CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No.

00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
A REFRIGERATION SYSTEM
1 COMPRESSOR NO.1 Suction Pressure VS Oil Pressure.

Check for leak in valve & joints remedy if necessary.

Maintain oil level in crankcase @ minimum of 1/4 in sight


glass

2 COMPRESSOR NO.2 Suction Pressure VS Oil Pressure.

Check for leak in valve & joints remedy if necessary.

Maintain oil level in crankcase @ minimum of 1/4 in sight


glass.

3 COMPRESSOR NO.3 Suction Pressure VS Oil Pressure.

Check for leak in valve & joints remedy if necessary.

Maintain oil level in crankcase @ minimum of 1/4 in sight


glass.
4 Evaporators /Valve External Inspection & leak check
Station Check Drain Pan, unclog if necessary.
5 Evaporative Condenser External inspection & Leak Check.
Check water pumps and water level.
Check gas leaks in joints, remedy if present.

Check operation of Float Valve control, remedy if not


normal.
6 Check gauges performance.

Liquid Check pressure difference. Min of .5 bar


Pump/Ammonia pump Visual inspection for physical abnormality.
SCADA monitoring and
7 Management. Check during defrosting & normal operation of evaporator.

Check levels of all pressure vessel , adjust feed setting if not


normal.

Check liquid injection controls, remedy if beyond normal.

Check all temperature sensor of all evaporator, conduct


physical inspection of beyond normal parameter noticed.
Analyse temperature curve.
Check defrost schedule setting.
Check thermostat setting, Min -22 Deg. C
8 MCC Check operating voltage and record hourly data.
Check ampere and KWHR & record hourly data.
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS

Check temp. reading of all thermometer and conduct


correction if beyond normal, Set point is -18 deg. C

Check operation in mimic diagram & perform inspection &


correction if component operation is not align w/ actual.
B OPERATIONAL SUPPORT EQUIPMENT
1 Cold Room Doors Check door handles and Opening condition.

Check operation of PRV, inspect & correct if not normal.

Check door heater condition, inspect & correct if not normal.

2 Dock levelers Check-up for abnormalities, turn around inspection.


If not in used, rest position shoul be horizontal.
3 Roll-up Door Check -up cable status for wear & tear.

Walk around inspection, check loose bolts & Screw,door


lock and handle.
C Generator Set
1.0 Generator Set STAND BY

1.1 Lubricating Check Leaks of oil in flange gasket tigthen if necessary.


Operation of oil heater.
1.2 Fuel Check level.
1.3 Battery Check connection of charger, connect if detach.
2.0 Generator Set Check operation of oil heater.
2.1 Lubricating Check oil leak and remedy if necessary.
Check hydraulic Oil Governor.
2.2 Cooling Check for leaks and remedy if nessesary.
Check radiator Air restriction.

Check hose and connection for leaks remedy if necessary.


Check Fan Hub, Drive pulley and water pump.

2.3 Air intake Check Piping and connection for leak & tighten if necessary.
2.4 Fuel Check for Leak and correct if present.

Drain sediment from tanks.


2.5 Exhaust Check for leaks and tigthen flange if necessary.

Commenced by: Noted by: LEGEND:

/ DONE
Plant Operator/Electrician Engineering & Maintenace Officer X NOT DONE
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
Signature over printed name. Signature Over Printed Name. > FOR RE SCHEDULE
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
1.0 REFRIGERATION SYSTEM
1.1 COMPRESSOR NO.1
Suction Pressure VS Oil Pressure.
Check for leak in valve & joints remedy if necessary.
Maintain oil level in crankcase @ minimum of 1/4 in sight glass
2 COMPRESSOR NO.2
Suction Pressure VS Oil Pressure.
Check for leak in valve & joints remedy if necessary.
Maintain oil level in crankcase @ minimum of 1/4 in sight glass
3 COMPRESSOR NO.3
Suction Pressure VS Oil Pressure.
Check for leak in valve & joints remedy if necessary.
Maintain oil level in crankcase @ minimum of 1/4 in sight glass
4 VALVE STATION
Check Drain Pan, unclog if necessary.
External Inspection & leak check
5 EVAPORATIVE CONDENSER 1
Check water pumps and water level.
Check gas leaks in joints, remedy if present.
Check operation of Float Valve control, remedy if not normal.
6 EVAPORATIVE CONDENSER 2
Check water pumps and water level.
Check gas leaks in joints, remedy if present.
Check operation of Float Valve control, remedy if not normal.
AMMONIA PUMP 1
6 Check gauges performance.
Check pressure difference. Min of .5 bar
Visual inspection for physical abnormality.
AMMONIA PUMP 2
Check gauges performance.
Check pressure difference. Min of .5 bar
Visual inspection for physical abnormality.
SCADA MONITORING
7 Check during defrosting & normal operation of evaporator.
Check levels of all pressure vessel , adjust feed setting if not normal.
Check liquid injection controls, remedy if beyond normal.

