Вы находитесь на странице: 1из 133

ECE 5750

Distribution System & Power Quality


Part 4: Transformers & voltage regulation
Instructor: Dr. Ha Le
Department of Electrical and Computer Engineering
California State Polytechnic University, Pomona
What will be presented?
1. Voltage regulation
 Two-winding transformer
 Two-winding autotransformer
 1-phase voltage regulators
 3-phase voltage regulators

2. Three-phase transformer models

 3-phase TRF models for different connection types:


 - Grounded Y,  - , Grounded Y– Grounded Y, etc.

Reading: DS textbook, Chapter 7

2
Voltage regulation

3
Methods of regulating voltage
 The regulation of voltages is an important function on a
distribution feeder.

 As the loads on the feeders vary, there must be some


means of regulating the voltage so that every customer
voltage remains within an acceptable level.

 Common methods of regulating the voltage are to


use:
1) Step-type voltage regulators
2) Load tap changing (LTC) transformers
3) Shunt capacitors.

4
Standard voltage ratings (1)
Based on ANSI C84.1-1995 for “Electric Power Systems and
Equipment Voltage Ratings (60 Hertz)”:

1) System voltage: The RMS phasor voltage of a portion of an


alternating current electric system.

2) Nominal system voltage: The voltage by which a portion of


the system is designated and to which certain operating
characteristics of the system are related.

3) Maximum system voltage: The highest system voltage


that occurs under normal operating conditions, and the
highest system voltage for which equipment and other
components are designed for satisfactory continuous
operation without derating of any kind.
5
Standard voltage ratings (2)
4) Service voltage: The voltage at the point where the electrical
system of the supplier and the electrical system of the user
are connected.

5) Utilization voltage: The voltage at the line terminals of


utilization equipment.

6) Nominal utilization voltage: The voltage rating of certain


utilization equipment used on the system.

6
Simplified voltage ranges (limits)
ANSI standards give the distribution engineer a range of “normal
steady-state” voltages (range A) and a range of “emergency
steady-state” voltages (range B) that must be supplied to all users.
For a normal three-wire 120/240 V service:

Range A:
1) Nominal utilization voltage = 115 V
2) Maximum utilization and service voltage = 126 V
3) Minimum service voltage = 114 V
4) Minimum utilization voltage = 110 V

Range B:
1) Nominal utilization voltage = 115 V
2) Maximum utilization and service voltage = 127 V
3) Minimum service voltage = 110 V
4) Minimum utilization voltage = 107 V
7
Voltage unbalance limit
The ANSI standard recommends that the “electric supply
systems should be designed and operated to limit the
maximum voltage unbalance to 3% when measured at the
electric-utility revenue meter under a no-load condition.”

8
Two-winding transformer theory
Z1 N 1: N 2 Z2
H1 X1
+ Iex + + +
IS I1 I2 H1, H2: High voltage terminals
VS Ym E1 E2 VL X1, X2: Low voltage terminals

-
H2 - - -
X2

Fig. 7.1 Exact equivalent circuit The primary impedance Z1 is


referred to the secondary side
N 1: N 2 Z
H1 t
X1
+ I + + +
ex
IS I1 I2
Ym
VS E1 E2 VL N2
E2   E1  n t  E1
-
N1
H2 - - -
X2
1:n t
N2 N2
n t= ___ I1   I 2  nt  I 2
N1 N1
Fig. 7.2 Approximate equivalent circuit 9
Two winding TRF analysis (1)
N 1: N 2 Z
H1 t
X1
+ I + + +
ex
IS I1 I2
VS Ym E1 E2 VL

-
H2 - - -
X2
1:n t
N2
___
n t=
N1
Applying KVL in the secondary circuit
1 Zt
I S  Ym  VL  Ym   I 2  nt  I 2
E 2  VL  Z t  I 2 nt nt
1 1 Z  
V S  E1   E2   V L  t I 2 (7.6) I  Ym  V   Ym  Z t  n   I
nt nt nt S L  t  2 (7.11)
nt  nt 

