SHEET

DRAWING TITLE DRAWING NO SCALE REVISI REMARK


NO
00 DRAWING LIST 00 NTS 0

01 EXISTING LAYOUT 2ND FLOOR 01 NTS 0

02 PROPOSED LAYOUT 2ND FLOOR 02 NTS 0

03 PROPOSED LAYOUT NEW SERVER ROOM 03 NTS 0

04 TRAY LAYOUT 04 NTS 0

05 RACK LAYOUT 05 NTS 0

06 ELECTRICAL LAYOUT 06 NTS 0

07 MECHANICAL AND ELECTRICAL LAYOUT 07 NTS 0

08 SECTION A 08 NTS 0

09 SECTION B 09 NTS 0

10 SECTION C 10 NTS 0

11 SECTION D 11 NTS 0

12 DETAIL PENULANGAN PARTISI 12 NTS 0

13 PANEL MDP 13 NTS 0

14 PANEL DCPDB 14 NTS 0

15 WIRING DIAGRAM MDP 15 NTS 0

16 WIRING DIAGRAM ACPDB 16 NTS 0

17 WIRING DIAGRAM DCPDB 17 NTS 0

18 WIRING DIAGRAM PANEL ALARM 18 NTS 0

19 ALARM SYSTEM AND DC FAN CONTROL 19 NTS 0


4500
2250 2250

1185
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

4040
No. DATE REVISION SIGN

4380
RUKO RUKO RUKO

15000
SEBELAH SEBELAH SEBELAH

AC 2
OWNER
PT. MORA TELEMATIKA INDONESIA

NITTAN
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME
LANTAI
4380

KERAMIK

4860
UJB UPGRADE
(SALATIGA)

DRAWING TITLE
1015

AC 1

SCALE NTS FIRST DRAWING


2550
DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
- EXISTING LAYOUT 2nd FLOOR
F. CHOTIMAH INF
7200

CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

JL.OSAMALIKI MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
4500
2250 2250

1185
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

4040
No. DATE REVISION SIGN

4380
RUKO RUKO

15000
SEBELAH SEBELAH

THE DOOR IS MOVED TO


NEW SERVER ROOM
AIR INLET
IS MOVED
TO SIDE

AC 2
AIR 2 IS MOVED HOLE FOR OWNER
TO UNDER AC 1 TRAY FROM
EXISTING
PT. MORA TELEMATIKA INDONESIA

NITTAN
SHELTER TO
NEW SHELTER
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

LANTAI PROJECT NAME


4380

KERAMIK

4860
UJB UPGRADE
(SALATIGA)

DRAWING TITLE
1015

AC 1

SCALE NTS FIRST DRAWING


2550
DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
- PROPOSED LAYOUT 2nd FLOOR
F. CHOTIMAH INF
7200

CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

JL.OSAMALIKI MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

THE DOOR IS MOVED TO


No. DATE REVISION SIGN

NEW SERVER ROOM


AC 1 AC 2

AC 2
AIR 2 IS MOVED HOLE FOR
TO UNDER AC 1 TRAY FROM
EXISTING

NITTAN
SHELTER TO
NEW SHELTER
OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
AC 1 APPROVAL BY
ADI SUSANTO INF
DRAWING No

- PROPOSED LAYOUT NEW SERVER ROOM MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

AC 1 AC 2

HOLE FOR
TRAY FROM
EXISTING
SHELTER TO
NEW SHELTER

NITTAN
OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
AC 1 & 2 APPROVAL BY
ADI SUSANTO INF
DRAWING No

- TRAY LAYOUT
MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

AC 1 AC 2

HOLE FOR
TRAY FROM
EXISTING
SHELTER TO
NEW SHELTER

NITTAN
OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
AC 1 & 2
ADI SUSANTO INF
DRAWING No

- RACK LAYOUT MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
HD

SD REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

SD HD

No. DATE REVISION SIGN

AC 1 AC 2

HOLE FOR
TRAY FROM
EXISTING
SHELTER TO
NEW SHELTER

NITTAN
OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
AC 1 & 2
ADI SUSANTO INF
DRAWING No

- ELECTRICAL LAYOUT MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
HD

SD REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

SD HD

No. DATE REVISION SIGN

AC 1 AC 2

HOLE FOR
TRAY FROM
EXISTING
SHELTER TO
NEW SHELTER

NITTAN
OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
AC 1 & 2 ADI SUSANTO INF
DRAWING No

MECHANICAL AND ELECTRICAL LAYOUT MTI-INF-UJB UPGRADE-SALATIGA


-
SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF

- SECTION A-A IMAM SANTOSO


CHECK BY
INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
- SECTION B-B F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE

- SECTION C-C F. CHOTIMAH INF


CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE

SECTION D-D
F. CHOTIMAH INF
- CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

- DETAIL PENULANGAN DEPAN - DETAIL PENULANGAN SAMPING

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No
- DETAIL PENULANGAN BELAKANG
MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

L3 L2 L1 N

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

300.0000
UJB UPGRADE
(SALATIGA)
60.0000

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
- PANEL MDP DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

