IBM Flex System Enterprise Chassis &

PureFlex Power Requirements Guide

World Wide

Author: William S. Champion


wchamp@us.ibm.com

Version: 1.3.2
Date: August 27, 2013

The user of this document is responsible for obtaining the latest copy prior to use. Obsolete copies may be
archived and used for reference purposes only. The latest version of this document is located at:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP102111

© IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Revision History

1.0.0 – April 30, 2012 Initial Release


1.1.0 – June 29, 2012 Updated power cord information, IBM System x PDU information to include
feature code, and “IBM Flex & PureFlex System Documents” section. Add
IBM Power Systems PDU information.
1.2.0 – December 17, 2012 Update information and configurations for the 2100W optional PSU. Added
information on PDU line cords. Correct 2500W PSU amp rating. Added IBM
PureFlex power & cooling part numbers section.
1.2.1 – January 4, 2013 Correct problem in the “2x Flex (6x PSU) on 60A@208V 3ph PDUs – North
America” section with IBM Power System PDUs for the “2500W PSU N+N
Wiring Diagram” configuration.
1.2.2 – January 15, 2013 Added 2100W PSU compatibility matrix section.
1.3.0 – June 7, 2013 Added PureFlex Configuration Example Sections, new 16A@380-480V
System x PDU information, and IBM ToR Switches & IBM Storwize V7000
Power Numbers reference section. Updated Flex System line cord section.
1.3.1 – July 12, 2013 Fix UPS example diagrams. Updated switch part numbers in the “IBM Flex
System Power & Cooling Part Numbers” section.
1.3.2 – August 27, 2013 Updated the “PSU Compatibility Matrix” section to include x222.

Contributors:
Doug Evans – IBM System x Development
dougevan@us.ibm.com

Joe Prisco – IBM Power Systems Development


prisco@us.ibm.com

Matthew R. Archibald – IBM Lab Services Datacenter


archibam@us.ibm.com

Jason Daniel – IBM Global Technology Services


jdaniel@us.ibm.com

Notices:

This paper is intended to provide information regarding powering IBM Flex System Enterprise Chassis solutions. It presents findings based on
configurations that were created and tested under laboratory conditions. These findings may not be realized in all customer environments, and
implementation in such environments may require additional steps, configurations and performance analysis. The information herein is
provided “AS IS” with no warranties, express or implied. This information does not constitute a specification or form part of the warranty for any
IBM or non-IBM products.

Information in this document was developed in conjunction with the use of the equipment specified and is limited in application to those
specific hardware and software products and levels.

The information contained in this document has not been submitted to any formal IBM test and is distributed as is. The use of this information
or the implementation of these techniques is a customer responsibility and depends on the customer’s ability to evaluate and integrate them
into the customer’s operational environment. While each item may have been reviewed by IBM for accuracy in a specific situation, there is no
guarantee that the same or similar results will be obtained elsewhere. Customers attempting to adapt these techniques to their own
environments do so at their own risk.

IBM may not officially support techniques mentioned in this document. For questions regarding officially supported techniques, please refer to
the product documentation, announcement letters or contact the IBM Support Line at 1-800-IBM-SERV.
This document makes references to vendor-acquired applications or utilities. It is the customer responsibility to obtain licenses of these utilities
prior to their usage.

© Copyright International Business Machines Corporation 2012, 2013. All rights reserved. U.S. Government Users Restricted Rights –
Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.

Page |2 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Table of Contents
INTRODUCTION ............................................................................................................................................................... 7
HOW TO USE THIS GUIDE ............................................................................................................................................................... 7
IBM FLEX POWER OVERVIEW ........................................................................................................................................... 8
IBM FLEX SYSTEM POWER SUPPLY UNIT (PSU) ................................................................................................................................. 8
2500W PSU – Rating & Part Number Information ............................................................................................................... 8
2100W PSU – Rating & Part Number Information ............................................................................................................... 8
PSU Compatibility Matrix ..................................................................................................................................................... 9
2500W PSU – Half Wide Nodes Minimum PSU Required For N+N..................................................................................... 10
2100W PSU – Half Wide Nodes Minimum PSU Required For N+N..................................................................................... 10
2500W PSU – Full Wide Nodes Minimum PSU Required For N+N ..................................................................................... 11
2100W PSU – Full Wide Nodes Minimum PSU Required For N+N ..................................................................................... 11
2500W PSU – Half Wide Nodes Minimum PSU Required For N+1 ..................................................................................... 12
2100W PSU – Half Wide Nodes Minimum PSU Required For N+1 ..................................................................................... 12
2500W PSU – Full Wide Nodes Minimum PSU Required For N+1 ...................................................................................... 13
2100W PSU – Full Wide Nodes Minimum PSU Required For N+1 ...................................................................................... 13
IBM FLEX SYSTEM ZONE COOLING ................................................................................................................................................. 14
IBM FLEX SYSTEM POWER CORDS ................................................................................................................................................. 14
IBM System x Worldwide Power Cords .............................................................................................................................. 14
IBM System x North American Power Cords ...................................................................................................................... 15
IBM System x International Power Cords ........................................................................................................................... 16
IBM Power Systems Worldwide Power Cords .................................................................................................................... 17
IBM Power Systems North American Power Cords ............................................................................................................ 17
PDU CONFIGURATIONS (6X PSU / FLEX) – NORTH AMERICA ........................................................................................... 18
2X FLEX (6X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 18
2X FLEX (6X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 22
1X FLEX (6X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 23
1X FLEX (6X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 25
1X FLEX (6X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 27
1X FLEX (6X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 29
PDU CONFIGURATIONS (5X PSU / FLEX) – NORTH AMERICA ........................................................................................... 31
1X FLEX (5X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 31
1X FLEX (5X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 33
1X FLEX (5X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 35
1X FLEX (5X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 37
1X FLEX (5X PSU) ON 5X 30A@200-240V 1PH PDUS – NORTH AMERICA ......................................................................................... 39
PDU CONFIGURATIONS (4X PSU / FLEX) – NORTH AMERICA ........................................................................................... 41
3X FLEX (4X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 41
3X FLEX (4X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 44
3X FLEX (4X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 46
3X FLEX (4X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 48
1X FLEX (4X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 50
1X FLEX (4X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 52
1X FLEX (4X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 54
1X FLEX (4X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 56
1X FLEX (4X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 58
PDU CONFIGURATIONS (3X PSU / FLEX) – NORTH AMERICA ........................................................................................... 60
2X FLEX (3X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 60
1X FLEX (3X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 62

Page |3 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1X FLEX (3X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 64


1X FLEX (3X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 66
1X FLEX (3X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 68
PDU CONFIGURATIONS (2X PSU / FLEX) – NORTH AMERICA ........................................................................................... 70
1X FLEX (2X PSU) ON 60A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 70
1X FLEX (2X PSU) ON 50A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 73
1X FLEX (2X PSU) ON 30A@208V 3PH PDUS – NORTH AMERICA .................................................................................................... 76
1X FLEX (2X PSU) ON 60A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 79
1X FLEX (2X PSU) ON 30A@200-240V 1PH PDUS – NORTH AMERICA ............................................................................................. 82
PDU CONFIGURATIONS (6X PSU / FLEX) – INTERNATIONAL ............................................................................................ 84
2X FLEX (6X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................... 84
1X FLEX (6X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................... 88
1X FLEX (6X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................... 90
1X FLEX (6X PSU) ON 32A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................... 92
PDU CONFIGURATIONS (5X PSU / FLEX) – INTERNATIONAL ............................................................................................ 95
1X FLEX (5X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................... 95
1X FLEX (5X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................... 97
1X FLEX (5X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................... 99
1X FLEX (5X PSU) ON 32A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 101
PDU CONFIGURATIONS (4X PSU / FLEX) – INTERNATIONAL .......................................................................................... 104
3 X FLEX (4X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................ 104
3 X FLEX (4X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................ 107
2X FLEX (4X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 109
1X FLEX (4X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 111
1X FLEX (4X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 113
1X FLEX (4X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 115
1X FLEX (4X PSU) ON 32A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 117
PDU CONFIGURATIONS (3X PSU / FLEX) – INTERNATIONAL .......................................................................................... 120
2X FLEX (3X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 120
1X FLEX (3X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 122
1X FLEX (3X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 124
1X FLEX (3X PSU) ON 32A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 126
PDU CONFIGURATIONS (2X PSU / FLEX) – INTERNATIONAL .......................................................................................... 128
1X FLEX (2X PSU) ON 32A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 128
1X FLEX (2X PSU) ON 16A@380-415V 3PH PDUS – INTERNATIONAL ............................................................................................. 131
1X FLEX (2X PSU) ON 63A@220-240V 1PH PDUS – INTERNATIONAL ............................................................................................. 134
1X FLEX (2X PSU) ON 2X 32A@220-240V 1PH PDUS – INTERNATIONAL ......................................................................................... 138
UPS CONFIGURATIONS ................................................................................................................................................ 142
1X FLEX (6X PSU) ON 2X IBM UPS11000 – WORLD WIDE ............................................................................................................ 142
1X FLEX (4X PSU) ON 2X IBM UPS6000 – WORLD WIDE .............................................................................................................. 143
1X FLEX (4X PSU) ON 2X IBM UPS6000 – NORTH AMERICA .......................................................................................................... 144
PUREFLEX SYSTEMS X-CONFIG CONFIGURATION EXAMPLES ......................................................................................... 145
3X FLEX CHASSIS W/ 4X TOR SWITCHES – 3 PHASE 60A@208V & 32A@380-415V – X-CONFIG EXAMPLE ........................................... 146
North America PDU Options ............................................................................................................................................ 146
International PDU Options ............................................................................................................................................... 146
3X FLEX CHASSIS W/ 6X TOR SWITCHES – 3 PHASE 60A@208V & 32A@380-415V – X-CONFIG EXAMPLE ........................................... 147
North America PDU Options ............................................................................................................................................ 147

Page |4 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

International PDU Options ............................................................................................................................................... 148