I S  YmVS  I1 VL  nt  VS  Z t  I L
10
Two winding TRF analysis (2)
In general form: N2
nt 
N1
Vs  a  VL  b  I L (7.7)
1
a
I s  c  VL  d  I L (7.12) nt
Zt
VL  A  Vs  B  I L (7.16) b
nt
Later: Ym
c
 The terms a, b, c, d will be expanded nt
to 3 x 3 matrix for all possible
Ym  Zt
3-phase regulator connections. d  nt
nt
 The expressions for A and B will be
expanded to 3 x 3 matrix for all A  nt
possible 3-phase transformer
B  Zt
connections.
11
Practice: 2-winding TRF analysis
Kersting Example 7.1: A single-phase transformer is rated 75 kVA,
2400/240 V. The transformer has the following impedances and shunt
admittance:
Z1 = 0.612 + j1.2 Ω (high-voltage winding impedance)
Z2 = 0.0061 + j0.0115 Ω (low-voltage winding impedance)
Ym = 1.92 × 10−4 − j8.52 × 10−4 S (referred to the HV winding)

Determine:

1) The generalized a, b, c, and d constants and


the A and B constants.

2) The source voltage and current. Given that the transformer


is operated at rated load and rated voltage with a power
factor of 0.9 lagging.

3) The load voltage.


12
Solution: 2-winding TRF analysis (1)

The transformer “turns ratio” is

The equivalent transformer impedance referred to the


low-voltage side:

13
Solution: 2-winding TRF analysis (2)
The generalized
constants are:

14
Solution: 2-winding TRF analysis (3)
Calculating the source voltage and current:

15
Solution: 2-winding TRF analysis (4)
Load voltage

 This example shows that the generalized constants


provide a quick method for analyzing the operating
characteristics of a two-winding transformer.

16
Solution: 2-winding TRF analysis (5)
For future reference, the per-unit impedance of the transformer is

The per-unit shunt admittance is

17
Two-winding Autotransformer
A two-winding TRF can be
connected as an autotransformer
where LV X1-X2 is called “Series”
and HV H1-H2 is called “Shunt”
winding.

Step-up AutoTRF (top):


The HV terminal H1 is connected o
the LV terminal X2.
The source is connected to
terminals H1 and H2, while the load
is connected between
the X1 terminal and the extension
of H2.

Step-down AutoTRF (bottom):


H1, H2: High voltage terminals
X1, X2: Low voltage terminals

18
Two-winding step-up autoTRF (1)

Applying KVL in the secondary circuit,


E1  nt  E1  (1  nt )  E1  VL  Z t  I 2
E1  E2  VL  Z t  I 2
VS = E1 and I2 = IL
N2
E2   E1  nt  E1 1 Zt
N1 Vs   VL   IL (7.21)
1  nt 1  nt
19
Two-winding step-up autoTRF (2)

Applying KCL at input node H1

I S  I1  I 2  I ex
N2
I1   I 2  nt  I 2
N1
I S  (1  nt )  I 2  Ym  VS

 1 Zt 

I S  (1  nt )  I 2  Ym   VL   I 2 
 1  nt 1  nt 

Ym  Ym  Z t 
IS   VL    nt  1  I L (7.26a)
1  nt  1  nt  20
Two-winding step-up autoTRF (3)
General equations with generalized constants :

21
Two-winding step-down autoTRF (1)

Ideal transformer relation:

E1  E 2  V L  Z t  I 2

E1  nt  E1  (1  nt )  E1  VL  Zt  I 2
1 Zt
Vs   VL   IL (7.31)
1  nt 1  nt
22
Two-winding step-down autoTRF (2)
General equations:

Vs  a  VL  b  I L
I s  c  VL  d  I L (7.32)

VL  A  Vs  B  I L

 Same form as the equations for


the two-winding transformer

23
General equations for autoTRF
The general equations and constants N2
applied to both step-up and step-down nt 
autoTRF are: N1
1
a
Vs  a  VL  b  I L 1  nt
Zt
I s  c  VL  d  I L b
1  nt
VL  A  Vs  B  I L c
Ym
1  nt
 The sign of nt is positive for the Ym  Zt
d  1  nt
step-up connection and negative for 1  nt
the step-down connection.
A  1  nt
B  Zt
24
Autotransformer ratings (1)

KVA rating  rated input VS  rated input I S  rated load VL  rated load I L

25
Autotransformer ratings (2)
Neglecting derivation:

 (7.48) gives the kVA rating of a two-winding transformer when


connected as an autotransformer.