Check all temperature sensor of all evaporator, conduct physical inspection of beyond
normal parameter noticed.
Analyse temperature curve.
Check defrost schedule setting.
Check thermostat setting, Min -20 Deg. C
8 MCC
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
Temperature controllers
Magnetic contactor
Circuit breaker
Relay
Safety switches
B OPERATIONAL SUPPORT EQUIPMENT
1 Cold Room Doors
Check door handles and Opening condition.
Check operation of PRV, inspect & correct if not normal.
Check door heater condition, inspect & correct if not normal.
Dock levelers
2 Check-up for abnormalities, turn around inspection.
If not in used, rest position shoul be horizontal.
Roll-up Door
3 Check -up cable status for wear & tear.
Walk around inspection, check loose bolts & Screw,door lock and handle.
C Generator Set
1.0 Generator Set STAND BY

1.1 Lubricating Check Leaks of oil in flange gasket tigthen if necessary.


Operation of oil heater.
1.2 Fuel Check level.
1.3 Battery Check connection of charger, connect if detach.
2.0 Generator Set Check operation of oil heater.
2.1 Lubricating Check oil leak and remedy if necessary.
Check hydraulic Oil Governor.
2.2 Cooling Check for leaks and remedy if nessesary.
Check radiator Air restriction.

Check hose and connection for leaks remedy if necessary.


Check Fan Hub, Drive pulley and water pump.

2.3 Air intake Check Piping and connection for leak & tighten if necessary.
2.4 Fuel Check for Leak and correct if present.

Drain sediment from tanks.


2.5 Exhaust Check for leaks and tigthen flange if necessary.

Commenced by: Noted by: LEGEND:

/ DONE
Plant Operator/Electrician Engineering & Maintenace Officer X NOT DONE
Signature over printed name. Signature Over Printed Name. > FOR RE SCHEDULE
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
1.0 REFRIGERATION SYSTEM
1.1 COMPRESSOR
a) Suction Pressure VS Oil Pressure.
b) Check for leak in valve & joints remedy if necessary.
c) Maintain oil level in crankcase @ minimum of 1/4 in sight glass
COMPRESSOR NO.1
COMPRESSOR NO.2
COMPRESSOR NO.3
1.2 VALVE STATION
a) Check Drain Pan, unclog if necessary.
b) External Inspection & leak check
c) Solinoid valve function
VS 1
VS 2
VS 3
VS 4
VS 5A
VS 5B
VS 6A
VS 6B
VS 7
VS 8
VS 9
VS 10
VS 11
1.3 EVAPORATIVE CONDENSER
a) Check water pumps and water level.
b) Check gas leaks in joints, remedy if present.
c) Check operation of Float Valve control, remedy if not normal.
EVAPORATIVE CONDENSER 1
EVAPORATIVE CONDENSER 2
1.4 AMMONIA PUMP
Check water pumps and water level.
Check gas leaks in joints, remedy if present.
Check operation of Float Valve control, remedy if not normal.
AMMONIA PUMP 1
AMMONIA PUMP 2
SCADA MONITORING
7 Check defrosting schedule.
Check setting.

check updating status of data logs.