3X FLEX CHASSIS W/ 6X TOR SWITCHES – 1 PHASE 60A@200-240V & 63A@220-240V – X-CONFIG EXAMPLE ................................... 149
North America PDU Options ............................................................................................................................................ 149
International PDU Options ............................................................................................................................................... 149
2X FLEX CHASSIS W/ 6X TOR SWITCHES – 3 PHASE 60A@208V & 32A@380-415V – X-CONFIG EXAMPLE ........................................... 150
North America PDU Options ............................................................................................................................................ 150
International PDU Options ............................................................................................................................................... 151
2X FLEX CHASSIS W/ 6X TOR SWITCHES – 1 PHASE 60A@200-240V & 63A@220-240V – X-CONFIG EXAMPLE ................................... 152
North America PDU Options ............................................................................................................................................ 152
International PDU Options ............................................................................................................................................... 152
2X FLEX CHASSIS W/ 6X TOR SWITCHES – 1 PHASE 20A@200-240V & 30A@200-240V – X-CONFIG EXAMPLE ................................... 153
North America PDU Options ............................................................................................................................................ 153
International PDU Options ............................................................................................................................................... 153
PUREFLEX SYSTEMS E-CONFIG CONFIGURATION EXAMPLES ......................................................................................... 154
3X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 2X V7000 – 3PH 60A@208V & 32A@380-415V – E-CONFIG EXAMPLE....................... 155
North America PDU Options ............................................................................................................................................ 155
International PDU Options ............................................................................................................................................... 156
3X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 2X V7000 – 1PH 60A@200-240V & 63A@220-240V – E-CONFIG EXAMPLE ............... 157
North America PDU Options ............................................................................................................................................ 157
International PDU Options ............................................................................................................................................... 158
2X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 7X V7000 – 3PH 60A@208V & 32A@380-415V – E-CONFIG EXAMPLE....................... 159
North America PDU Options ............................................................................................................................................ 159
International PDU Options ............................................................................................................................................... 160
2X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 7X V7000 – 1PH 60A@200-240V & 63A@220-240V – E-CONFIG EXAMPLE ............... 161
North America PDU Options ............................................................................................................................................ 161
International PDU Options ............................................................................................................................................... 162
2X FLEX CHASSIS W/ 6X TOR SWITCHES & 7X V7000 – 1 PHASE 20A@200-240V & 30A@200-240V – E-CONFIG EXAMPLE ................. 163
North America PDU Options ............................................................................................................................................ 163
International PDU Options ............................................................................................................................................... 163
1X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 12X V7000 – 3PH 60A@208V & 32A@380-415V – E-CONFIG EXAMPLE..................... 164
North America PDU Options ............................................................................................................................................ 164
International PDU Options ............................................................................................................................................... 165
1X PUREFLEX CHASSIS W/ 6X TOR SWITCHES & 12X V7000 – 1PH 60A@200-240V & 63A@220-240V – E-CONFIG EXAMPLE ............. 166
North America PDU Options ............................................................................................................................................ 166
International PDU Options ............................................................................................................................................... 167
IBM SYSTEM X & POWER SYSTEMS NORTH AMERICAN PDUS ....................................................................................... 168
IBM SYSTEM X PDU INFORMATION NORTH AMERICA ..................................................................................................................... 168
IBM POWER SYSTEMS PDU INFORMATION NORTH AMERICA ........................................................................................................... 168
IBM SYSTEM X & POWER SYSTEMS NORTH AMERICAN PDUS INPUT LINE CORDS................................................................................. 169
NEMA L6-30 ..................................................................................................................................................................... 169
IEC 309 2P+G – 60A@200-240V 1ph................................................................................................................................ 170
NEMA L21-30 ................................................................................................................................................................... 171
CS8365L – 50A@208V 3ph ............................................................................................................................................... 172
IEC309 3P+G – 60A@208V 3ph ........................................................................................................................................ 173
IBM SYSTEM X & POWER SYSTEMS INTERNATIONAL PDUS ........................................................................................... 174
IBM SYSTEM X PDU INFORMATION INTERNATIONAL ....................................................................................................................... 174
IBM POWER SYSTEMS PDU INFORMATION INTERNATIONAL ............................................................................................................. 175
IBM SYSTEM X & POWER SYSTEMS INTERNATIONAL PDUS INPUT LINE CORDS .................................................................................... 176
IEC 309 P+N+G – 32A@220-240V 1ph ............................................................................................................................. 176
AUS/NZ 3112 32A – 32A@230V 1ph ............................................................................................................................... 177
KSC 8305 30A – 30A@220V 1ph ...................................................................................................................................... 178
IEC 309 P+N+G – 63A@220-240V 1ph ............................................................................................................................. 179

Page |5 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC309 3P+N+G – 16A@380-415V 3ph ............................................................................................................................ 180


PDL 56P532 / Clipsal 56PA532 – 32A@415V 3ph ............................................................................................................ 181
IEC 309 3P+N+G – 32A@380-415V 3ph ........................................................................................................................... 182
IBM FLEX SYSTEM POWER & COOLING PART NUMBERS ............................................................................................... 183
IBM SYSTEM X FLEX SYSTEM POWER & COOLING PART NUMBERS .................................................................................................... 183
G8264R – IBM System x PureFlex Part Numbers ............................................................................................................. 183
G8052R – IBM System x PureFlex Part Numbers ............................................................................................................. 183
Flex System Enterprise Chassis – IBM System x PureFlex Part Numbers.......................................................................... 184
Rack & Rear Door Heat eXchanger (RDHx) – IBM System x PureFlex Part Numbers ....................................................... 184
IBM POWER SYSTEMS FLEX SYSTEM POWER & COOLING PART NUMBERS .......................................................................................... 184
Storwize V7000 (External) – IBM Power Systems PureFlex Part Numbers....................................................................... 184
G8264R – IBM Power Systems PureFlex Part Numbers ................................................................................................... 184
G8052R – IBM Power Systems PureFlex Part Numbers ................................................................................................... 185
Flex System Enterprise Chassis – IBM Power Systems PureFlex Part Numbers................................................................ 185
Rack & Rear Door Heat eXchanger (RDHx) – IBM Power Systems PureFlex Part Numbers ............................................. 185
REFERENCE MATERIAL ................................................................................................................................................. 186
IBM TOR SWITCHES & IBM STORWIZE V7000 POWER NUMBERS.................................................................................................... 186
IBM FLEX SYSTEM POWER MANAGEMENT POLICIES ....................................................................................................................... 186
IBM Flex Power Management Policies Overview ............................................................................................................. 186
WHAT IS N+N AND N+1 PSU REDUNDANCY ................................................................................................................................. 187
N+N and N+1 Examples ................................................................................................................................................... 187
IEC 320 CONNECTORS .............................................................................................................................................................. 188
IEC 309 PIN & SLEEVE PLUG DECODE .......................................................................................................................................... 188
INGRESS PROTECTION (IP) DECODE .............................................................................................................................................. 189
60A THREE PHASE DELTA POWER CALCULATIONS .......................................................................................................................... 189
50A THREE PHASE DELTA POWER CALCULATIONS .......................................................................................................................... 190
30A THREE PHASE DELTA POWER CALCULATIONS .......................................................................................................................... 190
32A THREE PHASE WYE POWER CALCULATIONS............................................................................................................................. 190
16A THREE PHASE WYE POWER CALCULATIONS............................................................................................................................. 191
IBM FLEX SYSTEM & PUREFLEX SYSTEM DOCUMENTS..................................................................................................................... 191
HELPFUL LINKS ......................................................................................................................................................................... 191

Page |6 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Introduction
The IBM Flex System Enterprise Chassis covered in this guide is currently marketed worldwide. The intent of this
guide is to provide power information for installation planning of IBM Flex System Enterprise Chassis. The guide
contains examples of the IBM Flex System Enterprise Chassis connected to various PDUs and circuits.

This guide is best used in softcopy form since it contains hyperlinks for navigation. This document can still be
used in hardcopy as reference only. You can obtain the latest copy of this document from this web page:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/PRS4401

How to Use This Guide


All of the IBM Flex System Enterprise Chassis configuration examples documented in this guide state the
supported redundancy in the “IBM Flex Power Management Policies” table. IBM Flex System Enterprise Chassis
has configurations with N+N redundancy, where the goal is to provide the support for two power source
configurations. To take full advantage of this redundancy and reliability, the chassis must be powered from two
independent distribution panels and the IBM Flex Power Management Policy must be set to a policy that is N+N
capable. When properly wired and the appropriate power policy set, the IBM Flex SE chassis can remain in
operation if one of the two power sources fails.

Power connections to the IBM Flex chassis must be wired to comply with local and/or national electrical codes.
Consult your local AHJ (Authority Having Jurisdiction) to ensure compliance.

Important Notice: All wiring examples provided in this document are based on nameplate label ratings for the
systems.

Each example covered in this guide gives System x PDU options information (if available), along with information
on Flex power policies.

Example Configuration:

Power
Management
Policies

Wiring Diagram

Required Flex
Line Cord

System x PDU
Options

Page |7 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Flex Power Overview


Use the IBM Power Configurator for System x, BladeCenter, and Flex System tool at the link below to estimate
power consumption and heat load for the Flex System Enterprise Chassis configurations.

IBM Power Configurator for System x, BladeCenter, and Flex System tool link:
http://www.ibm.com/systems/bladecenter/resources/powerconfig.html

IBM Flex System Power Supply Unit (PSU)


2500W PSU – Rating & Part Number Information Rear of Flex Chassis
PSU DC Output Wattage = 2500W
Power 1 10 3 Power 2 5 4
200-240V Supply
IN OUT 200-240V Supply
IN OUT
13,8A Bay 13,8A Bay
50/60Hz 50/60Hz CMM2
I/O Bay I/O Bay I/O Bay I/O Bay

PSU 6

PSU 3
CMM
6 Bay

PSU Nominal Input Voltage Range = 200-208, 220-240V AC @ 50-60 Hz. Fan
Bay
5

4
Fan
Bay

PSU Max Input Amps @ 200-240V = 13.8A


Single PSU IBM System x P/N: 43W9049 | FC: A0UD
Single PSU IBM Power Systems FC: 3590 Power
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Fan
Bay 200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Power Fan
Bay

PSU 5

PSU 2
Power
Supply
Bays
6 3

5 2

4 1

Fan
Bays

2100W PSU – Rating & Part Number Information


10 5
9 4
8 3
7 2
6 1

Fan Fan
Bay Bay
TX/ RX

PSU DC Output Wattage = 2100W 50/60Hz


Power
200-240V Supply
IN OUT
13,8A Bay
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Power
LINK

PSU Nominal Input Voltage Range = 200-208, 220-240V AC @ 50-60 Hz.

PSU 4

PSU 1
Fan Fan
Bay Bay

PSU Max Input Amps @ 200-240V = 11.8A 3

Single PSU IBM System x P/N: 47C7633 | FC: A3JH 1

CMM1

Single PSU IBM Power Systems: Not supported by Power Systems 1 6 3 2 1 4

2500W 2500W 2500W 2500W 2500W 2500W


PSU PSU PSU PSU PSU PSU
Fan Fan Fan Fan Fan Fan

12.2V

System System
Personality Card

Fan 1 Full Wide Node or 2 Half Nodes Fan


IO Bay Fans (40mm)

IO Bay Fans (40mm)


(80mm) (80mm)
CMM
CMM

IO Bay
IO Bay
IO Bay
IO Bay

1 Full Wide Node or 2 Half Nodes


Fan Distribution Card

Fan Distribution Card

System System
1 Full Wide Node or 2 Half Nodes
Fan Fan
(80mm) (80mm)
1 Full Wide Node or 2 Half Nodes

System 1 Full Wide Node or 2 Half Nodes System


Fan Fan
(80mm) 1 Full Wide Node or 2 Half Nodes (80mm)

1 Full Wide Node or 2 Half Nodes


System System
Fan Fan
(80mm) (80mm)
Fan Logic Card Fan Logic Card

Page |8 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PSU Compatibility Matrix


This table assumes worst case for ITEs and that means the ITEs are configured to the maximum. Currently, we
don’t have a method to plan for less than worst case or configuration based planning. IBM Power Configurator, in
the future, will be able to validate configurations that are less than worst case and are configuration based.