 For the step-up connection, the sign of nt is positive, while the


step-down connection uses the negative sign.

 In general, the turns ratio nt is relatively small so that the kVA


rating of the autotransformer is considerably greater than the
kVA rating of the two-winding TRF.
26
Practice: 2-winding autoTRF analysis
Consider the previous single-phase TRF with ratings of 75 kVA,
2400/240 V. The TRF has the following parameters:
Z1 = 0.612 + j1.2 Ω (high-voltage winding impedance)
Z2 = 0.0061 + j0.0115 Ω (low-voltage winding impedance)
Ym = 1.92 × 10−4 − j8.52 × 10−4 S (referred to the HV winding)
The TRF is connected as a step-up autotransformer.

Determine:

1) The kVA and voltage ratings of the autotransformer.

2) The source voltage and current if the autotransformer is


supplying rated kVA at rated voltage with a power factor of
0.9 lagging.

27
Solution: 2-winding autoTRF (1)
From Example 7.1, the turns ratio was determined to be nt = 0.1.
The rated kVA of the autotransformer using Equation 7.35 is

The voltage ratings are

 The autotransformer would be rated as 825 kVA, 2400–2640 V.


28
Solution: 2-winding autoTRF (2)
The load voltage and current:

Determining the generalized constants:

29
Solution: 2-winding autoTRF (3)

The source voltage and current

30
Solution: 2-winding autoTRF (4)
Calculating the load voltage knowing source voltage and load
current: the A and B parameters are needed:

31
Solution: 2-winding autoTRF (5)
Rework this example by setting
the transformer impedances Zt
and shunt admittance Ym to
zero.

The generalized matrices are:

32
Solution: 2-winding autoTRF (6)
Using these matrices the source voltages and currents are

The “errors” for the source voltages and currents are:

 Very little error has been made. For all practical purposes,
the impedances and shunt admittance of an autotransformer
can be ignored. 33
Single-phase step-voltage regulators
 A step-voltage regulator consists of an autotransformer
and a load tap changing (LTC) mechanism.

 The voltage change is obtained by changing the


taps of the series winding of the autotransformer.
The position of the tap is determined by a control circuit
(line drop compensator).

 Standard step-regulators contain a reversing switch


enabling a ±10% regulator range, usually in 32 steps.

 This amounts to a 5/8% change per step, or 0.75 V


change per step on a 120 V base, or 0.00625 per unit.

34
Step-voltage regulator types
 Step-regulators can be connected in a “Type A” or
“Type B” according to the ANSI/IEEE C57.15-1986
standard.

 We focus on Type B which is more common


connection.

35
Type B step-voltage regulator (1)
Required settings:
1) Voltage level: The desired
voltage
2) Bandwidth: The allowed
variance of the load center
voltage from the set voltage
level.
3) Time delay: Length of time
that a raise or lower
operation is called for before
the actual execution of the
command.
4) Line drop compensator:
Regulator controller, set to
compensate for the voltage
drop between the regulator
and the load center.

36
Type B step-voltage regulator (2)
More on required settings:

1) Voltage level: The desired voltage (on 120 V base) to be held at the
“load center”, which can be the output terminal of the regulator or a
remote node on the feeder.

2) Bandwidth: The voltage held at the load center will be ±1/2 of the
bandwidth. E.g. if the voltage level is set to 122 V and the bandwidth set
to 2 V, the load center voltage is regulated between 121 and 123 V.

3) Time delay: This prevents taps changing during a transient or short time
change in current.

4) Line drop compensator: The settings consist of R and X settings in volts


corresponding to the equivalent impedance between the regulator and
the load center. The regulator required rating is based on the kVA
transformed. It is typically 10% of the line rating since rated current flows
through the series winding, which represents the ±10% voltage change.
37
Step-regulator control circuit

38
Type B regulator in raise position (1)

 The system primary circuit is connected, via taps, to the


series winding of the regulator.
 The series winding is connected to the shunt winding,
which is connected directly to the regulated circuit.
39
Type B regulator in raise position (2)

 (7.66) and (7.67) are the defining equations for


modeling a Type B regulator in RAISE position.
40
Type B regulator in lower position (1)

41
Type B regulator in lower position (2)

 (7.73) and (7.74) are the required equations for


modeling a Type B regulator in LOWER position.
42
Type B regulator raise vs. lower position

Raise vs. Lower

 Effective regulator ratio: (7.67)


and (7.74)

43
Regulator effective ratio
Regulator effective ratio are defined in (7.67) and (7.74).

 The actual turns ratio of the windings is not known.


