Академический Документы
Профессиональный Документы
Культура Документы
PAGE
A Pillar Hydrant 1
E Water Demand 5
A Pillar Hydrant
1 Equipment
2 way Pillar Hydrant
Model : 2-Ways with Self-Pressure Regulating Landing Valve
Quantity : 6 Sets Pillar Hydrant
2 Design Data
Minimum required pressure at
: 6.9 Bar
pillar hydrant (P)
Duration = 60 minutes
1
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
2 Design Data
Width = 5.70 m (D)
Length = 7.00 m (L)
Surface Area = 39.90 sq.m
Minimum Application Rate = 6.50 lit/ min/ m.sq (Refer to NFPA-11 Table 3-8. 1)
Discharge Duration = 30 minutes (Refer to NFPA-11 Table 3-8. 1)
5 Water Requirement
Water Flowrate Required for
= Ff x (1 - FC)
Foam Station
= 251.57 lit/min
Water Requirement = 7547.09 liters
2
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
Duration = 60 minutes
3
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
c Hose Reel
1 Hose Stream Demand = 120 lit/ min
4
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
E Water Demand
Calculation based on the fact that fire will only occur in a single area and consider the following scenario:
1 Hydrant and Automated Fire Water Monitor
a Scenario 1
2 pillar hydrants operating at the same time = 163,440.00 liters
b Scenario 2
2 automated fire water monitor operating at the same time = 180,000.00 liters
c Scenario 3
1 pillar hydrant and 1 automated fire water monitor = 171,720.00 liters
operating at the same time
Taking into consideration, a min. supply of 1200L/min of water for 60 min = 72,000.00 liters
5
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
A) Design Criteria
1) Design Flow : 3,300 lit/min
2) Pd, Design Pressure at most : 6.9 bars
3) Pipe Work Selection : 150mm (ID) GI 'C' Pipe BS 1387
4) Serving Location : From GF Fire Pump Room to Pillar Hydrants (furthest point)
B) Input Data - Static Pressure, Travel Distance and Losses Due to Friction
Note: Consideration for Most Remote End Hydrant
1) Hs, Static Height Against = 3.0 m
2) Hd, Design Pressure Equivalent = 69.0 m
3) Pipe Fittings and Valves Details:
Frictional Equivalent
Resistance Length
Size (mm) Fittings (m) Qty (m)
150 90 deg Elbow 4.30 11 47.30
150 45 deg Elbow 2.30 0 0.00
150 Equal Tee (Branch) 8.61 3 25.83
150 Equal Tee (Run) 1.13 3 3.39
150 Gate Valve (Flanged) 1.13 3 3.39
150 Check Valve (Wafer Type) 7.17 1 7.17
Total Equivalent Pipe Length (m): 87.08
6
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
C) Output Data - Pressure Required
Note: Consideration for Most Highiest and Remote Far End Hose Reel Station
1) Pressure Require, Preq = Hd + H s + H f
= 74.4 m
2) Suggested Pump Head = 75.0 m
D) Pump Selection
1) Duty Pump:
Type : Centrifugal, End Suction
Drive : Electrical Motor
Pump Head : 75m
Flow : 3300lpm
Quantity : 1 nos
2) Standby Pump:
Type : Centrifugal, End Suction
Drive : Diesel Engine
Pump Head : 75m
Flow : 3300lpm
Quantity : 1 nos
3) Jockey Pump:
Type : Centrifugal, Vertical Multi-Stage
Drive : Electrical Motor
Pump Head : 90m
Flow : 136lpm
Quantity : 1 nos
7
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
HYDRAULIC CALCULATION FOR
AUTOMATED FIRE WATER MONITOR
A) Design Criteria
1) Design Flow : 3,300 lit/min
2) Pd, Design Pressure at most : 10 bars
3) Pipe Work Selection : 150mm (ID) GI 'C' Pipe BS 1387
4) Serving Location : From GF Fire Pump Room to Automated Fire Water Monitor
B) Input Data - Static Pressure, Travel Distance and Losses Due to Friction
Note: Consideration for Most Remote End Automated Fire Water Monitor
1) Hs, Static Height Against = 23.0 m
2) Hd, Design Pressure Equivalent = 100.0 m
3) Pipe Fittings and Valves Details:
Frictional Equivalent
Resistance Length
Size (mm) Fittings (m) Qty (m)
150 90 deg Elbow 4.30 9 38.70
150 45 deg Elbow 2.30 0 0.00
150 Equal Tee (Branch) 8.61 1 8.61
150 Equal Tee (Run) 1.13 2 2.26
150 Gate Valve (Flanged) 1.13 3 3.39
150 Check Valve (Wafer Type) 7.17 1 7.17
Total Equivalent Pipe Length (m): 60.13