2100W PSU 2500W PSU


N+1, N = 5 N+1, N = 4 N+1, N = 3 N+N, N = 3 N+1, N = 5 N+1, N = 4 N+1, N = 3 N+N, N = 3
ITE CPU 6 Total 5 Total 4 Total 6 Total 6 Total 5 Total 4 Total 6 Total
50W 14 14 14 14 14 14 14 14
60W 14 14 14 14 14 14 14 14
x220 70W 14 14 14 14 14 14 14 14
80W 14 14 14 14 14 14 14 14
95W 14 14 14 14 14 14 14 14
50W 14 14 13 14 14 14 14 14
60W 14 14 12 13 14 14 14 14
x222 70W 14 14 11 12 14 14 14 14
80W 14 14 10 11 14 14 13 14
95W 14 13 9 10 14 14 12 13
60W 14 14 14 14 14 14 14 14
70W 14 14 13 14 14 14 14 14
80W 14 14 13 14 14 14 14 14
x240 95W 14 14 12 13 14 14 14 14
115W 14 14 11 12 14 14 14 14
130W 14 14 11 11 14 14 14 14
135W 14 14 11 11 14 14 13 14
95W 7 7 6 6 7 7 7 7
x440 115W 7 7 5 6 7 7 7 7
130W 7 7 5 5 7 7 6 7
p24L – 14 12 9 10 14 14 12 13
p260 – 14 12 9 10 14 14 12 13
p460 – 7 6 4 5 7 7 6 6
FSM – 2 2 2 2 2 2 2 2
V7000 – 3 3 3 3 3 3 3 3

Notes: All ITEs fully configured Supported: No Restrictions


Assumes throttling and over subscription are enabled Supported: Power Restrictions
6 max power supplies per chassis
For more information on N+N and N+1 redundancy see “What is N+N and N+1 Redundancy” section
on page 187 in this document.

Page |9 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU – Half Wide Nodes Minimum PSU Required For N+N
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
14 6 408 6 408 Not Supported
13 6 444 6 440 Not Supported
12 6 476 6 476 6 476
11 6 500 6 520 6 520
10 4 329 6 572 6 572
9 4 374 4 374 6 644
8 4 431 4 431 6 700
7 4 493 4 493 4 493
6 4 500 4 575 4 575
5 4 500 4 600 4 700
4 2 296 4 600 4 700
3 2 395 2 395 2 395
2 2 500 2 593 2 593
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

2100W PSU – Half Wide Nodes Minimum PSU Required For N+N
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU1 Fault # of PSU1 Fault
14 Not Supported Not Supported Not Supported
13 6 347 Not Supported Not Supported
12 6 376 Not Supported Not Supported
11 6 410 6 410 Not Supported
10 6 451 6 451 Not Supported
9 6 500 6 510 6 510
8 4 331 6 584 6 584
7 4 378 4 378 6 667
6 4 441 4 441 4 441
5 4 500 4 546 4 546
4 500 4 600 4 700
3 2 261 4 600 4 700
2 2 392 2 392 2 392
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

P a g e | 10 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU – Full Wide Nodes Minimum PSU Required For N+N
# of Full Wide 1000 W ITE 1200 W ITE 1400 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
7 6 816 6 816 Not Supported
6 6 953 6 953 6 953
5 4 658 6 1143 6 1143
4 4 863 4 863 6 1400
3 4 1000 4 1150 4 1150
2 2 593 4 1200 4 1400
1 2 1000 2 1185 2 1185
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

2100W PSU – Full Wide Nodes Minimum PSU Required For N+N
# of Full Wide 1000 W ITE 1200 W ITE 1400 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
7 6 645 Not Supported Not Supported
6 6 752 Not Supported Not Supported
5 6 902 6 902 6 902
4 4 662 6 1168 6 1168
3 4 883 4 883 4 883
2 4 1000 4 1200 4 1400
1 2 784 2 784 2 784
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

P a g e | 11 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU – Half Wide Nodes Minimum PSU Required For N+1
# of Half Wide 500 W ITE 600 W ITE 700 W ITE
Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
14 4 414 4 414 5 590
13 4 446 4 446 5 635
12 4 483 4 483 4 483
11 4 500 4 527 4 527
10 3 333 4 580 4 580
9 3 379 3 379 4 653
8 3 436 3 436 4 700
7 3 499 3 499 3 499
6 3 500 3 582 3 582
5 3 500 3 600 3 700
4 2 296 3 600 3 700
3 2 395 2 395 2 395
2 2 500 2 593 2 593
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

2100W PSU – Half Wide Nodes Minimum PSU Required For N+1

# of Half Wide 500 W ITE 600 W ITE 700 W ITE


Nodes # of PSU1 Fault # of PSU 1
Fault # of PSU1 Fault
14 5 475 5 475 5 475
13 4 353 5 512 5 512
12 4 383 5 555 5 555
11 4 417 4 417 5 605
10 4 459 4 459 5 666
9 4 500 4 519 4 519
8 3 336 4 594 4 594
7 3 384 3 384 4 679
6 3 448 3 448 3 448
5 3 500 3 554 3 554
4 3 500 3 600 3 700
3 2 261 3 600 4 700
2 2 392 2 392 2 392
1 2 500 2 600 2 700
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

P a g e | 12 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU – Full Wide Nodes Minimum PSU Required For N+1

# of Full 1000 W ITE 1200 W ITE 1400 W ITE


1 1
Wide Nodes # of PSU Fault # of PSU Fault # of PSU1 Fault
7 4 828 4 828 5 1180
6 4 966 4 966 4 966
5 3 666 4 1159 4 1159
4 3 873 3 873 3 873
3 3 1000 3 1163 3 1163
2 2 593 3 1200 3 1400
1 2 1000 2 1185 2 1185
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

2100W PSU – Full Wide Nodes Minimum PSU Required For N+1

# of Full 1000 W ITE 1200 W ITE 1400 W ITE


1 1
Wide Nodes # of PSU Fault # of PSU Fault # of PSU1 Fault
7 4 656 5 951 5 951
6 4 765 5 1109 5 1109
5 4 918 4 918 4 918
4 3 672 4 1188 4 1188
3 3 896 3 896 3 896
2 3 1000 3 1200 3 1400
1 2 784 2 784 2 784
1 – Theoretical number that may require unrealistic throttle levels.

Note: When a fault occurs, all Nodes in the chassis must throttle to the average power, in watts, indicated in
the “Fault” column. For more information on N+N and N+1 redundancy see “What is N+N and N+1
Redundancy” section on page 187 in this document.

P a g e | 13 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Flex System Zone Cooling


80mm Fan Module, Pair IBM System x P/N: 43W9078 FC: A0UA
80mm Fan Module, Pair IBM Power Systems FC: 7805

Quantity of 80mm Fans required per number of Nodes installed to maintain cooling redundancy of N+1.

Zone 2 Zone 1
# of 80mm # of Nodes # of 80mm # of Nodes
Fans Required Installed Fans Required Installed
2 1-2 2 1-2
3 3-4 3 3-4
4 5-7 4 5-7

Rear of Flex Chassis


Power 1 10 3 Power 2 5 4
200-240V Supply
IN OUT 200-240V Supply
IN OUT
13,8A Bay 13,8A Bay
50/60Hz 50/60Hz CMM2
I/O Bay I/O Bay I/O Bay I/O Bay

CMM
6 Bay

4
Fan Fan
Bay Bay

Fan 9 Fan 4
Power Fan Power Fan
200-240V Supply
IN OUT Bay 200-240V Supply
IN OUT Bay
13,8A Bay 13,8A Bay
50/60Hz 50/60Hz

Fan 8 6

5
Power
Supply
Bays
3

2
Fan 3
4 1

Fan
Bays
10 5
9 4
8 3
7 2
6 1

Fan Fan
Bay Bay
TX/ RX

Power
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Fan 7 Power
200-240V Supply
IN OUT
13,8A Bay
50/60Hz
Fan 2 LINK

Fan Fan
Bay Bay

Fan 6 2

1
Fan 1
CMM1

1 6 3 2 1 4

IBM Flex System Power Cords


IBM System x Worldwide Power Cords
These power cords are used worldwide to connect Flex System PSUs to PDUs when ordered as part of an IBM
System x order. One of these power cords needs to be ordered for each PSU that is installed in each Flex
System Enterprise Chassis and is connected to a PDU.

Option Feature Code


P/N (FC) P/N Description
39Y7916 6252 2.5m (8.2ft), 16A/100-240V, C19 to IEC 320-C20 Rack Power Cable
– 6292 2m (6.5ft), 16A/100-250V, C19 to IEC 320-C20 Rack Power Cable

IEC320 C19 IEC320 C20

P a g e | 14 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x North American Power Cords


These power cords are only used in North America or countries on a similar type power grid to connect Flex
System PSUs directly to NEMA 6-15R, NEMA L6-20R, and NEMA L15-30R outlets when ordered as part of an
IBM System x order.

Option Feature Code


P/N (FC) P/N Description
00D7195 6566 2.5m (8.2ft), 15A/208V, C19 to NEMA 6-15P Line Cord
00D7196 6537 1.8m (6ft), 15A/208V, C19 to NEMA 6-15P Line Cord
00D7197 A1NV 4.3m (14ft), 15A/250V, C19 to NEMA 6-15P Line Cord
40K9772 6275 4.3m (14ft), 16A/208V, C19 to NEMA L6-20P Line Cord
4.3m (14ft) 30A @ 208V 3 phase Delta Line Cord
00D7192 A2Y3
NEMA L15-30P - (3P+Gnd) to 3x IEC 320 C19

IEC320 C19 NEMA 6-15P IEC320 C19 NEMA L6-20P

NEMA L15-30P - (3P+Gnd) to 3X IEC 320 C19


4.3m (14ft) 30A @ 208V 3 phase Delta line cord IBM System x only option
System x P/N: 00D7192 FC: A2Y3
Six PSU chassis only
IEC 320
NEMA L15-30P Plug C19
30A@208V 3ph Delta

IEC 320
C19

IEC 320
C19

P a g e | 15 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x International Power Cords


These power cords are used internationally to connect Flex System PSUs directly to IEC309 3P+N+G and
PDL/Clipsal outlets when ordered as part of an IBM System x order.