However, the particular tap position will be known.

 Then, (7.67) and (7.74) can be modified to give the effective


regulator ratio as a function of the tap position. Each tap
changes the voltage by 5/8% or 0.00625 per unit.

 Therefore, the effective regulator ratio is given by

 (7.75): minus sign for the “raise” and the positive sign for
the “lower” position.
44
Type A regulator in raise position

45
Type A regulator in lower position

46
Generalized constants for Type B & A
Relation between the source VS and IS and the load VL and IL:
Type A Type B

47
Line drop compensator (1)

Analog circuit of
the compensator

 The compensator models the voltage drop of the distribution line from the
regulator to the “load center.” It is an analog circuit that is a scale model
of the line circuit.

 Critical setting: R′ and X′ calibrated in volts. These values must


represent the equivalent impedance from the regulator to the load center. 48
Line drop compensator (2)
Setting and ratings:

1) Input voltage: Typically 120 V

2) Rated voltage:
 Nominal line-to-neutral voltage
for regulator line-ground
connection.
 Line-to-line voltage for line-line
connection.

3) The current transformer turns ratio is specified as CTP: CTS where


the primary rating (CTP) is typically the rated current of the
feeder.

4) The key requirement is to force the per-unit line impedance to be


equal to the per-unit compensator impedance.
49
Calculating compensator R′ and X′ (1)
Steps:

1) Selecting a base voltage and current for the line circuit

2) Computing the compensator base voltage and current


by dividing the system base values by the potential
transformer ratio and current transformer ratio

3) Computing the per-unit line impedance

4) Determining compensator impedance in Ohms and in


Volts

Note: For regulators connected line to ground, the base system


voltage is the rated line-to-neutral voltage (VLN), and the base
system current is the rating of the primary winding of the
current transformer (CTP).
50
Calculating compensator R′ and X′ (2)
Step 1 & 2: Table of base values for regulator connected line to ground.

51
Calculating compensator R′ and X′ (3)
Step 3: Per-unit line impedance

Step 4: Compensator impedance in Ohms

52
Calculating compensator R′ and X′ (4)
Step 4 (cont.): Compensator impedance in Volts

The compensator R and X settings in volts are determined by


multiplying the compensator R and X in Ohms by the rated secondary
current (CTS) of the current transformer:

53
Practice A: Compensator R′ and X′
Kersting Example 7.4: In the figure below, the substation transformer is
rated 5000 kVA, 115 kV  − 4.16 kV grounded Y, and the equivalent line
impedance from the regulator to the load center is 0.3 + j0.9 Ω.
Determine the R’ and X’ setting of the compensator in  and V.

54
Solution A: Compensator R′ and X′ (1)
Determine the potential TRF and current TRF ratings for the compensator
circuit. The rated line-to-ground voltage of the substation transformer is

To provide approximately 120 V to the compensator, the potential TRF


ratio is

The rated current of the substation transformer is

55
Solution A: Compensator R′ and X′ (2)
The primary rating of the CT is selected as 700 A, and if the
compensator current is reduced to 5 A, the CT ratio is

The R and X settings of the compensator in Ohms and volt are:


Applying Eqn. 7.78

 Note: The R and X settings on the compensator control board


are calibrated in volts.
56
Practice B: Compensator & load
Kersting Example 7.5 and 7.6: The substation in Practice A is
supplying 2500 kVA at 4.16 kV and 0.9 power factor lagging. The
regulator has been set so that

Voltage level = 120 V (desired voltage to be held at the load center)


Bandwidth = 2 V

1) Determine the tap position of the regulator that will hold


the load center voltage at the desired voltage level and within
the bandwidth.