Check defrost schedule setting.
CRYSTALCOLD CHAIN CORPORATION YEAR Doc. No. EMD-F-1802 Rev. No. 00

DAILY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 REMARKS
Check thermostat setting, Min -20 Deg. C
8 MCC
Temperature controllers
Magnetic contactor
Circuit breaker
Relay
Safety switches
B OPERATIONAL SUPPORT EQUIPMENT
1 Cold Room Doors
Check door handles and Opening condition.
Check operation of PRV, inspect & correct if not normal.
Check door heater condition, inspect & correct if not normal.
Dock levelers
2 Check-up for abnormalities, turn around inspection.
If not in used, rest position shoul be horizontal.
Roll-up Door
3 Check -up cable status for wear & tear.
Walk around inspection, check loose bolts & Screw,door lock and handle.
C Generator Set

1.0 Generator Set STAND BY


1.1 Lubricating Check Leaks of oil in flange gasket tigthen if necessary.
Operation of oil heater.
1.2 Fuel Check level.
1.3 Battery Check connection of charger, connect if detach.
2.0 Generator Set Check operation of oil heater.
2.1 Lubricating Check oil leak and remedy if necessary.
Check hydraulic Oil Governor.
2.2 Cooling Check for leaks and remedy if nessesary.

Check radiator Air restriction.


Check hose and connection for leaks remedy if necessary.

Check Fan Hub, Drive pulley and water pump.


2.3 Air intake Check Piping and connection for leak & tighten if necessary.

2.4 Fuel Check for Leak and correct if present.


Drain sediment from tanks.
2.5 Exhaust Check for leaks and tigthen flange if necessary.
Noted by: LEGEND:
Commenced by:
/ DONE
Engineering & Maintenace Officer X NOT DONE
Plant Operator/Electrician Signature Over Printed Name. > FOR RE SCHEDULE
Signature over printed name.
TABLE 2
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F- 1803 Rev. No.00
WEEKLY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 1st 2nd 3rd 4th REMARKS
A REFRIGERATION SYSTEM
Check coupling bolts and retighten if necessary.
Check shaft seal for oil leak.
Lubrication oil def. Min= 1.3 bar, Max= 4.5 bar, control oil pressure dif.= 8 bar
Check oil pressure for possible strainer clogging and clean if nessesary.
1 COMPRESSOR 1 & 2 Check Unloader valve for malfunction and clogging .

Compressor 1

Compressor 2
2
Check coupling bolts and retighten if necessary.
Check shaft seal for oil leak remedy or record if necessary.
Compressor 3 Lubrication oil def. Min= 1.8 bar, Max= 4.5 bar, control oil pressure dif.= 1.8 bar
Check oil pressure for possible strainer clogging and clean if nessesary.
3 Check Unloader valve for malfunction and clogging .
Check Bleed-off rate, adjust if necessary.
4 Condenser 2 Check condenser water status, replace if necessary.
Condenser 1
5 Condenser 2
Check the operation of Auto purger.
6 Auto Purger Check for NH3 discharge, remedy if necessary.
Check level Status and adjust regulating valve if necessary.
Check gauges, Fitting, valves and grease or paint corroded parts if necessary.

Pressure Vessel Check drain pan for possible clogging and unclog if necessary.
(Intercooler, Pump Check accuracy of Liquid controller by observing actual opening and clossing of liquid
7 Separator, Liquid Reciever) injection valves.
B MECHANICAL EQUIPMENT
Check Cable alignment in pulleys and correct if necessary.
Check Door balance/alignment, correct if necessary.
Check Wire rope tansion adjust if necessary.
1 Roll-Up Door Check lower air rubber gasket for correct seat align if necessary.
Check hydraulic Hose and fitting for leaks, correct is necessary.
Check Dock leveler joints pins and shafts lubricate if necessary.

2 Dock Leveler Check internal panel board for moisture, clean and dry using Vacuum if necessary.
3 Cold Room Doors Check guide rollers to guide rail alignment, re align if necessary.
4 Plastic Curtain Replace tear and damage curtain sheets.
Check loose capscrew retighten if present.
Check leaks and remedy if necessary
5 Water Pumps. Check Motor Control Center operation.
C GENERATOR
Check engine Oil Level.
1 Lubricating Check hydraulic Governor oil level.
2 Cooling Check Coolant Level.
3 Operational Procedure No load test for 5 mins.
4 Electrical Check Battery Charging System.
5 Engine Related Check for Unusual vibration during test record & correct if necessary.
D SAFETY EQUIPMENT
Check pressure in pipe , maintain 150 PSI.
Check Water level in storm cistern Tank ( Maintain1/2 status)
Check operation of Jockey pump.
Check Control panel.
Check Leaks in pipe, valves and joint correct if present.
Check gauges condition.
1 Fire Springkler System Check Siamese twin and ensure un obstructed all the time.
Check all component are in place.
Check valve status and ensure that always operational.
2 Fire Hoses Check the unit and ensure un obstructed and in proper location.