Option Feature Code


P/N (FC) P/N Description
4.3m (14ft) 32A@380-415V 3 phase Wye Line Cord
00D7193 A2Y4
IEC309 3P+N+G to 3X IEC 320 C19
4.3m (14ft) 32A@415V 3 phase Wye Line Cord – Australia & New Zealand
00D7194 A2Y5
PDL/Clipsal 32A (3P+N+Gnd) to 3X IEC 320 C19

IEC309 3P+N+G to 3X IEC 320 C19


4.3m (14ft) 32A@380-415V 3 phase Wye line cord IBM System x only option
System x P/N: 00D7193 FC: A2Y4
Six PSU chassis only
IEC 320
IEC 309 3P+N+G Plug C19
32A@380-415V 3ph Wye

L3 L2

N L1
IEC 320
G
C19

IEC 320
C19

PDL/Clipsal 32A (3P+N+Gnd) to 3X IEC 320 C19


4.3m (14ft) 32A@415V 3 phase Wye line cord IBM System x only option
System x P/N: 00D7194 FC: A2Y5
Six PSU chassis only
IEC 320
PDL/Clipsal 32A (3P+N+Gnd) Plug C19 For use in Australia
32A @ 415V 3ph Wye & New Zealand
L2
L1 N IEC 320
L3 C19
E

IEC 320
C19

P a g e | 16 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems Worldwide Power Cords


This power cord is used worldwide to connect Flex System PSUs to PDUs when ordered as part of an IBM Power
Systems order. One needs to be ordered for each PSU that is installed in each Flex System Enterprise Chassis
and is connected to a PDU.

Option Feature Code


P/N (FC) P/N Description
– 4558 2.5m (8.2ft), 16A/100-240V, C19 to IEC 320-C20 Rack Power Cable

IEC320 C19 IEC320 C20

IBM Power Systems North American Power Cords


These power cords are only used in North America or countries on a similar type power grid to connect Flex
System PSUs directly to NEMA 6-15R and NEMA L6-20R outlets, respectively, when ordered as part of an IBM
System x order. One of these power cords needs to be ordered for each PSU that is installed in each Flex
System Enterprise Chassis and is connected to the respective outlet.

Option Feature Code


P/N (FC) P/N Description
– 1452 4.3m (14ft) 200-240V 15A C19 to NEMA 6-15P
– 3733 2.5m (8.2ft) 200-240V 15A C19 to NEMA 6-15P
– 4560 .3m (14ft) 200-240V 20A C19 to NEMA L6-20P

IEC320 C19 NEMA 6-15P IEC320 C19 NEMA L6-20P

P a g e | 17 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (6x PSU / Flex) – North America


2x Flex (6x PSU) on 60A@208V 3ph PDUs – North America
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex System Power Management Policies” section on page
186 in this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on
page 187 in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex System Zone Cooling” on page 14 in this document.

2500W PSU N+N Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 18 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase
P/N: 39Y8923 or FC: 6061 PDU
P/N: 71763NU or FC: 6051 P/N: 46M4003 or FC: 5897

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 19 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 20 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase
P/N: 39Y8923 or FC: 6061 PDU
P/N: 71763NU or FC: 6051 P/N: 46M4003 or FC: 5897

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 21 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex (6x PSU) on 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex System Power Management Policies” section on page
186 in this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on
page 187 in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex System Zone Cooling” on page 14 in this document.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 22 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 23 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 24 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 25 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 26 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 27 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 28 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

IBM Monitored 30A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5416 or FC: 6654
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5418 or FC: 6655

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 29 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 30 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (5x PSU / Flex) – North America


1x Flex (5x PSU) on 60A@208V 3ph PDUs – North America
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 31 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 32 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 33 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 34 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 35 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 36 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 37 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 38 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 5x 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

IBM Monitored 30A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5416 or FC: 6654
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5418 or FC: 6655

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 39 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 40 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (4x PSU / Flex) – North America


3x Flex (4x PSU) on 60A@208V 3ph PDUs – North America
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

P a g e | 41 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

P a g e | 42 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 43 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex (4x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

P a g e | 44 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 45 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex (4x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

P a g e | 46 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 47 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex (4x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

P a g e | 48 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 49 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 60A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 50 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 51 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 52 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 53 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 54 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 55 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 56 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 57 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

IBM Monitored 30A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5416 or FC: 6654
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5418 or FC: 6655

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 58 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 59 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (3x PSU / Flex) – North America

2x Flex (3x PSU) on 60A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

P a g e | 60 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 61 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 62 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 63 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 64 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 65 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 66 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 67 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

IBM Monitored 30A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5416 or FC: 6654
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5418 or FC: 6655

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 68 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 69 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (2x PSU / Flex) – North America


1x Flex (2x PSU) on 60A@208V 3ph PDUs – North America
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 70 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

IBM Monitored 60A@208V 3 phase PDU


P/N: 42R8744 or FC: 7196

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 71 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@208V 3 phase Configuration

IBM Basic 60A@208V 3 phase PDUs IBM Switched & Monitored 60A@208V 3 phase PDU
P/N: 39Y8923 or FC: 6061 P/N: 46M4003 or FC: 5897
P/N: 71763NU or FC: 6051

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 72 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 50A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 73 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 74 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 50A@208V 3 phase Configuration

IBM Basic 50A@208V 3 phase PDUs IBM Switched & Monitored 50A@208V 3 phase PDU
P/N: 46M4140 or FC: 5926 P/N: 46M4134 or FC: 5931

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 50A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 75 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 30A@208V 3ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

P a g e | 76 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not have an available PDU to support this configuration. A suitable IBM System x
PDU from the list above or a third party PDU will need to be used to implement this configuration.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 77 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@208V 3 phase Configuration

IBM Switched & Monitored 30A@208V 3 phase PDU


P/N: 46M4167 or FC: 5928

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@208V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 78 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 60A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 79 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

IBM Monitored 60A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5417 or FC: 6492

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 80 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 60A@200-240V 1 phase Configuration

IBM Basic 60A@200-240V 1 phase PDUs IBM Switched & Monitored 60A@200-240V 1 phase PDU
P/N: 39Y8940 or FC: A11U P/N: 46M4002 + input line cord P/N: 40K9615 = FC: 5902
P/N: 39Y8948 + input line cord P/N: 40K9615 = FC: 6063
P/N: 71762NX + input line cord P/N: 40K9615 = FC: 6501

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 60A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 81 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 30A@200-240V 1ph PDUs – North America


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

IBM Monitored 30A@200-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5416 or FC: 6654
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5418 or FC: 6655

See the “IBM Power Systems PDU Information North America” section on page 168 for further details on IBM Power
Systems PDUs.

P a g e | 82 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 30A@200-240V 1 phase Configuration

IBM Basic 30A@200-240V 1 phase PDUs IBM Switched & Monitored 30A@200-240V 1 phase PDU
P/N: 39Y8939 or FC: A11T P/N: 46M4002 + input line cord P/N: 40K9614 = FC: 5901
P/N: 39Y8948 + input line cord P/N: 40K9614 = FC: 6062
P/N: 71762NX + input line cord P/N: 40K9614 = FC: 6500

See the “IBM System x PDU Information North America” section on page 168 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 30A@200-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 83 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (6x PSU / Flex) – International


2x Flex (6x PSU) on 32A@380-415V 3ph PDUs – International
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N Wiring Diagram

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 84 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 85 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N Wiring Diagram

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 86 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 87 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 88 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 89 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 90 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 91 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (6x PSU) on 32A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 92 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU PDU Input Line Cords


P/N: 42R8743 or FC: 7189 + input line cord D, E, or F D – P/N: 39M5414 or FC: 6656 (IEC 309 P+N+G)
E – P/N: 39M5419 or FC: 6657 (AUS/NZ 3112 32A)
F – P/N: 39M5420 or FC: 6658 (KSC 8305 30A)

IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 93 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 94 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (5x PSU / Flex) – International


1x Flex (5x PSU) on 32A@380-415V 3ph PDUs – International
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 95 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 96 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 97 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 98 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 99 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 100 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (5x PSU) on 32A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=4) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=4) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.
IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 101 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU PDU Input Line Cords


P/N: 42R8743 or FC: 7189 + input line cord D, E, or F D – P/N: 39M5414 or FC: 6656 (IEC 309 P+N+G)
E – P/N: 39M5419 or FC: 6657 (AUS/NZ 3112 32A)
F – P/N: 39M5420 or FC: 6658 (KSC 8305 30A)

IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 102 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 103 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (4x PSU / Flex) – International


3 x Flex (4x PSU) on 32A@380-415V 3ph PDUs – International
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

P a g e | 104 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.
IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

P a g e | 105 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 106 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3 x Flex (4x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

P a g e | 107 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 108 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex (4x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDUs are not supported with this configuration due to IBM Power Systems single phase PDUs derating.

P a g e | 109 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 110 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 32A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 111 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 112 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 113 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 114 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 115 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 116 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 32A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 117 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU PDU Input Line Cords


P/N: 42R8743 or FC: 7189 + input line cord D, E, or F D – P/N: 39M5414 or FC: 6656 (IEC 309 P+N+G)
E – P/N: 39M5419 or FC: 6657 (AUS/NZ 3112 32A)
F – P/N: 39M5420 or FC: 6658 (KSC 8305 30A)

IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 118 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 119 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (3x PSU / Flex) – International


2x Flex (3x PSU) on 32A@380-415V 3ph PDUs – International
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 120 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 121 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 122 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 123 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 124 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 125 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (3x PSU) on 32A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy NA Not Supported
AC Power Source Redundancy w/ Compute Node Throttling Allowed NA Not Supported
Power Module Redundancy N+1 (N=2) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=2) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs

P a g e | 126 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU PDU Input Line Cords


P/N: 42R8743 or FC: 7189 + input line cord D, E, or F D – P/N: 39M5414 or FC: 6656 (IEC 309 P+N+G)
E – P/N: 39M5419 or FC: 6657 (AUS/NZ 3112 32A)
F – P/N: 39M5420 or FC: 6658 (KSC 8305 30A)

IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 127 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU Configurations (2x PSU / Flex) – International


1x Flex (2x PSU) on 32A@380-415V 3ph PDUs – International
IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 128 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

IBM Monitored 32A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5413 or FC: 6489
P/N: 42R8743 or FC: 7189 + input line cord P/N: 69Y1619 or FC: 6667

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 129 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 32A@380-415V 3 phase Configuration

IBM Basic 32A@380-415V 3 phase PDUs IBM Switched & Monitored 32A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 40K9611 = FC: 6066 P/N: 46M4002 + input line cord P/N: 40K9611 = FC: 5905
P/N: 46M4143 or FC: 5927 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9611 = FC: 6504

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 130 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 16A@380-415V 3ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

IBM Monitored 16A@380-415V 3 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

P a g e | 131 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration
IBM Monitored 16A@380-415V 3 phase PDU
P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5412 or FC: 6653

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

P a g e | 132 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Currently IBM Power Systems does not support the Flex System 2100W PSU.