2) Calculate the actual voltage at the load center with the tap
setting found in Step 1. Assume that the load power and
voltage are measured at the substation low-voltage
terminals.
57
Solution B: Compensator & load (1)
Part 1: Bandwidth = 2V means that the tap on the regulator needs to be
set so that the voltage at the load center lies between 119 and 121 V.
The first step is to calculate the actual line current:

The current in the compensator is

The input voltage to the compensator is

58
Solution B: Compensator & load (2)
The voltage drop in the compensator circuit is equal to the
compensator current times the compensator R and X values in Ohms:

The voltage across the voltage relay is

 The voltage across the voltage relay represents the voltage at


the load center.
 Since this is well below the minimum voltage level of 119V, the
voltage regulator will have to change taps in the raise position
to bring the load center voltage up to the required level.
59
Solution B: Compensator & load (3)
Recall that on a 120 V base, one step change on the regulator
changes the voltage 0.75 V.
The number of required tap changes can then be approximated by

 The final tap position of the regulator will be “raise 13.”

60
Solution B: Compensator & load (4)
Part 2: With the tap set at +13, the effective regulator ratio
assuming a Type B regulator is

The generalized constants for modeling the regulator for this


operating condition are

61
Solution B: Compensator & load (5)
The actual L-G voltage and line current at the load-side terminals of
the regulator are

The actual L-G voltage at the load center is

On a 120-V base, the load center voltage is

62
Solution B: Compensator & load (6)
The +13 tap is an approximation and has resulted in a load center
voltage within the bandwidth.

However, since the regulator Table 7.3


started in the neutral
position, the taps will be
changed one at a time until the
load center voltage is inside the
119 lower bandwidth. Each step
changes the voltage by 0.75 V.

Table 7.3 shows the


compensator relay voltage as
the taps change from 0 to the
final value.

63
Special note on tap changing

Table 7.3
Tap change vs. load voltage

 Table 7.3 shows that the regulator tap changes at a time starting
from the neutral position. However, the tap may NOT be at
neutral position for a tap change event.

 There can be different taps for the same load depending upon
whether the voltage needed to be raised or lowered from an
existing tap position. 64
Calculating equivalent line impedance (1)
 The equivalent line impedance is NOT the actual
impedance of the line between the regulator and the load
center.

 Typically, the load center is located down the primary main


feeder after several laterals have been tapped. Hence, the
current measured by the CT of the regulator is NOT the current
that flows all the way from the regulator to the load center.

 To determine the equivalent line impedance value, a power-


flow program of the feeder without the regulator operating
is run.

 From the output of the program, the voltages at the regulator


output and the load center are obtained.

65
Calculating equivalent line impedance (2)
Once the voltages at the regulator output and the load center are
obtained, the equivalent line impedance can be computed as

In (7.83) the voltages must be specified in system Volt


and the current in system Ampere.

66
3-phase step-voltage regulators
Case 1:
 Three 1-phase step-voltage regulators are connected externally to form a
three-phase regulator.
 When three 1-phase regulators are connected together, each regulator
has its own compensator circuit, and, therefore, the taps on each
regulator are changed separately.
 Three-phase regulators are only connected in a three-phase wye or closed
delta.

Case 2:
 A three-phase regulator has the connections between the single-phase
windings internal to the regulator housing.
 The three-phase regulator is “gang” operated so that the taps on all
windings change the same. Hence, only one compensator circuit is
required.
 It is up to the engineer to determine which phase current and voltage will be
sampled by the compensator circuit.
67
3-P step-voltage regulators - Models
We consider models for the following regulators:

1) Wye-Connected Regulators

2) Closed Delta–Connected Regulators

3) Open Delta–Connected Regulators

Note: The phasing on the source side of the regulator use


capital letters A, B, and C. The load-side phasing use lower
case letters a, b, and c.

68
Y-connected regulators (1)

Three Type B single-phase regulators connected in wye


The polarities of the windings are shown in the “RAISE” position
69
Y-connected regulators (2)
For “LOWER” position, a reversing switch reconnects the series winding so
that the polarity on the series winding is at the output terminal. For both
RAISE and LOWER positions, the following equations apply:

Voltage equations

Current equations

70
Y-connected regulators (3)
Neglecting the series impedance and shunt admittance, the
forward and backward sweep matrices are:

71
Y-connected regulators (4)
 In (7.88), (7.91), (7.93) the effective turns ratio for each
regulator must satisfy 0.9 ≤ aR_abc ≤ 1.1 in 32 steps of
0.625%/step (0.75 V/step on 120 V base).

 aR_a, aR_b, and aR_c can take on different values when


three single-phase regulators are connected in wye.

