Data Sheet Cover Sheet

Client Data Sheet Number Rev.


Data Sheet Title HV LIVE TANK CIRCUIT BREAKER

Note: Please insert the attached NEW / REVISED Data Sheet(s) in your File Copy, and
DESTROY ALL SUPERSEDED PAGES
Prepared Checked Approved
Date Date Date

Include in This
Sheet No Revision Description Revision Status
Issue

Copyright 2014 by Jacobs Engineering Group Inc. 473779455.xls.xls


Page 1 of 4
#NAME?

#NAME? DOC NO REV

#NAME? #NAME? ###


#NAME?
EQUIPMENT TAGS:
SERVICE DESCRIPTION: HV Live Tank Circuit Breaker
CLIENT: #NAME? PURCHASER:
PROJECT TITLE: #NAME? PROJECT NUMBER: #NAME?
REQUISITION NUMBER: XXXXX-XXXX-33011
ITEM DESCRIPTION UNIT PURCHASER VENDOR

1.0 GENERAL
1.1 Manufacturer - VTS
1.2 Manufacturer Location - VTS
1.3 Model - VTS
1.4 Design Standard - IEC / GOST
1.5 Technical Specification -
1.6 Single Line Diagram
1.7 Wiring Specification - VTS
1.8 Arrangement/Detail Drawing
1.9 Design Life Years 40
1.10
2.0 SERVICE CONDITIONS
2.1 Site Conditions Specification
2.2 Altitude Above Sea Level m <1000m
2.3 Minimum Ambient Temperature o
C
2.4 Maximum Ambient Temperature o
C
2.5 Design Ambient Temperature o
C
2.6 Seismic Condition -
2.7 Surface Finishing Specification -
2.8 Location - Outdoor
2.9 Environment - Corrosive, snow, ice
2.10 Design Life - 40 years
2.11
3.0 Performance Data
3.1 Nominal Voltage kV
3.2 Highest Voltage kV
3.3 Rated Frequency Hz 50
3.4 Rated Normal Current A 2000
3.5 Operation 1 Pole / 3 Pole
3.6 System Earthing - Solid
3.7 Rated Lightning Impulse Withstand Voltage kVp VTS
3.8 Rated Short Term Power Frequency Withstand Voltage kV VTS
3.9 Rated Switching Impulse Withstand Voltage (relevant above 300kV)
3.10 Rated Operating Sequence - O‑0.3s‑CO‑1min-CO
3.11 First-Pole-to-Clear Factor - 1.5
3.12 Short Circuit Making and Breaking Capacity: -
3.13 Rated Symmetrical Short Circuit Breaking Current kA 31.5
3.14 Rated Duration of Short Circuits s 3
3.15 Rated Asymmetrical Peak Short Circuit Breaking Current kA VTS
3.16 Maximum DC component kA VTS
3.17 Maximum Break Time at Rated Values ms VTS
3.18 Rated Short Circuit Making Current kA VTS
3.19 Rated Out-of-Phase Breaking Current kA VTS
3.20 Rated Line-Charging Breaking Current A VTS
3.21 Rated Small Inductive Breaking Current A VTS
Max Permissible Switching Over voltage when Line Charging, Cable Charging, Capacitor Bank and Small
3.22
Inductive Current pu VTS
3.23 Rated Operating Times:
3.24 Opening Time/tolerance ms VTS
3.25 Closing Time / Tolerance ms VTS
3.26 Total Short Circuit Break Time ms VTS
3.27
3.28 Rated Supply Voltage of Charging Motor Vdc 110
3.29 Rated Supply Voltage of Control Circuits Including Shunt Closing and Opening Releases (<1kW) Vdc 110
3.30 Rated Supply Voltage of Auxiliary Contacts and Associated Circuitry for use by the Purchaser Vdc 110
3.31 Rated Supply Voltage of Anti-Condensation Heater and Associated Circuitry Vac 220
3.32 Insulation Type SF6 VTS
3.33 Maximum Temperature Rise at Rated Current o
C VTS
3.34 Radio Interference Voltage (RIV) micro V <2500
3.35
3.36
3.37
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?

Copyright 2014 by Jacobs Engineering Group Inc. 473779455.xls.xls


Page 2 of 4
#NAME?

#NAME? DOC NO REV

#NAME? #NAME? ###


#NAME?
EQUIPMENT TAGS:
SERVICE DESCRIPTION: HV Live Tank Circuit Breaker
CLIENT: #NAME? PURCHASER:
PROJECT TITLE: #NAME? PROJECT NUMBER: #NAME?
REQUISITION NUMBER: XXXXX-XXXX-33011
ITEM DESCRIPTION UNIT PURCHASER VENDOR