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292, or IBM Power Systems FC: 4558 | See “IBM Flex Power
Cords” section for further details.

IBM System x PDU Options for This 16A@380-415V 3 phase Configuration

IBM Basic 16A@380-415V 3 phase PDUs IBM Switched & Monitored 16A@380-415V 3 phase PDUs
P/N: 39Y8948 + input line cord P/N: 47C2495 = FC: A3T3 P/N: 46M4002 + input line cord P/N: 47C2495 = FC: A3T4
P/N: 71762NX + input line cord P/N: 47C2495 = FC: A3TC

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 16A@380-415V 3 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 133 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 63A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 134 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 135 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+1 Wiring Diagram for Derated International Power Systems Single Phase PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU


P/N: 42R8743 or FC: 7189 + input line cord P/N: 39M5415 or FC: 6491

Note: IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for
63A single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 136 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 63A@220-240V 1 phase Configuration

IBM Basic 63A@220-240V 1 phase PDUs IBM Switched & Monitored 63A@220-240V 1 phase PDU
P/N: 39Y8935 or FC: A11W P/N: 46M4002 + input line cord P/N: 40K9613 = FC: 5904
P/N: 39Y8948 + input line cord P/N: 40K9613 = FC: 6065 P/N: 46M4137 or FC: 5932
P/N: 71762NX + input line cord P/N: 40K9613 = FC: 6503

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 63A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 137 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (2x PSU) on 2x 32A@220-240V 1ph PDUs – International


IBM Flex Power Management Policies
Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=1) 1
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=1) 1
Power Module Redundancy N+1 (N=1) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=1) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 138 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2500W PSU N+N & N+1 Wiring Diagram for Derated International Power Systems Single Phase
PDUs

Requires Flex System power cord IBM Power Systems FC: 4558 | See “IBM Flex Power Cords” section for further details.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

IBM Monitored 63A@220-240V 1 phase PDU PDU Input Line Cords


P/N: 42R8743 or FC: 7189 + input line cord D, E, or F D – P/N: 39M5414 or FC: 6656 (IEC 309 P+N+G)
E – P/N: 39M5419 or FC: 6657 (AUS/NZ 3112 32A)
F – P/N: 39M5420 or FC: 6658 (KSC 8305 30A)

IBM Power Systems international single phase PDUs are derated to 24A for 32A single phase PDUs and 48A for 63A
single phase PDUs.

See the “IBM Power Systems PDU Information International” section on page 175 for further details on IBM Power
Systems PDUs.

2500W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

P a g e | 139 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDUs are not supported with this configuration due to IBM Power Systems single phase PDUs derating.

2100W PSU N+N & N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 140 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2100W PSU N+1 Wiring Diagram

Requires Flex System power cord IBM System x FC: 6252, 6292 | See “IBM Flex Power Cords” section for further details.

IBM System x PDU Options for This 32A@220-240V 1 phase Configuration

IBM Basic 32A@220-240V 1 phase PDUs IBM Switched & Monitored 32A@220-240V 1 phase
P/N: 39Y8934 (32A IEC 309 P+N+G) or FC: A11V PDU
P/N: 39Y8936 (30A KSC 8305) or FC: A11Y P/N: 46M4004 + input line cord A = FC: 5910
P/N: 39Y8937 (32A AUS/NZ 3112) or FC: A11X P/N: 46M4004 + input line cord B = FC: 5913
P/N: 39Y8948 + input line cord A = FC: 6064 P/N: 46M4004 + input line cord C = FC: 5914
P/N: 39Y8948 + input line cord B = FC: 6067
P/N: 39Y8948 + input line cord C = FC: 6068 PDU Input Line Cords
P/N: 71762NX + input line cord A = FC: 6502 A – P/N: 40K9612 (IEC 309 P+N+G)
P/N: 71762NX + input line cord B = FC: 6505 B – P/N: 40K9617 (AUS/NZ 3112 32A)
P/N: 71762NX + input line cord C = FC: 6506 C – P/N: 40K9618 (KSC 8305 30A)

See the “IBM System x PDU Information International” section on page 174 for further details on IBM System x PDUs.

IBM Power Systems PDU Options for This 32A@220-240V 1 phase Configuration

Currently IBM Power Systems does not support the Flex System 2100W PSU.

P a g e | 141 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

UPS Configurations
1x Flex (6x PSU) on 2x IBM UPS11000 – World Wide
This configuration will consume 20U in rack (Flex = 10U, two IBM UPS11000 = 10U). This means a maximum of
two of this configuration can be installed in a 42U rack.

IBM Flex Power Management Policies


Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=3) 3
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=3) 3
Power Module Redundancy N+1 (N=5) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=5) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.

IBM UPS11000 P/N: 53959KX & EBM P/N: 69Y1986 FC: 5735

See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655

P a g e | 142 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 2x IBM UPS6000 – World Wide


This configuration will consume 18U in rack (Flex = 10U, two IBM UPS600 = 8U). This means a maximum of two
of this configuration can be installed in a 42U rack.

IBM Flex Power Management Policies


Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.

IBM UPS6000 P/N: 53956KX & EBM P/N: 69Y1984 FC: 5734

See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655

P a g e | 143 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x Flex (4x PSU) on 2x IBM UPS6000 – North America


This configuration will consume 18U in rack (Flex = 10U, two IBM UPS600 = 8U). This means a maximum of two
of this configuration can be installed in a 42U rack.

IBM Flex Power Management Policies


Power Management Policies Redundancy PSU Failure Limit †
AC Power Source Redundancy N+N (N=2) 2
AC Power Source Redundancy w/ Compute Node Throttling Allowed N+N (N=2) 2
Power Module Redundancy N+1 (N=3) 1
Power Module Redundancy w/ Compute Nodes Throttling Allowed N+1 (N=3) 1
Basic Power Management None 0
† - The maximum number of PSU that can fail and the chassis remain operational
Note: For more information IBM Flex power management policies see “IBM Flex Power Management Policies” section on page 186 in
this document. For more information on N+1 and N+N redundancy see “What is N+N and N+1 Redundancy” section on page 187
in this document.

Important Notice: For information on the number of fans needed to support a given number of nodes in a chassis, see
section” IBM Flex Zone Cooling” on page 14 in this document.

2500W PSU N+N & N+1 Wiring Diagram

Requires Flex power cord FC: 6252 or 6292 | See “IBM Flex Power Cords” section for further details.

IBM UPS6000 P/N: 53956AX & EBM P/N: 69Y1984 FC: 5734

See the IBM System x Uninterruptible Power Supply (UPS) Guide for further details on the IBM UPS6000:
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP101655

P a g e | 144 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PureFlex Systems x-config Configuration Examples


What is the difference between PureFlex Systems and Flex Systems?

PureFlex Systems is a pre-configured, pre-integrated infrastructure with integrated management and cloud
capabilities, factory tuned from IBM with x86 and Power hybrid solution.

Flex Systems allows you to build and tune a custom configuration based on the most advanced blade server
in the market with maximum x86 EP compute and memory performance.

This section will cover some of the predefined PureFlex configurations examples available through Systems x.
Below is a link to the IBM System x and Cluster Solutions Configurator (x-config) used to create PureFlex
configurations for System x orders.

https://www.ibm.com/products/hardware/configurator/americas/bhui/asit/index.html

Below are some quick links to the PureFlex Systems x-config Configuration Examples in this section:

3x Flex Chassis w/ 4x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 146
3x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 147
3x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-240V – Page 149
2x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V – Page 150
2x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-240V – Page 152
2x Flex Chassis w/ 6x ToR Switches – 1 Phase 20A@200-240V & 30A@200-240V– Page 153

P a g e | 145 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex Chassis w/ 4x ToR Switches – 3 Phase 60A@208V & 32A@380-415V


– x-config Example

1x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
1x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


4x PDU A

North America PDU Options

PDU A Options – North America


FC: 5897 – 60A@208V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for information on the 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 5907 – 32A@380-415V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G

P a g e | 146 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V


– x-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


2x PDU A
4x PDU B

North America PDU Options

PDU A Options – North America


FC: 5895 – 60A@208V 3ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 173 for information on the 60A@208V 3ph line cord plug IEC309 3P+G
Or
FC: 5909 – 60A@200-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 170 for information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
FC: 5908 – 30A@200-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 169 for information on the 30A@200-240V 1ph line cord plug NEMA L6-30

P a g e | 147 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 5897 – 60A@208V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for information on the 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 5912 – 32A@380-415V 3ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
FC: 5911 – 63A@220-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 179 for information on the 63A@200-240V 1ph line cord plug IEC309 P+N+G
Or
FC: 5910 – 32A@220-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 176 for information on the 32A@200-240V 1ph line cord plug IEC309 P+N+G
Or
FC: 5913 – 32A@230-240V 1ph – Australia / New Zealand Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 177 for information on the 32A@200-240V 1ph line cord plug AUS/NZ 3112
Or
FC: 5912 – 30A@220V 1ph South Korea Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 178 for information on the 32A@200-240V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 5907 – 32A@380-415V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G

P a g e | 148 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-


240V – x-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


6x PDU A

North America PDU Options

PDU A Options – North America


FC: 5902 – 60A@200-240V 1ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 170 for information on the 60A@200-240V 1ph line cord plug IEC309 2P+G

International PDU Options

PDU A Options – International


FC: 5904 – 63A@220-240V 1ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 179 for information on the 63A@220-240V 1ph line cord plug IEC309 P+N+G

P a g e | 149 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex Chassis w/ 6x ToR Switches – 3 Phase 60A@208V & 32A@380-415V


– x-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


2x PDU A
2x PDU B

North America PDU Options

PDU A Options – North America


FC: 5895 – 60A@208V 3ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 173 for information on the 60A@208V 3ph line cord plug IEC309 3P+G
Or
FC: 5909 – 60A@200-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 170 for information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
FC: 5908 – 30A@200-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 169 for information on the 30A@200-240V 1ph line cord plug NEMA L6-30

P a g e | 150 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 5897 – 60A@208V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for information on the 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 5912 – 32A@380-415V 3ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
FC: 5911 – 63A@220-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 179 for information on the 63A@200-240V 1ph line cord plug IEC309 P+N+G
Or
FC: 5910 – 32A@220-240V 1ph Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 176 for information on the 32A@200-240V 1ph line cord plug IEC309 P+N+G
Or
FC: 5913 – 32A@230-240V 1ph – Australia / New Zealand Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 177 for information on the 32A@200-240V 1ph line cord plug AUS/NZ 3112
Or
FC: 5912 – 30A@220V 1ph South Korea Switched & Monitored PDU – 12x C13 Outlets Front
PDU line cord is included
See page 178 for information on the 32A@200-240V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 5907 – 32A@380-415V 3ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G

P a g e | 151 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex Chassis w/ 6x ToR Switches – 1 Phase 60A@200-240V & 63A@220-


240V – x-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


4x PDU A

North America PDU Options

PDU A Options – North America


FC: 5902 – 60A@200-240V 1ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 170 for information on the 60A@200-240V 1ph line cord plug IEC309 2P+G

International PDU Options

PDU A Options – International


FC: 5904 – 63A@220-240V 1ph Switched & Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 179 for information on the 63A@220-240V 1ph line cord plug IEC309 P+N+G

P a g e | 152 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex Chassis w/ 6x ToR Switches – 1 Phase 20A@200-240V & 30A@200-


240V – x-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R

Needed Quantities of PDUs


2x PDU A

North America PDU Options

PDU A Options – North America


FC: 5908 – 30A@200-240V 1ph Switched & Monitored PDU – 12x C19 Outlets Front
PDU line cord is included
See page 169 for information on the 30A@200-240V line cord plug NEMA L6-30P

International PDU Options

This PureFlex configuration is not supported internationally. It is only supported in North America and countries
that use the NEMA type electric plugs and outlets.