 It is also possible to sample the voltage and current only


on one phase and then all three phases are changed by
the same number of taps.

72
Practice: Y-connected regulators
Kersting example 7.7: An unbalanced three-phase load is served at the end of
a 10,000 ft, 12.47 kV distribution line segment. Given the following data:

Substation L-N voltages Load Currents leaving the substation

Load voltages Load voltages on a 120-V base

Three 1-P Type B step-voltage regulators are connected in wye and


installed in the substation. The potential and current transformers of the
regulators are rated: 7200V : 120V and 600 A : 5 A.
The regulators are to be set based on voltage level of 120 V and bandwidth 2 V.
Determine the tap position for each phase. 73
Solution: Y-connected regulators (1)
The potential and current transformers of the regulators are rated:

Voltage level = 120 V; Bandwidth = 2 V. The equivalent line impedance


for each phase can be determined by applying Equation 7.83:

74
Solution: Y-connected regulators (2)
Even though the three regulators will change taps independently, it is
the usual practice to set the R and X settings of the three regulators
the same.
The average value of the three line impedances can be used for this
purpose:

The compensator R and X settings are computed according


to Equation 7.82:

75
Solution: Y-connected regulators (3)
The compensator controls are not calibrated to that many significant
figures, so the values set are

The approximate tap settings are:

76
Solution: Y-connected regulators (4)
Since the taps must be integers, the actual tap settings will be

77
Solution: Y-connected regulators (5)
The effective turns ratio for the three regulators and the resulting
generalized matrices are determined by applying Equations 7.88, 7.91,
and 7.92 for each phase:

78
Solution: Y-connected regulators (6)
With the voltage regulators connected to the source, the one-line
diagram of the simple system is shown in Figure 7.13.

79
Closed Delta–connected regulators (1)
The closed delta connection is typically used in three-wire delta feeders.
NOTE: The potential TRF are monitoring the load-side line-to-line voltages and
the current TRF are NOT monitoring the load-side line currents.

The
regulators
are shown in
the “RAISE”
position.

80
Closed Delta–connected regulators (2)
Neglecting derivation, the relation between the L-L voltages are:

81
Closed Delta–connected regulators (3)

Closed delta–
connected
regulators
with currents

82
Closed Delta–connected regulators (4)
Neglecting derivation, the relation between the currents are:

[d] = [D]‐1

83
Closed Delta–connected regulators (5)
Special note:

 The matrices [b] and [c] are zero as long as the series
impedance and shunt admittance of each regulator are
neglected.

 The closed delta connection can be difficult to apply.

Reason:

 In both the voltage and current equations, a change of the tap


position in one regulator will affect voltages and currents in
two phases. As a result, increasing the tap in one regulator
will affect the tap position of the second regulator.

 Therefore, the bandwidth setting for the closed delta


connection will typically have to be wider than that for wye-
connected regulators.
84
Open Delta–connected regulators (1)
 An open delta
connection where
two single-
phase
regulators have
been connected
between
phases AB and
CB.

 Two other open


connections:
Between
phases BC and
AC and between
phases CA and
BA.

85
Open Delta–connected regulators (2)
The open delta connection is typically applied to 3-wire delta
feeders. Note that the potential TRF monitor the line-to-line voltages
and the current TRF monitor the line currents.

Neglecting derivation, the relation between the VOLTAGES are:

[bLL] = 0
if the series impedance and 
shunt admittance of the 
regulators are neglected, 
86
Open Delta–connected regulators (3)
Converting L-L voltages to equivalent L-N voltages and vice versa:

Converting generalized voltage equations:

87
Open Delta–connected regulators (4)
Calculating the load-side L-L voltages as function of the source-
side L-L voltages:

88
Open Delta–connected regulators (5)
Calculating the load-side L-L voltages as function of the source-
side L-L voltages (cont.):

89
Open Delta–connected regulators (6)
Neglecting derivation, the relation between the CURRENTS are:

[creg] = 0
when the series impedances
and shunt admittances are
neglected.
90
Open Delta–connected regulators (7)
Calculating the load-side line currents as a function of the source
line currents:

91
Open Delta–connected regulators (8)
Compensator settings:

 Calculation of the compensator R and X for the open delta


follows the same procedure as that of the wye-connected
regulators.