D) Pump Selection
1) Duty Pump:
Type : Centrifugal, End Suction
Drive : Electrical Motor
Pump Head : 125 m
Flow : 3300 lpm
Quantity : 1 nos
2) Standby Pump:
Type : Centrifugal, End Suction
Drive : Diesel Engine
Pump Head : 125 m
Flow : 3300 lpm
Quantity : 1 nos
3) Jockey Pump:
Type : Centrifugal, Vertical Multi-Stage
Drive : Electrical Motor
Pump Head : 150 m
Flow : 136 lpm
Quantity : 1 nos
9
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CALCULATIONS
HYDRAULIC CALCULATION FOR
HOSE REEL PUMP
A) Design Criteria
1) Design Flow : 136 lit/min
2) Pd, Design Pressure at most : 2 bars
3) Serving Location : From GF Fire Pump Room to Hose Reel on Equipment Structure Highest Level
B) Input Data - Static Pressure, Travel Distance and Losses Due to Friction
Note: Consideration for Most Remote End Hose Reel
1) Hs, Static Height Against = 38.0 m
2) Hd, Design Pressure Equivalent = 20.0 m
3) Pipe Fittings and Valves Details:
Equivalent
Length
Size (mm) Fittings L/D L (m) Qty (m)
50 90 deg Elbow 19.00 0.95 6 5.70
50 45 deg Elbow 14.00 0.70 0 0.00
50 Equal Tee (Branch) 60.00 3.00 4 12.00
50 Equal Tee (Run) 20.00 1.00 15 15.00
50 Gate Valve (Flanged) 7.50 0.38 2 0.75
50 Check Valve (Wafer Type) 420.00 21.00 1 21.00
Total Equivalent Pipe Length (m): 54.45
FINAL Pf = 6.7 m
D) Pump Selection
1) Duty Pump:
Type : Centrifugal, End Suction
Drive : Electrical Motor
Pump Head : 65 m
Flow : 136.36 LPM
Quantity : 1 nos
2) Standby Pump:
Type : Centrifugal, End Suction
Drive : Diesel Engine
Pump Head : 65 m
Flow : 136.36 LPM
Quantity : 1 nos
11
a. Pipes shall be held hydrostatic test and certified by certified engineer.
b. Have a water spray system for the tank as noted in the plan that its
installation shall conform to the standard approved by department.
c. Have a foam monitor system near the tank its installation shall conform to
approved standards by department.
d. Have a lightning arrester for storage tanks liquid and flammable gases.
e. Have a gas Detector and this detector system should be included in the To further clarify BOMBA
'Main Alarm Panel'. requirements.
DRIVEWAY
AIR COOLED
CONDENSER
PILI BOMBA 6
TOILET 1
(M)
MAIN DOM.
(FIRST AID ROOM)
WATER TANK
& PUMP ROOM
& PANTRY
OFFICE
REUSE WATER
RESERVOIR
ECONOMIZER
To relocate
To relocate
CONDENSER
PILI BOMBA 6
HALL 2
WARE
ST2
ROOM
AIR COMPRESSOR
SPACE
AIR COOLED
CONDENSER
PILI BOMBA 6
AIR COOLED
CONDENSER
PILI BOMBA 6
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
CONTENTS
1.0 GENERAL 2
1
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
1.0
1.0 GENERAL
The plant will have a staff population of 40 people. The plant will be operating for 24
hours and operators will work in shift to keep check on the process as well as keeping
watch over the plant and taking emergency action in the event of a fire.
Extinguishing
Fire Water Monitor (Remote-
controlled) to cool down any
abnormal heat increment
amongst the waste pile and to
put out any fire that occurs.
2
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
3
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Extinguishing
Portable fire extinguishers and
hose reels will be available for
immediate firefighting response.
Extinguishing
Portable fire extinguishers and
hose reels will be available for
immediate firefighting response.
Extinguishing
Portable fire extinguishers and
hose reels will be available for
immediate firefighting response.
4
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Extinguishing
Portable fire extinguishers and
hose reels.
As the room is not connected to
other structures or building and
only two panels are installed in
the room. Risk of fire and spread
of fire is minimal.
Extinguishing
Portable fire extinguishers, hose
reels and pressurised hydrants
shall be used for immediate fire-
fighting response.
Extinguishing
Portable fire extinguishers and
hose reels shall be used for
immediate fire-fighting response.