P a g e | 153 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PureFlex Systems e-config Configuration Examples


What is the difference between PureFlex Systems and Flex Systems?

PureFlex Systems is a pre-configured, pre-integrated infrastructure with integrated management and cloud
capabilities, factory tuned from IBM with x86 and Power hybrid solution.

Flex Systems allows you to build and tune a custom configuration based on the most advanced blade server
in the market with maximum x86 EP compute and memory performance.

This section will cover some of the predefined PureFlex configurations examples available through IBM Power
Systems. Below is a link to the IBM Configurator for e-Business (e-config) used to create PureFlex
configurations for IBM Power Systems orders.

http://www.ibm.com/services/econfig/announce/index.htm

Below are some quick links to the PureFlex Systems e-config Configuration Examples in this section:

3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 3ph 60A@208V & 32A@380-415V – Page 155
3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 1ph 60A@200-240V & 63A@220-240V – Page 157
2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 3ph 60A@208V & 32A@380-415V – Page 159
2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 1ph 60A@200-240V & 63A@220-240V – Page 161
2x Flex Chassis w/ 6x ToR Switches & 7x V7000 – 1 Phase 20A@200-240V & 30A@200-240V – Page 163
1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 3ph 60A@208V & 32A@380-415V – Page 164
1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 1ph 60A@200-240V & 63A@220-240V– Page 166

P a g e | 154 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 3ph 60A@208V &


32A@380-415V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
2x Storwize V7000 Storage

Needed Quantities of PDUs


2x PDU A
4x PDU B

North America PDU Options

PDU A Options – North America


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – North America


60A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6492
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
30A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6654
See page 169 for further information on the 60A@200-240V 1ph line cord plug NEMA L6-30P

P a g e | 155 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 7196 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for further information on the attached 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532
Or
16A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6653
See page 180 for information on the 16A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
63A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6491
See page 179 for information on the 63A@220-240V line cord plug IEC309 P+N+G
Or
32A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6656
See page 176 for information on the 32A@380-415V 3ph line cord plug IEC309 P+N+G
Or
32A@230-240V 1ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6657
See page 177 for information on the 32A@230-240V 1ph line cord plug AUS/NZ 3112
Or
30A@220V 1ph South Korea line cord option for 7109 & 7188 PDUs is FC: 6658
See page 178 for information on the 30A@220V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need one of the country appropriate lines cords from the section below.

PDU B Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532

P a g e | 156 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

3x PureFlex Chassis w/ 6x ToR Switches & 2x V7000 – 1ph 60A@200-240V


& 63A@220-240V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
2x Storwize V7000 Storage

Needed Quantities of PDUs


6x PDU A

North America PDU Options

PDU A Options – North America


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6492 60A@200-240V 1ph
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G

P a g e | 157 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

International PDU Options

PDU A Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6489 – 63A@220-240V 1ph
See page 179 for information on the 63A@220-240V 1ph line cord plug IEC309 P+N+G

P a g e | 158 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 3ph 60A@208V &


32A@380-415V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
7x Storwize V7000 Storage

Needed Quantities of PDUs


2x PDU A
2x PDU B

North America PDU Options

PDU A Options – North America


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – North America


60A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6492
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
30A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6654
See page 169 for further information on the 60A@200-240V 1ph line cord plug NEMA L6-30P

P a g e | 159 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 7196 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for further information on the attached 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532
Or
16A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6653
See page 180 for information on the 16A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
63A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6491
See page 179 for information on the 63A@220-240V line cord plug IEC309 P+N+G
Or
32A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6656
See page 176 for information on the 32A@380-415V 3ph line cord plug IEC309 P+N+G
Or
32A@230-240V 1ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6657
See page 177 for information on the 32A@230-240V 1ph line cord plug AUS/NZ 3112
Or
30A@220V 1ph South Korea line cord option for 7109 & 7188 PDUs is FC: 6658
See page 178 for information on the 30A@220V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need one of the country appropriate lines cords from the section below.

PDU B Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532

P a g e | 160 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x PureFlex Chassis w/ 6x ToR Switches & 7x V7000 – 1ph 60A@200-240V


& 63A@220-240V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
7x Storwize V7000 Storage

Needed Quantities of PDUs


2x PDU A
4x PDU B

North America PDU Options

PDU A Options – North America


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – North America


60A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6492
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
30A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6654
See page 169 for further information on the 60A@200-240V 1ph line cord plug NEMA L6-30P

P a g e | 161 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6492 60A@200-240V 1ph
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G

International PDU Options

PDU A Options – International


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532
Or
16A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6653
See page 180 for information on the 16A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
63A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6491
See page 179 for information on the 63A@220-240V line cord plug IEC309 P+N+G
Or
32A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6656
See page 176 for information on the 32A@380-415V 3ph line cord plug IEC309 P+N+G
Or
32A@230-240V 1ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6657
See page 177 for information on the 32A@230-240V 1ph line cord plug AUS/NZ 3112
Or
30A@220V 1ph South Korea line cord option for 7109 & 7188 PDUs is FC: 6658
See page 178 for information on the 30A@220V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6489 – 63A@220-240V 1ph
See page 179 for information on the 63A@220-240V 1ph line cord plug IEC309 P+N+G

P a g e | 162 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

2x Flex Chassis w/ 6x ToR Switches & 7x V7000 – 1 Phase 20A@200-240V &


30A@200-240V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
7x Storwize V7000 Storage

Needed Quantities of PDUs


2x PDU A

North America PDU Options

PDU A Options – North America


FC: 7189 – Monitored PDU – 12x C13 Outlets Front
PDU will need line cord FC: 6654 – NEMA L6-30 – 30A@200-240V 1ph
See page 169 for further information on the 30A@200-240V 1ph line cord plug NEMA L6-30

International PDU Options

This PureFlex configuration is not supported internationally. It is only supported in North America and countries
that use the NEMA type electric plugs and outlets.

P a g e | 163 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 3ph 60A@208V &
32A@380-415V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
12x Storwize V7000 Storage

Needed Quantities of PDUs


4x PDU A
2x PDU B

North America PDU Options

PDU A Options – North America


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – North America


60A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6492
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
30A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6654
See page 169 for further information on the 60A@200-240V 1ph line cord plug NEMA L6-30P

P a g e | 164 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 7196 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU line cord is included
See page 173 for further information on the attached 60A@208V 3ph line cord plug IEC309 3P+G

International PDU Options

PDU A Options – International


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532
Or
16A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6653
See page 180 for information on the 16A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
63A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6491
See page 179 for information on the 63A@220-240V line cord plug IEC309 P+N+G
Or
32A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6656
See page 176 for information on the 32A@380-415V 3ph line cord plug IEC309 P+N+G
Or
32A@230-240V 1ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6657
See page 177 for information on the 32A@230-240V 1ph line cord plug AUS/NZ 3112
Or
30A@220V 1ph South Korea line cord option for 7109 & 7188 PDUs is FC: 6658
See page 178 for information on the 30A@220V 1ph line cord plug KSC 8305

PDU B Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need one of the country appropriate lines cords from the section below.

PDU B Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532

P a g e | 165 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

1x PureFlex Chassis w/ 6x ToR Switches & 12x V7000 – 1ph 60A@200-240V


& 63A@220-240V – e-config Example

2x ToR Ethernet Switch


IBM G8264R
2x ToR 24 Port FC Switch
IBM SAN24B-4
2x ToR Management Switch
IBM G8052R
12x Storwize V7000 Storage

Needed Quantities of PDUs


4x PDU A
2x PDU B

North America PDU Options

PDU A Options – North America


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – North America


60A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6492
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G
Or
30A@200-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6654
See page 169 for further information on the 60A@200-240V 1ph line cord plug NEMA L6-30P

P a g e | 166 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDU B Options – North America


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6492 60A@200-240V 1ph
See page 170 for further information on the 60A@200-240V 1ph line cord plug IEC309 2P+G

International PDU Options

PDU A Options – International


FC: 7109 – Monitored PDU – 12x C13 Outlets Front | or | FC: 7188 – Basic PDU – 12x C13 Outlets Front
PDU will need one of the country appropriate lines cords from the section below.

PDU A Line Cord Options – International


32A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6489
See page 182 for information on the 32A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
32A@415V 3ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6667
See page 181 for information on the 32A@415V 3ph line cord plug PDL 56P532 / Clipsal 56PA532
Or
16A@380-415V 3ph line cord option for 7109 & 7188 PDUs is FC: 6653
See page 180 for information on the 16A@380-415V 3ph line cord plug IEC309 3P+N+G
Or
63A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6491
See page 179 for information on the 63A@220-240V line cord plug IEC309 P+N+G
Or
32A@220-240V 1ph line cord option for 7109 & 7188 PDUs is FC: 6656
See page 176 for information on the 32A@380-415V 3ph line cord plug IEC309 P+N+G
Or
32A@230-240V 1ph – Australia / New Zealand line cord option for 7109 & 7188 PDUs is FC: 6657
See page 177 for information on the 32A@230-240V 1ph line cord plug AUS/NZ 3112
Or
30A@220V 1ph South Korea line cord option for 7109 & 7188 PDUs is FC: 6658
See page 178 for information on the 30A@220V 1ph line cord plug KSC 8305

PDU A Options – International


FC: 7189 – Monitored PDU – 9x C19 Outlets Front & 3x C13 Outlets Back
PDU will need line cord FC: 6489 – 63A@220-240V 1ph
See page 179 for information on the 63A@220-240V 1ph line cord plug IEC309 P+N+G

P a g e | 167 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x & Power Systems North American PDUs


IBM System x PDU Information North America
See the “IBM System x PDU Guide – North America” for more information on IBM’s System x North American
PDUs.