 However, in the open delta connection the voltages applied to


the compensator are line to line and the currents are line
currents. The potential transformer will transform the system
L-L rated voltage down to 120V.

 The open delta–connected regulators maintain only two of the


line-to-line voltages at the load center within defined limits.

 The third L-L voltage will be dictated by the other two (KVL).
Hence, it may NOT be within the defined limits.
92
Open Delta–connected regulators (9)
Calculating equivalent impedance between the regulators and the
load center

Open delta
connected
to a load
center

 The equivalent impedance is


computed by taking the appropriate
line-to-line voltage drop and
dividing by the sampled line
current. Unit:  93
3-Phase Transformer Models

94
3-P transformers in DS
 3-P transformer banks are found in the distribution
substation where the voltage is transformed from the
transmission or subtransmission level to the distribution
feeder level.

 The substation transformer may have high-voltage no-


load taps and low-voltage load tap changing (LTC).

 For a four-wire wye feeder, the most common substation


transformer connection is the delta–grounded wye.

 A three-wire delta feeder will typically have a delta–delta


transformer connection in the substation.

95
3-P transformer connections
Possible three-phase connections are:
1) Delta–grounded wye
2) Ungrounded wye–delta
3) Grounded wye–delta
4) Open wye–open delta
5) Grounded wye–grounded wye
6) Delta–delta
7) Open delta–open delta

We consider two popular types:


 Delta–grounded wye: four-wire wye feeder
 Delta–delta: 3-wire delta line
96
General 3-P transformer bank (1)

 A, B, C, and N : Source side (node n)

 a, b, c, and n : Load side (node m) of the bank

 All variations of the Y– connections follow “American


Standard Thirty Degree” connection.
97
General 3-P transformer bank (2)

98
General 3-P transformer bank (3)
Generalized matrices:
In the “forward sweep” of the “ladder” iterative technique (later), the
voltages at node m are defined as a function of the voltages at node n and
the currents at node m:

In the “backward sweep”, the voltages and currents at node n are


functions of the voltages and currents at node m

 [VLNABC] and [VLNabc] represent the L-N voltages for an ungrounded wye
connection or the L-G voltages for a grounded wye connection.
 For a delta connection, the voltage matrices represent “equivalent” line-to-
neutral voltages.
99
Delta–grounded Y step-down TRF (1)

Actual winding
turns ratio (nt):
100
Delta–grounded Y step-down TRF (2)
The line-to-line voltages on the primary side of the TRF
connection as a function of the ideal secondary side voltages
are given by

101
Delta–grounded Y step-down TRF (3)
Computing equivalent line-to-neutral voltages based on the line-
to-line voltages:

Ideal TRF voltages:

102
Delta–grounded Y step-down TRF (4)
Voltage equations:

Ztabc = impedances 
matrix of the three 
1‐P transformers; 
Referred to the LV 
side
103
Delta–grounded Y step-down TRF (5)
L-L voltages as a function of the equivalent L-N voltages are:

Load voltages as a function source voltages and load currents:

104
Delta–grounded Y step-down TRF (6)
Delta–grounded wye connection with currents

105
Delta–grounded Y step-down TRF (7)
Current equations:

Line currents can be determined as a function of the delta currents

106
Practice: Delta–grounded Y step-down (1)
Kersting Example 8.1: In Figure 8.4, an unbalanced constant
impedance load is being served at the end of a 1 mile section of a
three-phase line. The line is being fed from a substation transformer
rated 5000 kVA, 115 kV delta–12.47 kV grounded wye with a per-unit
impedance of 0.085850. Determine:

a) the generalized matrices for the TRF


b) the “ideal” transformer voltages
c) the load currents
d) L-G voltages at the load and L-G voltages at node 2
e) Verify equivalent L-N and L-L voltages at node 1 using
backward sweep voltage equations