LEGEND:

/ DONE
Commenced by: Noted by: X NOT DONE
> FOR RE SCHEDULE
TABLE 2
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F- 1803 Rev. No.00
WEEKLY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
Plant Operator/ Electrician Engineering & Maintenance Officer
Signature Over Printed Name. Signature Over Printed Name.
TABLE 2
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F- 1803 Rev. No.00
WEEKLY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018
ACTIVITY 1st 2nd 3rd 4th REMARKS
A REFRIGERATION SYSTEM
Check coupling bolts and retighten if necessary.
Check shaft seal for oil leak.
Lubrication oil def. Min= 1.3 bar, Max= 4.5 bar, control oil pressure dif.= 8 bar
Check oil pressure for possible strainer clogging and clean if nessesary.
1 Compressor 1 Check Unloader valve for malfunction and clogging .
Check coupling bolts and retighten if necessary.
Check shaft seal for oil leak
Lubrication oil def. Min= 1.3 bar, Max= 4.5 bar, control oil pressure dif.= 8 bar
Check oil pressure for possible strainer clogging and clean if nessesary.
2 Compressor 2 Check Unloader valve for malfunction and clogging .
Check coupling bolts and retighten if necessary.
Check shaft seal for oil leak remedy or record if necessary.
Lubrication oil def. Min= 1.8 bar, Max= 4.5 bar, control oil pressure dif.= 1.8 bar
Check oil pressure for possible strainer clogging and clean if nessesary.
3 Compressor 3 Check Unloader valve for malfunction and clogging .
Check Bleed-off rate, adjust if necessary.
4 Condenser 1 Check condenser water status, replace if necessary.
Check Bleed-off rate, adjust if necessary.
5 Condenser 2 Check condenser water status, replace if necessary.
Check the operation of Auto purger.
6 Auto Purger Check for NH3 discharge, remedy if necessary.
Check level Status and adjust regulating valve if necessary.
Check gauges, Fitting, valves and grease or paint corroded parts if necessary.

Pressure Vessel Check drain pan for possible clogging and unclog if necessary.
(Intercooler, Pump Check accuracy of Liquid controller by observing actual opening and clossing of liquid
7 Separator, Liquid Reciever) injection valves.
B MECHANICAL EQUIPMENT
Check Cable alignment in pulleys and correct if necessary.
Check Door balance/alignment, correct if necessary.
Check Wire rope tansion adjust if necessary.
1 Roll-Up Door Check lower air rubber gasket for correct seat align if necessary.
Check hydraulic Hose and fitting for leaks, correct is necessary.
Check Dock leveler joints pins and shafts lubricate if necessary.

2 Dock Leveler Check internal panel board for moisture, clean and dry using Vacuum if necessary.
3 Cold Room Doors Check guide rollers to guide rail alignment, re align if necessary.
4 Plastic Curtain Replace tear and damage curtain sheets.
Check loose capscrew retighten if present.
Check leaks and remedy if necessary
5 Water Pumps. Check Motor Control Center operation.
C GENERATOR
Check engine Oil Level.
1 Lubricating Check hydraulic Governor oil level.
2 Cooling Check Coolant Level.
3 Operational Procedure No load test for 5 mins.
4 Electrical Check Battery Charging System.
5 Engine Related Check for Unusual vibration during test record & correct if necessary.
D SAFETY EQUIPMENT
Check pressure in pipe , maintain 150 PSI.
Check Water level in storm cistern Tank ( Maintain1/2 status)
Check operation of Jockey pump.
Check Control panel.
Check Leaks in pipe, valves and joint correct if present.
Check gauges condition.
1 Fire Springkler System Check Siamese twin and ensure un obstructed all the time.
Check all component are in place.
Check valve status and ensure that always operational.
2 Fire Hoses Check the unit and ensure un obstructed and in proper location.