Line Cord PDU + Number /


PDU Part Part Line Line Cord Type of Form
PDU Name Number Number Cord FC Phase Voltage (Derated) Line Cord Plug Outlet Factor
Front End 39Y8939 Comes with A11T 1ph 200-240V 30A (24A) NEMA L6-30P
3 / C19 Front ½U
Basic 39Y8940 PDU A11U 1ph 200-240V 60A (48A) IEC 309 2P+G
Enterprise – C13 40K9614 6012 1ph 200-240V 30A (24A) NEMA L6-30P
39Y8941 12 / C13 Front 1U
Basic 40K9615 6013 1ph 200-240V 60A (48A) IEC 309 2P+G
40K9614 6062 1ph 200-240V 30A (24A) NEMA L6-30P
Enterprise 39Y8948
40K9615 6063 1ph 200-240V 60A (48A) IEC 309 2P+G 6 / C19 Front 1U
Basic
39Y8923 Attached 6061 3ph Δ 208V 60A (27.7A/ph) IEC 309 3P+G
Ultra Density 40K9614 6500 1ph 200-240V 30A (24A) NEMA L6-30P
71762NX 9 / C19 Front
Enterprise 40K9615 6501 1ph 200-240V 60A (48A) IEC 309 2P+G 1U
3 / C13 Back
Basic 71763NU Attached 6051 3ph Δ 208V 60A (27.7A/ph) IEC 309 3P+G
0U 24 C13 46M4125 Attached 5923 3ph Δ 208V 30A (13.85A/ph) NEMA L21-30P
24 / C13 Front 0U
Basic 46M4128 Attached 5924 1ph 200-240V 30A (24A) NEMA L6-30P
1
0U 12 C19 / 12 C13 12 / C19 Front
46M4140 Attached 5926 3ph Δ 208V 50A (23.09A/ph) CS8365L 0U
Basic 12 / C13 Back
Enterprise PDU+ - 40K9614 6032 1ph 200-240V 30A (24A) NEMA L6-30P
39M2816 12 / C13 Front 1U
C13 Monitored 40K9615 6033 1ph 200-240V 60A (48A) IEC 309 2P+G
40K9614 5908 1ph 200-240V 30A (24A) NEMA L6-30P
1U 12 C13 46M4004
40K9615 5909 1ph 200-240V 60A (48A) IEC 309 2P+G 12 / C13 Front 1U
Switched & Monitored
46M4005 Attached 5895 3ph Δ 208V 60A (27.7A/ph) IEC 309 3P+G
40K9614 5901 1ph 200-240V 30A (24A) NEMA L6-30P
1U 9 C19 / 3 C13 46M4002 9 / C19 Front
40K9615 5902 1ph 200-240V 60A (48A) IEC 309 2P+G 1U
Switched & Monitored 3 / C13 Back
46M4003 Attached 5897 3ph Δ 208V 60A (27.7A/ph) IEC 309 3P+G
1
0U 24 C13U1
46M4116 Attached 5929 1ph 200-240V 30A (24A) NEMA L6-30P 24 / C13 Front 0U
Switched & Monitored
1
0U 12 C19 / 12 C13 12 / C19 Front
46M4134 Attached 5931 3ph Δ 208V 50A (23.09A/ph) CS8365L 0U
Switched & Monitored 12 / C13 Back
1U 9 C19 / 3 C13 9 / C19 Front
46M4167 Attached 5928 3ph Δ 208V 30A (13.85A/ph) NEMA L21-30P 1U
Switched & Monitored 3 / C13 Back
1 – Use caution when using 0U PDUs with IBM Flex System. Be aware that 0U PDUs can impede serviceability of components in the back of
the IBM Flex System Enterprise Chassis.

IBM Power Systems PDU Information North America


PDU PDU Line Cord Line Cord Line Cord Number / Form
Feature Part Feature Part Line Cord Amperage Type of Factor
Code Number Code Number Phase Voltage (Derated) Line Cord Plug Outlet
6492 39M5417 1ph 200-240V 60A (48) IEC 309 2P+G
7109
44V3897 6654 39M5416 1ph 200-240V 30A (24A) NEMA L6-30P 12 / C13 Front 1U
Monitored 2
6655 39M5418 1ph 200-240V 30A (24A) RS 3750DP
6492 39M5417 1ph 200-240V 60A (48) IEC 309 2P+G
7188
39J1183 6654 39M5416 1ph 200-240V 30A (24A) NEMA L6-30P 12 / C13 Front 1U
Basic 2
6655 39M5418 1ph 200-240V 30A (24A) RS 3750DP
6492 39M5417 1ph 200-240V 60A (48) IEC 309 2P+G
7189 6 / C19 Front
42R8743 6654 39M5416 1ph 200-240V 30A (24A) NEMA L6-30P 1U
Monitored 2 3 / C13 Back
6655 39M5418 1ph 200-240V 30A (24A) RS 3750DP
7196 60A 6 / C19 Front
42R8744 Attached - 3ph Δ 208V IEC 309 3P+G 1U
Monitored (27.7A/ph) 3 / C13 Back
2 – Watertight plug, not commonly used

P a g e | 168 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x & Power Systems North American PDUs Input Line Cords
NEMA L6-30
NEMA L6-30P (4.3m) 30A (24A Derated) @ 200V-240V Single Phase

200-240V 100-120V

100-120V
G

X
EQUIP.
GR. Y
G

NEMA L6-30

Used with:
IBM System x PDU Information North America

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
Comes with
Front End Basic 39Y8939 A11T 3 / C19 Front ½U
PDU
Enterprise – C13 Basic 39Y8941 40K9614 6012 12 / C13 Front 1U
Enterprise Basic 39Y8948 40K9614 6062 6 / C19 Front 1U
9 / C19 Front
Ultra Density Enterprise Basic 71762NX 40K9614 6500 1U
3 / C13 Back
0U 24 C13 Basic 46M4128 Attached 5924 24 / C13 Front 0U
Enterprise PDU+ - C13 Monitored 39M2816 40K9614 6032 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9614 5908 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9614 5901 1U
3 / C13 Back
0U 24 C13U Switched & Monitored 46M4116 Attached 5929 24 / C13 Front 0U

IBM Power Systems PDU Information North America

PDU Line Cord Line Cord Number / Form


Part Feature Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6654 39M5416 12 / C13 Front 1U
7188 Basic 39J1183 6654 39M5416 12 / C13 Front 1U
6 / C19 Front
7189 Monitored 42R8743 6654 39M5416 1U
3 / C13 Back

P a g e | 169 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC 309 2P+G – 60A@200-240V 1ph


IEC 309 2P+G (4.3m) - 60A (48A Derated) @ 200V-240V Single Phase Plug (Type 360P6W)

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 360R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL360R6W
Matching connector listing 360C6W IP-67 HUBBELL, Hubbell connector P/N HBL360C6W

Female Sleeve Male Pin L2


100-120V 200-240V
L1
100-120V
L2 L1 L1 L2
G
G G
EQUIP.
GR.

Used with:
IBM System x PDU Information North America

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
Comes with
Front End Basic 39Y8940 A11U 3 / C19 Front ½U
PDU
Enterprise – C13 Basic 39Y8941 40K9615 6013 12 / C13 Front 1U
Enterprise Basic 39Y8948 40K9615 6063 6 / C19 Front 1U
9 / C19 Front
Ultra Density Enterprise Basic 71762NX 40K9615 6501 1U
3 / C13 Back
Enterprise PDU+ - C13 Monitored 39M2816 40K9615 6033 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9615 5909 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9615 5902 1U
3 / C13 Back

IBM Power Systems PDU Information North America

PDU Line Cord Line Cord Number / Form


PDU Feature Part Feature Part Type of Factor
Code Number Code Number Outlet
7109 Monitored 44V3897 6492 39M5417 12 / C13 Front 1U
7188 Basic 39J1183 6492 39M5417 12 / C13 Front 1U
6 / C19 Front
7189 Monitored 42R8743 6492 39M5417 1U
3 / C13 Back

P a g e | 170 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

NEMA L21-30
Attached 3.0 meter line cord with NEMA L21-30P Plug
30A (13.85A / Phase Derated) @ 200V-240V Three Phase Delta
41.55A Total Derated Circuit Capacity

L21-30 Z
X 120V 208V
Y
N
Y 208V
G
Z
120V 208V
N
120V
X SYS.
GR.
G

EQUIP.
GR.

Used with:
IBM System x PDUs

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
0U 24 C13 Basic 46M4125 Attached 5923 24 / C13 Front 0U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4167 Attached 5928 1U
3 / C13 Back

IBM Power Systems PDU Information North America


Currently IBM Power Systems does not have an available PDU to support this outlet. A suitable IBM System
x PDU from the list above or a third party PDU will need to be used to connect this outlet.

P a g e | 171 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

CS8365L – 50A@208V 3ph


Attached 3.0 meter line cord with CS8365L Plug
50A (23.09A / Phase Derated) 200V-240V Three Phase Delta
69.27A Total Derated Circuit Capacity

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord.
Matching receptacle listing CS8369
Matching connector listing CS8364

Used with:
46M4140 – 0U 12 C19/12 C13 PDU Basic
46M4134 – 0U 12 C19/12 C13 Switched and Monitored

Female Male Z
208V 208V 120V
X X
Y Y Y
208V 120V
Z Z
G G X
120V
G

EQUIP.
GR.

Used with:
IBM System x PDU Information North America

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
12 / C19 Front
0U 12 C19 / 12 C13 Basic 46M4140 Attached 5926 0U
12 / C13 Back
12 / C19 Front
0U 12 C19 / 12 C13 Switched & Monitored 46M4134 Attached 5931 0U
12 / C13 Back

IBM Power Systems PDU Information North America


Currently IBM Power Systems does not have an available PDU to support this outlet. A suitable IBM System
x PDU from the list above or a third party PDU will need to be used to connect this outlet.

P a g e | 172 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC309 3P+G – 60A@208V 3ph


Attached 14-foot (4.3 meter) line cord with IEC-309 60A, 3P4W Plug (Type 460P9W)
60A (27.7A / Phase Derated) 200V-240V Three Phase Delta
83.1A Total Derated Circuit Capacity

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 460R9W IP-67 HUBBELL, Hubbell receptacle P/N HBL460R9W
Matching connector listing 460C9W IP-67 HUBBELL, Hubbell connector P/N HBL460C9W

Female Sleeve Male Pin L3


120V 208V
L3 L3 L2 208V
120V 208V
G L2 L2 G L1
120V
L1 L1 G

EQUIP.
GR.