Figure 8.4, 

107
Practice: Delta–grounded Y step-down (2)
Line phase impedance matrix

The general matrices for the line are:

108
Solution: Delta–grounded Y step-down (1)
Converting TRF impedance Zt to per unit referenced to the LV side

The TRF phase impedance matrix is

109
Solution: Delta–grounded Y step-down (2)
The unbalanced constant impedance load is connected in grounded
wye. The load impedance matrix is specified to be

The unbalanced L-L voltages at node 1 are given as:

110
Solution: Delta–grounded Y step-down (3)
a. Determine the generalized matrices for the transformer:

Equation 8.19

111
Solution: Delta–grounded Y step-down (4)

Equation 8.23

112
Solution: Delta–grounded Y step-down (5)

Eqn. 8.37 and 8.28

113
Solution: Delta–grounded Y step-down (6)
Eqn. 8.31

b. Determine the “ideal” transformer voltages: Eqn. 8.13

114
Solution: Delta–grounded Y step-down (7)
c. Determine the load currents

Since the load is modeled as constant impedances, we can combine all


of the impedances (transformer, line, and load) to an equivalent
impedance matrix

115
Solution: Delta–grounded Y step-down (8)
The line currents are:

d. Determine L-G voltages at the load and L-G voltages at Node 2

116
Solution: Delta–grounded Y step-down (9)
The load voltages on a 120 V base are:

The L-G voltages at node 2 are:

117
Solution: Delta–grounded Y step-down (10)
e. Verify equivalent L-N voltages and the L-L voltages at node 1
using backward sweep voltage equations

 The L-L voltages at Node 1 are the same as the given values
118
Delta–grounded Y step-up TRF (1)

119
Delta–grounded Y step-up TRF (2)
The primary (low side) line-to-line voltages are given by

The primary delta currents are given by

120
Delta–grounded Y step-up TRF (3)
The primary line currents are:

121
Delta–grounded Y step-up TRF (4)
Forward sweep matrices are:

122
Delta–grounded Y step-up TRF (5)
Backward sweep matrices are:

[ct] = 0
123
Delta – Delta TRF (1)

124
Delta – Delta TRF (2)
The basic “ideal” transformer voltage and current equations as a
function of the “turn's ratio” are:

125
Delta – Delta TRF (3)

126
Delta – Delta TRF (4)
Source-side delta currents:

The line currents as a function of the delta currents on the


source side are:

127
Delta – Delta TRF (5)
Currents equations:

The load-side line currents as a function of the load-side delta currents:

 The line currents on the two sides of the TRF are in


phase and differ only by the turn's ratio of the TRF
windings. In the per-unit system, the per-unit line currents on
the two sides of the TRF are exactly equal. 128
Delta – Delta TRF (6)
The ideal delta voltages on the secondary side as a function of the L-L
voltages, the delta currents, and the transformer impedances are given by

Source and load voltages:

129
Delta – Delta TRF (7)
The delta currents are a function of the transformer impedances:

[G1] = [G] where


the 3rd column is
set to zero
130
Delta – Delta TRF (8)
Generalized matrices are defined in terms of the line-to-neutral
voltages on the two sides of the transformer bank:

Backward sweep equations for voltage:

131
Delta – Delta TRF (9)
Generalized equation for currents:

Forward sweep equations for voltage:

132
References
1. S. Santoso, Fundamentals of Electric Power Quality, 2012.
2. R. C. Dugan, M. F. McGranaghan, S. Santoso, W. Beaty,
Electrical Power Systems Quality, McGraw Hill 2012.
3. T. A. Short, Electric Power Distribution Handbook, 2003.
4. J. D. Glover, M. S. Sarma, T. J Overbye, Power System Analysis
and Design, 5th Ed., CENGAGE Learning, 2012.
5. T. Gonen, Electric Power Distribution Engineering, 3rd ed., 2014,
CRC Press, ISBN 9781482207002.
6. W. H. Kersting, Distribution System Modeling and Analysis, 3rd
ed., CRC Press, 2012.
7. H. Saadat, Power System Analysis, PSA Publishing, 3rd (2010)
and previous editions.
8. IEEE Std. 519-1992.
9. Other sources.

133

Вам также может понравиться