5
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Extinguishing
Portable fire extinguishers,
pressurised hydrants and hose
reels shall be used for immediate
fire-fighting response.
Malaysian Standards : -
o M.S. 1176 : Part 5 – Specification for Components of Automatic Fire
Detection Systems Part 5 : Heat Sensitive Detectors – Point Detectors
containing a Static Element System
o M.S. 1745 : Part 2 – Fire Detection and Fire Alarm Systems Part 2 :
Control and Indicative Equipment
o M.S. 1745 : Part 3 – Fire Detection and Fire Alarm Systems Part 3 :
Audible Fire Alarm Devices
6
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
o M.S. 1745 : Part 4 – Fire Detection and Fire Alarm Systems Part 4 :
Power Supply Equipment
o M.S. 1745 : Part 11– Fire Detection and Fire Alarm Systems Part 11 :
Manual Call Point
British Standards : -
o B.S. 5839 : Part 1 – Automatic Fire Detection and Alarm System for
Buildings : Code of Practice for System Design, Installation and
Servicing.
o B.S. 7273 : Part 1 – Code of Practice for the Planning, Installation and
Servicing of Electrical Equipment for Actuation of Gaseous Fire
Suppression System
o B.S. 6266 – Code of Practice for Fire Protection for Electronic Data
Processing Installations
The equipment selected shall comply with relevant Malaysian Standards and shall have
SIRIM approved certification.
A conventional fire alarm system will be employed for this plant. Selection of the
conventional fire alarm system is due to the small number of compartments/rooms in
the building. Therefore, it would be more cost effective to use a conventional fire alarm
system. Furthermore, the connections and maintenance of a conventional fire alarm
system is simpler, therefore, making maintenance and installation simpler with less
room for error.
The main fire alarm panel (MFAP) shall be located in the Central Control Room so that
the main fire alarm panel can be constantly monitored. A repeater fire alarm panel will
7
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
be located near the ground floor to reflect the main fire alarm panel for the fire brigade
during an emergency.
Smoke detectors and heat detectors shall be provided in areas where required and shall
be spaced as per Uniform Building By-Laws and fire-fighting department requirements.
Manual call points shall also be placed within the building in locations as required by By-
Laws and shall also be placed external to the building as per client requirement.
The detectors and manual call points shall be wired back to the MFAP and grouped into
zones will be defined in accordance to fight-fighting department requirements. The
detectors and manual call points on activation shall sound the main alarm bell at the
MFAP and alarm bells placed throughout the building to alert of fire such that
emergency evacuation procedures can be carried out and emergency response team
can carry out fire-fighting actions. Furthermore, an emergency signal shall be sent to the
fire brigade control center via the Central Monitoring System connected to the MFAP.
The MFAP shall also shutdown any mechanical ventilation systems to prevent spread of
fire and smoke throughout the building.
Portable Fire Extinguishers shall be provided where deemed necessary and as required
by regulations set out by Jabatan Bomba dan Penyelamat Malaysia and by Uniform
Building By-Law 227. The portable fire extinguishers used shall be designed, tested,
selected, installed and maintained in accordance to Malaysian Standards : -
8
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Clean Agent Fire Suppression System is selected for human safety. These clean agent
fire suppression systems can be used in areas occupied by humans as these clean
agents do not cause suffocation to humans when controlled under certain
concentrations.
Quantity required for each room is based on design concentration requirements as set
forth by the NFPA 21. The system is set to activate when its detectors detect an actual
fire. Prior to activation, the control panel shall power off any Ventilation equipment and
close off the dampers to prevent escape of the clean agent from the room enclosure.
The system shall have be FM/UL approved.
Foam systems shall be applied to areas where combustible or flammable liquids are
stored.
Combustible and flammable liquids found in this plant are diesel storage tank found
outdoors and the lubricating oil reservoir found in the Turbine Generator Room. Foam
system is not being catered for diesel storage tank as the tank fulfills the requirement of
M.S. 761 : 1982. The diesel storage tank is adequately situated at a distance away from
any property and without the requirement for protection as stated by the standard.
Foam handlines shall be provided in the Turbine Generator Room to handle oil spill fires
from the lubricating oil reservoir as well as possible spills from the gas turbine generator.
The foam acts to cover the spill to smother the flames as well as to prevent further
spread of the fire. The handlines shall be capable of providing a continuous stream of
foam for at least 20 minutes until the gas turbine can be shutdown. Water handlines
shall be used in conjunction to cool the equipment but this shall be done carefully to
avoid disturbing the foam layer on top of the oil spill.