250.0000

UJB UPGRADE
(SALATIGA)
60.0000

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
- PANEL DCPDB ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
- WIRING DIAGRAM MDP DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
IMAM SANTOSO INF
- WIRING DIAGRAM ACPDB APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

No. DATE REVISION SIGN

OWNER
PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882

PROJECT NAME

UJB UPGRADE
(SALATIGA)

DRAWING TITLE

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
CHECK BY
- WIRING DIAGRAM DCPDB IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
ACPDB
L.1 L.2 L.3

FAP ON REMARKS
SMOKE
DETEKTOR NOTE:
GENSET
1 2 3
( SD ) 1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

R.220
ACPDB

TEM. SUHU
GROUNDING BAR

R / L.1
PANEL ALARM
S / L.2
MERAH
T / L.3

L
L
L
L
N
8 4 8 4 8 4
FUSE 5A FUSE 5A FUSE 5A
K 1A K 2A K 3A TO LSA KRONE (POWER ALRM)

ARRESTER 13 13 13 12 12 12
K 1A K 2A K 3A
DOOR OPEN
14 14 14
C NC
HEAT DETEKTOR
( HD )

TERMINAL BLOCK WIRING DIAGRAM POWER ALARM ACPDB


NTS No. DATE REVISION SIGN
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
DOOR OPEN
DOOR OPEN
L-1
L-1

SPARE - 1
SPARE - 1
FAP ON
FAP ON
SUHU
SUHU

SPARE - 2
SPARE - 2
GENSET
GENSET
ARRESTER
ARRESTER
-2
-2
-3
-3

WIRING DIAGRAM RED BOX


NTS

WIRING DIAGRAM RELAY POWER ALARM & WIRING DIAGRAM ALARM

OWNER
TO LSA KRONE (POWER ALARM) 1 1
PLN POWER PT. MORA TELEMATIKA INDONESIA
Gedung Grha9, 4th floor
2 2
HIGH TEMPERATURE JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
3 3 http://www.moratelindo.co.id
AC-1
Tel:+62-21-3157533 - Fax:+62-21-3142882
TO ALARM TERMINAL

4 4
HEAT DETECTOR
PROJECT NAME

ALARM BOX / LSA


K 1A K 2A K 3A 5 5
SMOKE DETECTOR
6 6
DOOR OPEN ACTIVE
UJB UPGRADE
7 7
TO PHASE R RECTIFIER (GENERAL ALARM) (SALATIGA)
8 8
BATERY DISCHARGE ALARM
TO PHASE S
9 9
AC-2
DRAWING TITLE
TO PHASE T
10 10
SPARE

WIRING DIAGRAM RELAY POWER ALARM


WIRING DIAGRAM ALARM

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE
F. CHOTIMAH INF
- DETAIL WIRING DIAGRAM PANEL ALARM CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET

-
REMARKS

NOTE:
1. THE DRAWING SHOULD NOT BE SCALED. ALL MEASUREMENT SHALL BE
CONFIRMED ON SITE
2. ALL MEASUREMENTS IN MM UNLESS OTHERWISE STATED.

(-)

1
SMOKE HEAT
DETECTOR DETECTOR
2
8 4
2
- 3 4 8 4
K 6A TO LSA
FROM ACPDB POWER SUPPLY Indicator 13 - 1
Lamp K 5A TO LSA 13 -
220 V AC / DC
+ K 5A K 6A 12
Indicator
14 + 14 +
Lamp 12

RESET SWITCH
(+)
No. DATE REVISION SIGN

SMOKE DETECTOR RESET ALARM HEAT DETECTOR


NTS NTS

( - ) 48V DC

8 4

K 1A T THERMOSTAT

NC 12 OWNER
TO LSA KRONE PCM 0.6 mm NO
PT. MORA TELEMATIKA INDONESIA
8 4 Gedung Grha9, 4th floor
RELAY 48V JL. Panataran No.9 Proklamasi
Jakarta Pusat 10320
K 4A TO LSA http://www.moratelindo.co.id
Tel:+62-21-3157533 - Fax:+62-21-3142882
NYA 1x2,5 mm BLUE 1 2 13 -
THERMOSTAT DC
FROM RECTIFIER ( - ) PROJECT NAME
K 4A FAN 12
14 +
NYA 1x2,5 mm RED UJB UPGRADE
FROM RECTIFIER ( + ) (+) (SALATIGA)
TO DC FAN
DRAWING TITLE

WIRING DIAGRAM CONTROL EXHAUST FAN DC


TEMPERATURE SENSOR AND DC FAN CONTROLER NTS
NTS

SCALE NTS FIRST DRAWING


DRAWING BY INF
DESIGN BY
NAME DIVISION SIGN & DATE

ALARM SYSTEM AND DC FAN CONTROL F. CHOTIMAH INF

NTS CHECK BY
IMAM SANTOSO INF
APPROVAL BY
ADI SUSANTO INF
DRAWING No

MTI-INF-UJB UPGRADE-SALATIGA

SHEET No. TOTAL SHEET