LEGEND:

/ DONE
Commenced by: Noted by: X NOT DONE
> FOR RE SCHEDULE
TABLE 2
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F- 1803 Rev. No.00
WEEKLY - PREVENTIVE MAINTENANCE CHECKLIST MONTH Effective date: Sept. 01, 2018

Plant Operator/ Electrician Engineering & Maintenance Officer


Signature Over Printed Name. Signature Over Printed Name.
CRYSTALCOLD CHAIN CORP. Period: Doc. No.EMD-F-1804 Rev.No. 00
MONTHLY - PREVENTIVE MAINTENANCE CHECKLIST YEAR 2018 Effective date: Sept. 01, 2018
ACTIVITY JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC REMARKS
A REFRIGERATION SYSTEM
1 Check Insulation Resistance of motor when stand by and
Compressor 1 record data.

Visual sampling of oil.


2
Check Insulation Resistance of motor when stand by and
Compressor 2 record data.

Visual sampling of oil.


3
Check Insulation Resistance of motor when stand by and
Compressor 3 record data.

Visual sampling of oil.


4 Evaporators &
valve station De-Ice piping if necessary.

Check regulating valve and adjust if necessary.

Check solinoid coil operation during cooling and


defrosting.
5
Ammonia pump Apply grease filling subject to ice buil-up.

Check Insulation resistance during stand dy.

Check Bracket and tigthen if necessary.

Clean rusted parts and repaint if necessary.


8

Isolating Valve
(suction valve,
discharge valve,
Intremediate Check leaks tighten packing nuts and apply grease if
valve,King valve) necessary.
9
Auto Purger Cheak leaks

Check and calibrate and adjust the control if necessary.


10
MCC Check and record the supply voltage.

Check setting of timer and overload relay.


11
Intercooler Drain oil pot.

Check Isolation valve, Drain valve & relief valve grease if


necessary.
12
Drain oil pot.

Pump separator Check Isolation valve, Drain valve & relief valve grease if
-33 necessary.
13
Drain oil pot.

Pump separator Check Isolation valve, Drain valve & relief valve grease if
-42 necessary.

B MECHANICAL EQUIPMENT
1 Roll-Up Door Check and apply Low temp. Grease to wire ropes.

Check and retigthen loose Bolts.

Check seat status of Air gasket, correct if necessary.

2 Cold Room Doors Check Door alignment, re align if necessary.


Check & inspect pressure relief valve physical condition
grease/paint if neccessary.

3 Dock Leveler Check Power supply @ load side, arrange if necessary.

Check controller for possible moisture accumulation, dry if


necessary.

Check physical appearance and repair, stitch or remedy if


4 Dock Shelter physical damage is present.

5 Transfer Pump Check vibration and body temp.

Check insulation resistance ,Min. of 5 mega Ohm.

Check terminal box, sealed if necessary.


6 Plastic Curtain Check torn curtain leaves,replace if neccesary.

C GENERATOR
Fuel Check hose and connection.

Check Radiator Air restriction.


Check belt condition and tension, apply belt dressing of
necessary.

Check fuel level, refil if necessary.


3 Exhaust Check For leaks.

Check for Exhaust Restriction.

Check line for Condensate trap.


CRYSTALCOLD CHAIN CORP. Period: Doc. No.EMD-F-1804 Rev.No. 00
MONTHLY - PREVENTIVE MAINTENANCE CHECKLIST YEAR 2018 Effective date: Sept. 01, 2018
ACTIVITY JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC REMARKS

4 Electrical Check battery electrolite level and specific gravity.

5 Main Generator Check Air inlet and outlet for restriction.

Operational Test w/ load not less than 20 %, Ensure service tool


6 Procedure availability.

D FIRE PROTECTION SYSTEM


1 Check gauges.
Fire Sprinkler
System Check alarm valve status.

Check Hydraulic name plate wipe with damp cloth.

Check insulation Resistance of the fire pump and jockey


pump (must not be less than 5 mega ohm)

Test pump and hoses by actual operation.


2 Fire Extinguisher Check operation of Auto switches.

Check location designation.

Conduct inspection and confirmed in the inspection sheet.

Check if operating instruction on nameplate legible and


facing outward, correct if necessary.

Examine for obvious physical damage, corrosion, leakage


or clog nozzle.

Pressure gauge reading must be in operable condition.

Condition of tires,wheels,carriage,nozzle ckecks (for


wheeled units).

Observe unit in operation, note any unusual noise or


vibration indoor & outdoor unit.
Check discharge temp. of Indoor & out door unit & record
data.

Conduct actual test by generating smoke in selected


Fire Alarm System smoke detector and check if fire alarm panel respond.