9
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Pressurised hydrants shall be provided for the fire protection of the plant. Design of
hydrants shall be based on requirements set forth by Jabatan Bomba dan Penyelamat
Malaysia and Uniform Building By-laws 225(2) and 225(3) and Malaysian Standards : -
M.S. 1489 Part 1 : Hydrant Systems, Hose Reels and Foam Inlets
The hydrants shall be positioned at strategic points around the plant building and
process area to provide effective coverage. It shall be taken that in the worse case
scenario of a fire only two hydrants shall be used at any one time for fire-fighting.
The water supply for pressurized hydrants shall come from the fire water tank and
minimum water capacity for the pressurized hydrants shall be sized based on local fire
fighting regulations.
Hydrant pumps shall be provided to provide the necessary flowrate and pressure for
effective operation of the pressurized hydrants. One electric and one diesel-driven hose
reel pump shall be provided together with an electric-driven jockey pump.
The diesel-driven pump shall be capable of electric start from storage batteries and the
engine exhaust shall be piped to a safe point outside the pump house enclosure.
Two remote controlled fire water monitors shall be deployed in the waste bunker area to
provide immediate fire protection. The fire water monitors shall also cover the hopper
decks, hopper and shredder. As this is a relatively new technology in Malaysia, the
design shall is based on vendor’s recommendation and shall be subjected to review and
approval from Jabatan Bomba dan Penyelamat Malaysia.
The design of pipe routing for the fire water monitor is based on similar concept of
design for fire hydrants and hose reel systems.
The remote controlled fire water can be operated by operators via remote controls
located in the control room and is capable of being automatically directed to the source
of fire and automatically automated upon reaching a certain temperature threshold via
infrared scanning sensors.
As such, the remote controlled fire water monitor shall be integrated with infrared
scanning in the bunker area, which detects fires and sends out the signal to have the
waste cranes automatically move to the maintenance areas. At the same time, upon
detection of fire, signals shall be sent to activate acoustic and visual alarms to alert the
10
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
operators and provide the control room operators the possibility to intervene prior to the
activation of the remote controlled fire water monitor.
Due to the operating capacity and pressure of the remote controlled fire water monitor, it
is similar to that of a pressurized hydrant and it shall therefore be considered as a
pressurized hydrant in this design and water supply shall come from the pressurized
hydrant mains.
Hose Reels shall be provided throughout the plant building and process area in
accordance to requirements from
Malaysian Standard : -
o M.S. 1489 Part 1: 2012 –Fire Extinguishing installations and equipment
Part 1: Hose reels and foam inlets (First Revision)
The hose reels shall be positioned at strategic points around the plant building and
process area to provide effective coverage.
Supply of water for the hose reel shall come from the fire water tank and water capacity
for hose reel usage is sized based on local fire fighting regulations. The water supply for
hose reel shall be combined with the water supply for pressurized hydrant as approved
by Jabatan Bomba dan Penyelamat Malaysia.
Hose reel pumps shall be provided to provide the necessary flowrate and pressure for
effective operation of the hose reels. One electric and one diesel-driven hose reel pump
shall be provided. The diesel-driven hose reel pump shall only be activated should the
electric pump fail.
The diesel-driven pump shall be capable of electric start from storage batteries and the
engine exhaust shall be piped to a safe point outside the pump house enclosure.
11
JURUTERA SINARUNDING AIDIL SDN BHD
DESIGN CRITERIA FOR FIRE-FIGHTING SYSTEM
Based on Uniform Building By-Law 230 and 232, dry risers are required for the office
building as the building height exceeds 18.3 metres. The equipment selected shall
adhere to relevant Malaysian Standards : -
M.S. 1489 : Part 1 – Hydrant Systems, Hose Reels and Foam Inlets
M.S. 1210 : Part 4 – Boxes for Landing Valves for Dry Risers
Corporate management should establish strict policies with regards to fire risk control
and implement comprehensive fire risk control programs to ensure life safety and
property protection. In order to maintain the effectiveness of the fire-fighting system, it is
imminent for the management to conduct preventative maintenance to the fire-fighting
system equipment.
Involvement of staff in fire prevention and fire-fighting effort is another important aspect
to ensure that the fire-fighting system implemented is effectively used. Plant personnel
must be trained to identify hazards or conditions which are likely to lead to fire, utilize
the fire-fighting system to extinguish fires and also detect faults in the fire-fighting
system. Plant personnel must be alert and patrol the plant premises at fixed times to
observe for abnormal conditions or fires.
12