Construction Requirements
#REF! Number of Poles qty 3
#REF! Type of Circuit Breaker - Live Tank
#REF! Steel Supporting Structure Included Yes / No Yes
#REF! Steel Supporting Structure Material - Hot dip galvanised
#REF! Three Pole Rapid Auto-Reclosing Yes / No TBC
#REF! Main Contact Material Yes/No VTS
#REF! Local Open/Close Test Pushbuttons Yes / No Yes
#REF! Remote electrical closing and opening Yes / No Yes
#REF! Number of Closing Coils / power consumption -/W 1 / VTS
#REF! Number of Shunt Trip Coils / power consumption -/W 2 / VTS
#REF! Mechanical indication Open Yes / No Yes
#REF! Mechanical indication Close Yes / No Yes
#REF! Indicator fitted showing springs fully charged/discharged Yes / No Yes
#REF! Energy Storage Method - Spring
#REF! Energy Storage Quantity No of Operations VTS
#REF! Electrical anti-pumping device to prevent immediate reclosure when tripped Yes / No Yes
#REF! Non-Resettable Counter Yes / No Yes
#REF! Non-Resettable Counter Manufacturer VTS
#REF! Drain/Sample Valve Type (on oil and air chambers) Yes / No Yes
#REF! Level Gauge/Indicator Type (on Lubricating Oil Chambers/Reservoirs) Yes / No Yes
#REF! Level Gauge/Indicator Manufacturer - VTS
#REF! Pressure relief device type - VTS
#REF! Anti-condensation heater installed Yes / No VTS
#REF! Anti-condensation heater power W VTS
#REF! Nominal Operating and Minimum SF6 Gas Pressure MPa/MPa VTS
#REF! Gas Pressure Monitoring Device Yes / No Yes
#REF! SF6 Gas Pressure (Lockout) MPa VTS
#REF! SF6 Gas Pressure (Alarm) Yes / No Yes
#REF! Pole Position Discrepancy Trip Yes / No VTS
#REF! Normally Open Auxiliary Contacts qty 6
#REF! Normally Closed Auxiliary Contacts qty 6
#REF! Test Control Interface Yes / No Yes
#REF! Cubicle Heater Power W VTS
#REF! Circuit Breaker Local Control and Junction Box Yes / No Yes
#REF! Circuit Breaker Local Control and Junction Box Material 316 SS
#REF! Circuit Breaker Local Control and Junction Box Ingress Protection IP 65
#REF! Circuit Breaker Local Control and Junction Box Heater Yes / No & W Yes
#REF! Local Control Panel Glandplate Material and thickness Al, 3mm
#REF! Local Control Panel Cable Entry Bottom
#REF! Circuit Breaker Remote Control Panel Yes / No Yes
#REF! Circuit Breaker Remote Control Panel Material Painted Mild Steel
4.42 Circuit Breaker Remote Control Panel Ingress Protection IP 56
4.43 Control Panel Glandplate Material and thickness Al, 3mm
4.44 Control Panel Cable Entry Bottom
4.45 Minimum Clearance in Air: - VTS
4.46 Between Poles mm VTS
4.47 Phase to earth mm VTS
4.48 Phase Mounting Centres mm VTS
4.49 Bushing / Insulators / Interrupter: - VTS
4.50 Manufacturer / Country - VTS
4.51 Material - VTS
4.52 Colour - VTS
4.53 Creepage Distance for insulators/ interrupters based on maximum system voltage mm/ kV VTS
4.54 Terminal Loads: VTS
4.55 Horizontal / Vertical /Traverse N VTS
4.56 In any Direction N VTS
4.57 Circuit Breaker Colour - RAL 7035
4.58 Number of Operations without maintenace at rated current
4.59 Structure Earthing Tags Yes/No Yes
4.60
4.61
Disc Project
REV DATE Prepared Checked DESCRIPTION
Approved Approved
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?

Copyright 2014 by Jacobs Engineering Group Inc. 473779455.xls.xls


Page 3 of 4
#NAME?

#NAME? DOC NO REV

#NAME? #NAME? ###


#NAME?
EQUIPMENT TAGS:
SERVICE DESCRIPTION: HV Live Tank Circuit Breaker
CLIENT: #NAME? PURCHASER:
PROJECT TITLE: #NAME? PROJECT NUMBER: #NAME?
REQUISITION NUMBER: XXXXX-XXXX-33011
ITEM DESCRIPTION UNIT PURCHASER VENDOR

5.0 Construction Data


5.1 Steel Support Structure - Overall Length x Width x Height mm VTS
5.2 Steel Support Structure Weight kg VTS
5.3 In-Service Dimension - Overall Length x Width x Height mm VTS
5.4 Shipping Weight kg
5.5 Shipping dimensions - Overall Length x Width x Height mm
5.6 Total Quantity of SF6 Gas kg VTS
5.7
6.0 Inspection And Testing
6.1 Type Test Certificate Yes / No Yes
6.2 Material Certificates Yes / No Yes
6.3 Routine Tests Yes / No Yes
6.4 Factory Test Certificate Yes / No Yes
6.5 Witness Testing Required Yes / No Yes
6.6
6.7
NOTES
1. Vendor to complete all empty fields or where noted as "VTS" (Vendor to State)
1. "TBC" To be confirmed

END OF EQUIPMENT DATA