Check Fire alarm panel for detectors sending fault signal


and have FDAS technician check and repair the fault.

3 Check battery charging status.

LEGEND:

/ DONE
X NOT DONE
> FOR RE SCHEDULE
CRYSTALCOLD CHAIN CORP. Period: Doc. No.EMD-F-1804 Rev.No. 00
MONTHLY - PREVENTIVE MAINTENANCE CHECKLIST YEAR 2018 Effective date: Sept. 01, 2018
ACTIVITY JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC REMARKS
Commenced by: Noted by:

Plant Operator/ Electrician Engineering & Maintenance Officer


Signature Over Printed Name. Signature Over Printed Name.
TABLE 4
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F-1805 Rev. No. 00

QUARTERLY - PREVENTIVE MAINTENANCE CHECKLIST QUARTER Effective date: SEPT. 01, 2018
ACTIVITY 1ST 2ND 3RD 4TH REMARKS
A REFRIGERATION SYSTEM
1 Compressor 1 Check for leaks in joints & tigthen if necessary.
Retighten motor terminal.
Check mounting, retigthen if necessary.
2 Compressor 2 Check for leaks in joints & tigthen if necessary.
Retighten motor terminal.
Check mounting, retigthen if necessary.
3 Compressor 3 Check for leaks in joints & tigthen if necessary.
Retighten motor terminal.
Check mounting, retigthen if necessary.
Evaporators &
4 valve station Check for rust formation, repainting if necessary.
Check bracket for stability, correct if necessary.

Service the strainer EVM (NO & NC) and Solinoid valve.

5 NH3 pump Check Differential pressure, clean filter if necessary.


Retighten motor terminal

Check for rust formation, repainting if necessary

Check mounting for stability, correct if necessary.

6 Check leak in coupling, retigten bolt if necessary.

Isolating Valve
( Suction valve,
Discharge valve,
Intermediate Check leak in valve bonnet, retigthen packing gasket if
valve,King valve) necessary.
7 Auto Purger Check solinoid valve operation.
Check for rust formation repaint if necessary.

Check insulation resistance of all Fan & Pump motor and


CONDENSER record data.
Clean-up Body and Coil using pressure washer.

Inspect belts for proper tension and wear (if belts are
replaced, record belt type and replacement date on
unit)

Observe unit in operation, note any unusual noise or


vibration.

Provide lubrication to pillow block bearing motor


bearing (if applicable) and record the activity.

Inspect fan and motor pulleys for proper alignment.


Inspect all fan wiring for deterioration.
Ensure tightness of all electrical connections
Inspect motor starter/control center.
Inspect electrical contact surfaces.
8 Inspect fan assembly.

Inspect unit for unusual noise and/or vibration, ensure


9 PUMPS that it is in good working order.
Provide lubrication to motor bearing and pump bearing
as required.
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F-1805 Rev. No. 00

QUARTERLY - PREVENTIVE MAINTENANCE CHECKLIST QUARTER Effective date: SEPT. 01, 2018
ACTIVITY 1ST 2ND 3RD 4TH REMARKS

If unit is not running or an identified problem requires


the unit to be serviced, perform ALL NonCritical Tasks
listed below.
Inspect seals and packing, tighten or replace as
necessary.
Lubricate impeller shaft bearings.
Inspect motor and pump alignment.
B Split System Air Conditioner

Indoor & Inspect all wiring for deterioration and tighten electrical
1 Outdoor contacts. Check for corrosion and cleanliness.

Observe unit in operation, note any unusual noise or


vibration

Coduct Servicing to indoor & outdoor unit operating 24


hour per day.
Inspect and clean condenser coils. Remove accumulated
dirt and debris.
Inspect mounting bolts and tighten if needed.
Verify unit is properly grounded.
Check for refrigerant leaks and repair as necessary.
Check refrigerant levels and recharge if needed.
Run machine, check action of controls, relays, switches
and safeties or limit switches.

Verify unit operates at the proper suction and discharge


pressures. Measure and record each.

Verify unit operates at proper discharge temperature,


measure and record temperature difference across the
coil.
C GENERATOR
1 Lubricating Change full flow filter.
Change By-pass filter.
Change engine oil.
Change hydraulic Governor oil refil of necessary.
2 Cooling Check heat exchanger, Zinc Anode plugs.
3 Fuel Check governor linkage.
Check fuel lines and connection.
Drain sediment from tank.
Change fuel filter.
4 Electrical Check Safety control and alarm.
5 Intake Clean or change air cleaner element.

