOCATION Chamundadevi IPS _ Ghaziabad Quantity - 1 no


Sl.No Description Wabag Requirement Vendor Data
1.00 GENERAL DATA
1.01 Required Quantity 1 no
1.02 Design Ambient Temperature 45 Deg C
1.03 Relative Humidity 95 % R.H
1.04 Zone of Operation Non- hazardous
1.05 Area Indoor
1.06 Altitude <1000 meters above sea level
1.07 System neutral earthing Effectively Earthed
2.00 AC Input
2.01 Input Voltage 415V AC
2.02 Input Voltage Variation ± 10%
2.03 Phase Three Phase ,4 Wires
2.04 Input Frequency 50Hz
2.05 Input Frequency Variation ±5%
2.06 Combined Voltage and Frequency Variation ±10%
2.07 Panel Main Input (TPN) MCCB
2.08 Main Input Rating 400 A
3.00 Panel
3.01 Type Indoor Application
3.02 Overall Dimension LXWXH Not Available
No of out going feeders 4
out going feeders rating 100 A, 100A, 100A, 100A
3.03 Degree of Protection IP-54
3.04 Material CRCA Sheet Steel ( 2mm Thick)
Powder Coated (Shade RAL 7032) with anti rust
3.05 Painting
chemical coating
3.06 Doors Front-1
3.07 Cable Entry From Bottom
3.08 Ventilation Fan cooled with louvers backed by find wire mesh
Required numbers of Lifiting Hook shall be provide on
3.09 Lifiting Hooks
top of frame for transporting panel.
Sl.No Description Wabag Requirement Vendor Data
Earth bus shall provide throughout the length of panel
3.10 Earth Bus
(MOC: Aluminum)
3.11 Cable Gland Plate Gland Plate – 3mm Aluminium
3.12 Total Weight VTS
Recommended Minimum Clearance for Installation
Front clearance
3.13 VTS
Back clearance
Side Clearance
3.14 Danger Sticker (as per IS 2551-2010) Shall be in 2 Languages( English and Hindi)
To be Provided
3.15 Name Plate
Trifoliate (White Background & Black Font)
3.16 Space Heater with Thermostat VTS
3.17 Cubicle illumination Required
Phase to Phase ‐25 mm
3.18 Min. clearance
Phase to earth ‐19 mm
3.19 Make Reputed
High Conductivity Aluminum of alloy of E-91E grade of
3.20 Main Busbar /Control Busbar
IS 5082
3.21 Type of Separation Form 2B
3.22 Base frame ISMC-75
4.00 Indication (minimum requirement)
4.01 AC Supply Healthy (R, Y,B Phases) Required
4.02 ON Indication (Colour -RED) Required
4.03 OFF Indication (Colour-GREEN) Required
4.04 Trip Indication (Colour -AMBER ) Required
4.05 Other system required indication lamp Required
5.00 Metering
5.01 AC Voltmeter with Selector Switch at input Required
5.02 Ammeter Shall be provide for motor feeder
5.03 Ammeter for Motor above 5.0 KW Shall be provide ammeter with selector switch.
6.04 Control Cable 1100V PVC Copper cable
7.00 Others
7.01 Control Transformer Insulation Class F with temp. rise limited to Class B
7.02 Heater Requirement VTS
Notes
1 Vendor to specify (VTS) - Data to be furnished by vendor.
2 Vendor Shall submit the 2 year O &M Spares List with offer
3 General Description Shall be provide for Submerssible pump Starter Panel
4 All panel Component shall be as per List of vendor
5 Motor feeder switch rating are to selected based on Type-2 co-ordination .
6 Vendor shall provide panel GA ( Front View (Door open/Close), Left Side View & Right side view.
7 Indication lamp shall be LED Type with series resistance
8 Voltmeter shall be Analog type
9 Voltmeter selctor switch selector switch shall be provide RY,YB,RB and off positions.
Sl.No Description Wabag Requirement Vendor Data
10 System required interlock shall be provide
11 Ammeter shall be moving iron type ,90 deg scale for ammeter suppersed scale in case motor feeder ammeter dial range to suit CT Primary current,Size 96 Sq.Accuracy-class-1.0
12 The Control wiring shall be carriedout with 1.5 Sq.mm standard copper wire and 2.5 sq.mm for current circuit.
13 Motor starters shall be povided single phase preventer with thermal overload
16 Push button shall be momentary type ,2 NO & 2 NC contacts of 10A at 240 V AC.