Restricted Earth Fault Protection

Earth fault is the unintended fault between the live conductor and the earth. It also
occurs, because of the insulation breakdown. When the fault occurs, the short-circuit
currents flow through the system, and this current is returned through the earth or any
electrical equipment. This fault current damaged the equipment of the power system
and also interrupted the continuity of the supply.

The earth fault can be dispersed by using the restricted earth fault protection scheme.
The earth fault protection scheme consists the earth fault relay, which gives the tripping
command to the circuit breaker and hence restricted the fault current.

The earth fault relay is placed in the residual part of the current transformers shown in
the figure below. This relay protects the delta or unearthed star winding of the power
transformer against the fault current. The connection of earth fault relay with the star or
delta winding of the transformer is shown in the figure below.

https://circuitglobe.com/restricted-earth-fault-protection.html 1/9
4/26/2020 Restricted Earth Fault Protection System - Explanation & Working - Circuit Globe

The current transformers are placed on both sides of the protective zone. The secondary
terminal of the current transformer is connected in parallel with the relay. The output of
the current transformer is equal to the zero sequence current flows in the line. The zero
sequence current is absent for the external fault and for the internal fault it becomes
twice the value of fault current.

Working with Earth Fault Protection System

The star connected side is protected by a restricted earth fault protection shown in the
figure below.
https://circuitglobe.com/restricted-earth-fault-protection.html 2/9
4/26/2020 Restricted Earth Fault Protection System - Explanation & Working - Circuit Globe

Let F1 be the external fault occurs in the network. This fault induces the I1 and I2 current
which flows in the secondary of the CTs. The resultant current of the I1 and I2 becomes
zero. When the fault occurs inside the protective zone say F2, then only current I2 exist,
and I1 is neglected. The current I2 passes through the earth fault relay. The earth fault
relay operates only for the internal fault of the protective zone.

The earth fault relay must be very sensitive for sensing the fault. The relay is designed
for sensing the fault current which is 15% more than that of the rated winding
current. Such settings protect a restricted portion of the winding. Hence the name
restricted earth fault protection.

https://circuitglobe.com/restricted-earth-fault-protection.html 3/9
4/26/2020 Restricted Earth Fault Protection System - Explanation & Working - Circuit Globe

The stabilising current is connected in series with the relay for avoiding the magnetising
inrush current.

Related Terms:
1. Balanced Earth Fault Protection
2. Rotor Earth Fault Protection
3. Differential Protection of a Transformer
4. Protection Zone in Power System
5. Differential Protection of a Generator

5 Comments

silas sibanda
January 4, 2017 at 8:21 am
Reply

good explanation

Haritha
October 5, 2018 at 4:36 am
Reply

What is the case of i1 current??it will goes through earth??

https://circuitglobe.com/restricted-earth-fault-protection.html 4/9

Вам также может понравиться