6 Main Generator Measure and record Generator winding resistance.


Check and Clean Generator from foreign particles with
vacuum cleaner.
7 Switch gear Check Power distribution and wiring.
Check Power Circuit Breaker.
Check transfer switch.
Clean terminal through vacuum cleaner.
Check transfer switch.

LEGEND:

/ DONE
X NOT DONE
Commenced by: Noted by: > FOR RE SCHEDULE
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No.EMD-F-1805 Rev. No. 00

QUARTERLY - PREVENTIVE MAINTENANCE CHECKLIST QUARTER Effective date: SEPT. 01, 2018
ACTIVITY 1ST 2ND 3RD 4TH REMARKS

Plant Operator/ Electrician Engineering & Maintenance Officer


Signature Over Printed Name Signature Over Printed Name
TABLE 5

CRYSTALCOLD CHAIN CORPORATION Year Doc. No. EMD-F-1806 Rev. No. 00

SEMI-ANNUALLY - PREVENTIVE MAINTENANCE CHECKLIST Period Effective date: SEPT. 01, 2018
ACTIVITY 1st 2nd REMARKS
A REFRIGERATION SYSTEM

Check for Change Oil interval, Change oil if necessary.

Check Cut-outs & Safety switches.

1 COMPRESSOR 1 Check performance of pressure transmitter/ Calibrate if necessary.

Check for Change Oil interval, Change oil if necessary.

Check Cut-outs & Safety switches.

2 COMPRESSOR 2 Check performance of pressure transmitter/ Calibrate if necessary.

Check for Change Oil interval, Change oil if necessary.

Check Cut-outs & Safety switches.

3 COMPRESSOR 3 Check performance of pressure transmitter/ Calibrate if necessary.

Check & straighten coil fins if necessary.

Clean and flush strainers.

Clean entire body with damp cloth, motor and fan assembly and coils with
pressure washer.

Retighten motor terminal & check & record insulation resistance of fan
motor.

4 UNIT COOLERS Inspect unit for unusual noise and/or vibration correct if present.

Check & test vessel high level cut out switch.

Check operation of feeder valve, solinoid and motorized valve adjust if


necessary.

PRESSURE VESSEL Check temperature controls calibrate if necessary.


(Intercooler, Pump
5 Separator) Inspect and clean terminal box and LCC switches w/ vacuum.

Check & inspection all electrical control terminals and connections by a


qualified/competent electrician.
ELECTRICAL
COMPONENTS (Primary Vacuum foreign particles.
& Secondary circuit
breaker,Transformer, Retigthen terminal.
control center, junction
6 boxes) Check Setting of relays & timer.

B GENERATOR

Change Full flow Filter if required.

Change By-pass Filter if required base on running hour (RH).

Change Engine Oil if necessary base on running hours (Pls. see manual)

1 Lubricating Change hydraulic Governor oil.

2 Cooling Change DCA water filter

C SUPPORT EQUIPMENT

Check Hydraulic telescopic for leak ,replace gasket if necessary.

Check Insulation resistance of motor, Min. 5 Mega ohm.

1 DOCK LEVELER Check and Lubricate Lip swing.

Replace Lifting cable if necessary.

Check and replace lock and handle.

2 ROLL-UP DOOR Check and replace Air gasket if necessary.

Check Control center for condensater trap, drain if present.

3 COLD ROOM -PRV Check opening & closing status.

Check hanger, repair if necessary.

4 PLASTIC CURTAIN Check & tigthen loose Screws.

LEGEND:

/ DONE
X NOT DONE
> FOR RE SCHEDULE
Commenced by: Noted by:

Plant Operator/ Electrician Engineering & Maintenance Officer


Signature Over Printed Name Signature Over Printed Name
TABLE 6

CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No. EMD - F-1807 Rev. No. 00

ANNUALLY - PREVENTIVE MAINTENANCE CHECKLIST. Schedule Effective date: SEPT. 1, 2018


ACTIVITY MONTH Next REMARKS

A REFRIGERATION SYSTEM

Check for schedule of top overhaul & internal


service, commence service as per manufacturers
recommendation.
Check parameter of drive motor for possible
1 COMPRESSOR 1 reconditioning.
Repaint compressor & motor body.
Inspect bolt & mounting grease if necessary.

Open coupling cover and check alignment, re


align if necessary.

Check for schedule of top overhaul & internal


service, commence service as per manufacturers
2 COMPRESSOR 2 recommendation.

Check parameter of drive motor for possible


reconditioning.
Repaint compressor & motor body.
Inspect bolt & mounting grease if necessary.
Open coupling cover and check alignment, re
align if necessary.

Check for schedule of top overhaul & internal


service, commence service as per manufacturers
3 COMPRESSOR 3 recommendation.

Check parameter of drive motor for possible


reconditioning.
Repaint compressor & motor body.
Inspect bolt & mounting grease if necessary.

Check if charge is sufficient, Fill-up all vessel @


least 45 %, if level @ liquid reciever below 1/4
4 AMMONIA CHARGE fill-up NH3.
Open coupling cover and check alignment, re
align if necessary.
5 COLD ROOM PRV Inspect pilot positioner.
Check for Air during close position.
Inspect condition of valve actuator.

Verify that the control valve is providing tight


shutoff of the controlled medium.

Operate the controls over the full range of


modulation to ensure proper operation of the
valve and actuator.

Inspect mounting bolts and vibration isolators of


6 PUMPS the pump under load conditions

Start and stop pump, noting any vibration and


overall performance.

Inspect drive shaft coupling and re- align if


necessary.

ELECTRICAL CABINET
7 & POWER SUPPLY Check grounding must not greater than 24 ohms.

Check buss bar color, have electrical engineer


/competent eletrician inspect if color is found
abnormal.

Check Buss bar temp. using thermal scanner,


correct if temp. is beyond normal.
8 CONDENSER Repaint condenser body, internal & External.
General Inspection of unit
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No. EMD - F-1807 Rev. No. 00

ANNUALLY - PREVENTIVE MAINTENANCE CHECKLIST. Schedule Effective date: SEPT. 1, 2018


ACTIVITY MONTH Next REMARKS

Use pressurized spray for coil cleaning, Used de-


scaling chemical for coil cleaning if necessary.
Repaint Condenser catwalk.
Check alignment of centrifugal fan main shaft, re-
align if necessary.
Pressure wash drift eleminator.

Check Pillow block bearing status clean & grease


& replace if required.

Check mounting screw, re- tighthen & grease if


necessary
B SPLIT SYSTEM AIR CONDITIONING

1 Check refrigerant levels and re-charge if needed.

Check mounting bracket and tigten if necessary.


Check operation and re-process the system if
necessary.
C GENERATOR
1 Cooling Clean cooling system.
Check Fan hub, drive pulley and water pump.
2 Fuel Change float tank breather if necessary.

Check Torque manifold & Turbo charger


3 Exhaust capscrew & retigthen.

Clean engine w/ vacuum & wash with soap and


water.
4 Engine Related Tighten mounting hardware.
5 Main Generator Check winding & electrical Connection.
Check operation of Generator heater strips if
installed.
Grease-up bearing of Generator and Radiator fan
bearing.

Measure and record generator winding


Resistance.
D FIRE PROTECTION EQUIPMENT
Fire Sprinkler
1 System Check & certified by Authorized Engineers & BFP.
Check Pre-action/deludge valve.
Check Backflow prevention component.
Check main drain.
Check water flow alarm if installed.
Check gauges replace if damage.
Check alarm device, repair or replace if
functioning.
Check hangers & bracing.

Check pipes and fittings specially in joints and


coupling retigthen if leaking.

Check control valve, repair if found or replace if


found malfunction.
2 Fire Extinguisher Refill content.
Check Bracket for stability.
Prepare New Inspection Checklist.

LEGEND:
CRYSTALCOLD CHAIN CORPORATION YEAR 2018 Doc. No. EMD - F-1807 Rev. No. 00

ANNUALLY - PREVENTIVE MAINTENANCE CHECKLIST. Schedule Effective date: SEPT. 1, 2018


ACTIVITY MONTH Next REMARKS
/ DONE
Commenced by: Noted by: X NOT DONE
> FOR RE SCHEDULE

Plant Operator/ Electrician Engineering & Maintenance Officer


Signature Over Printed Name Signature Over Printed Name