Used with:
IBM System x PDU Information North America

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
Enterprise Basic 39Y8923 Attached 6061 6 / C19 Front 1U
9 / C19 Front
Ultra Density Enterprise Basic 71763NU Attached 6051 1U
3 / C13 Back
1U 12 C13 Switched & Monitored 46M4005 Attached 5895 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4003 Attached 5897 1U
3 / C13 Back

IBM Power Systems PDU Information North America

PDU Line Cord Line Cord Number / Form


PDU Feature Part Feature Part Type of Factor
Code Number Code Number Outlet
6 / C19 Front
7196 Monitored 42R8744 Attached - 1U
3 / C13 Back

P a g e | 173 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x & Power Systems International PDUs


IBM System x PDU Information International
See the “IBM System x PDU Guide – International” for more information on IBM’s System x international PDUs.

Line Cord PDU + Number /


PDU Part Part Line Line Cord Type of Form
PDU Name Number Number Cord FC Phase Voltage (Derated) Line Cord Plug Outlet Factor
39Y8934 A11V 1ph 220-240V 32A IEC 309 P+N+G
39Y8935 Comes A11W 1ph 220-240V 63A IEC 309 P+N+G
Front End Basic 3 / C19 Front ½U
39Y8936 with PDU A11Y 1ph 230-240V 32A AUS/NZ 3112
39Y8937 A11X 1ph 220V 30A KSC 8305
40K9612 6014 1ph 220-240V 32A IEC 309 P+N+G
40K9613 6015 1ph 220-240V 63A IEC 309 P+N+G
Enterprise C13 40K9617 6017 1ph 230-240V 32A AUS/NZ 3112
39Y8941 12 / C13 Front 1U
Basic 40K9618 6018 1ph 220V 30A KSC 8305
40K9611 6016 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3T1 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
40K9612 6064 1ph 220-240V 32A IEC 309 P+N+G
40K9613 6065 1ph 220-240V 63A IEC 309 P+N+G
DPI Enterprise 40K9617 6067 1ph 230-240V 32A AUS/NZ 3112
39Y8948 6 / C19 Front 1U
Basic 40K9618 6068 1ph 220V 30A KSC 8305
40K9611 6066 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3T3 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
40K9612 6502 1ph 220-240V 32A IEC 309 P+N+G
40K9613 6503 1ph 220-240V 63A IEC 309 P+N+G
DPI Ultra Density 40K9617 6505 1ph 230-240V 32A AUS/NZ 3112 9 / C19 Front
71762NX 1U
Enterprise Basic 40K9618 6506 1ph 220V 30A KSC 8305 3 / C13 Back
40K9611 6504 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3TC 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
1 46M4122 Attached 5922 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
0U 24 C13 Basic 24 / C13 Front 0U
46M4131 Attached 5925 1ph 200-240V 32A IEC 309 P+N+G
1
0U 12 C19 / 12 C13 12 / C19 Front
46M4143 Attached 5927 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G 0U
Basic 12 / C13 Back
40K9612 6034 1ph 220-240V 32A IEC 309 P+N+G
40K9613 6035 1ph 220-240V 63A IEC 309 P+N+G
Enterprise + - C13 40K9617 6037 1ph 230-240V 32A AUS/NZ 3112
39M2816 12 / C13 Front 1U
Monitored 40K9618 6038 1ph 220V 30A KSC 8305
40K9611 6036 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3T2 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
40K9612 5910 1ph 220-240V 32A IEC 309 P+N+G
40K9613 5911 1ph 220-240V 63A IEC 309 P+N+G
1U 12 C13 Switched & 40K9617 5913 1ph 230-240V 32A AUS/NZ 3112
46M4004 12 / C13 Front 1U
Monitored 40K9618 5914 1ph 220V 30A KSC 8305
40K9611 5912 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3T5 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
40K9612 5903 1ph 220-240V 32A IEC 309 P+N+G
40K9613 5904 1ph 220-240V 63A IEC 309 P+N+G
1U 9 C19 / 3 C13 40K9617 5906 1ph 230-240V 32A AUS/NZ 3112 9 / C19 Front
46M4002 1U
Switched & Monitored 40K9618 5907 1ph 220V 30A KSC 8305 3 / C13 Back
40K9611 5905 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G
47C2495 A3T4 3ph Y 380-415V 16A (16A/ph) IEC 309 3P+N+G
1
0U 24 C13U
46M4119 Attached 5930 1ph 220-240V 32A IEC 309 P+N+G 24 / C13 Front 0U
Switched & Monitored
1
0U 12 C19 / 12 C13 12 / C19 Front
46M4137 Attached 5932 3ph Y 380-415V 32A (32A/ph) IEC 309 3P+N+G 0U
Switched & Monitored 12 / C13 Back
1 – Use caution when using 0U PDUs with IBM Flex System. Be aware that 0U PDUs can impede serviceability of components in the back of
the IBM Flex System Enterprise Chassis.

P a g e | 174 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Power Systems PDU Information International


PDU PDU Line Cord Line Line Line Cord Number / Form
Feature Part Feature Cord Part Cord Amperage Type of Factor
Code Number Code Number Phase Voltage (Derated) Line Cord Plug Outlet
6489 39M5413 3ph Y 380-415V 32A IEC 309 3P+N+G
6491 39M5415 1ph 220-240V 63A (48A) IEC 309 P+N+G
6653 39M5412 3ph Y 380-415V 16A IEC 309 3P+N+G
7109 6656 39M5414 1ph 220-240V 32A (24A) IEC 309 P+N+G
44V3897 12 / C13 Front 1U
Monitored 6657 39M5419 1ph 220-240V 32A AUS/NZ 3112
6658 39M5420 1ph 220-240V 30A (24A) KSC 8305
69Y1619 / PDL 56P532 /
6667 3ph Y 380-415V 32A
69Y1615 Clipsal 56PA532
6489 39M5413 3ph Y 380-415V 32A IEC 309 3P+N+G
6491 39M5415 1ph 220-240V 63A (48A) IEC 309 P+N+G
6653 39M5412 3ph Y 380-415V 16A IEC 309 3P+N+G
7188 6656 39M5414 1ph 220-240V 32A (24A) IEC 309 P+N+G
39J1183 12 / C13 Front 1U
Basic 6657 39M5419 1ph 220-240V 32A AUS/NZ 3112
6658 39M5420 1ph 220-240V 30A (24A) KSC 8305
69Y1619 / PDL 56P532 /
6667 3ph Y 380-415V 32A
69Y1615 Clipsal 56PA532
6489 39M5413 3ph Y 380-415V 32A IEC 309 3P+N+G
6491 39M5415 1ph 220-240V 63A (48A) IEC 309 P+N+G
6653 39M5412 3 380-415V 16A IEC 309 3P+N+G
7189
6656 39M5414 1ph 220-240V 32A (24A) IEC 309 P+N+G 6 / C19 Front
Monitored 42R8743 1U
6657 39M5419 1ph 220-240V 32A AUS/NZ 3112 3 / C13 Back
6658 39M5420 1ph 220-240V 30A (24A) KSC 8305
69Y1619 / PDL 56P532 /
6667 3ph Y 380-415V 32A
69Y1615 Clipsal 56PA532

P a g e | 175 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM System x & Power Systems International PDUs Input Line Cords
IEC 309 P+N+G – 32A@220-240V 1ph
IEC 309 P+N+G (4.3m) - 32A / 220-240V Single Phase

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 332R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL332R6W
Matching connector listing 332C6W IP-67 HUBBELL, Hubbell connector P/N HBL332C6W

Female Sleeve Male Pin L


220- 240V 220- 240V
N
L N N L
G
G G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8934 Comes with PDU A11V 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9612 6014 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9612 6064 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9612 6502 1U
3 / C13 Back
0U 24 C13 Basic 46M4131 Attached 5925 24 / C13 Front 0U
Enterprise + - C13 Monitored 39M2816 40K9612 6034 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9612 5910 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9612 5903 1U
3 / C13 Back
0U 24 C13U Switched & Monitored 46M4119 Attached 5930 24 / C13 Front 0U

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


PDU Feature Part Feature Cord Part Type of Factor
Code Number Code Number Outlet
7109 Monitored 44V3897 6656 39M5414 12 / C13 Front 1U
7188 Basic 39J1183 6656 39M5414 12 / C13 Front 1U
6 / C19 Front
7189 Monitored 42R8743 6656 39M5414 1U
3 / C13 Back

P a g e | 176 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

AUS/NZ 3112 32A – 32A@230V 1ph


P+N+G (PDL P/N 56P332) Australia/New Zealand connector

Female Sleeve Male Pin


L
230V 230V
N L L N N

G G G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8936 Comes with PDU A11Y 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9617 6017 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9617 6067 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9617 6505 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9617 6037 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9617 5913 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9617 5906 1U
3 / C13 Back

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6657 39M5419 12 / C13 Front 1U
7188 Basic 39J1183 6657 39M5419 12 / C13 Front 1U
6 / C19 Front
7189 Monitored 42R8743 6657 39M5419 1U
3 / C13 Back

P a g e | 177 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

KSC 8305 30A – 30A@220V 1ph


P+N+G (Shin Ju P/N SJ-P3302) Korea connector

Female End Male End


L

N L L N 220V 220V
N
G G
G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8937 Comes with PDU A11X 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9618 6018 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9618 6068 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9618 6506 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9618 6038 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9618 5914 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9618 5907 1U
3 / C13 Back

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6658 39M5420 12 / C13 Front 1U
7188 Basic 39J1183 6658 39M5420 12 / C13 Front 1U
7189 Monitored 6 / C19 Front
42R8743 6658 39M5420 1U
3 / C13 Back

P a g e | 178 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC 309 P+N+G – 63A@220-240V 1ph


IEC 309 P+N+G (4.3m) - 63A / 220-240V Single Phase

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 363R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL363R6W
Matching connector listing 363C6W IP-67 HUBBELL, Hubbell connector P/N HBL363C6W

Female Sleeve Male Pin L


220- 240V 220- 240V
N
L N N L
G
G G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

PDU + Number /
PDU Part Line Cord Line Type of Form
PDU Name Number Part Number Cord FC Outlet Factor
Front End Basic 39Y8935 Comes with PDU A11W 3 / C19 Front ½U
Enterprise C13 Basic 39Y8941 40K9613 6015 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9613 6065 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9613 6503 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9613 6035 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9613 5911 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9613 5904 1U
3 / C13 Back

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6491 39M5415 12 / C13 Front 1U
7188 Basic 39J1183 6491 39M5415 12 / C13 Front 1U
7189 Monitored 6 / C19 Front
42R8743 6491 39M5415 1U
3 / C13 Back

P a g e | 179 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC309 3P+N+G – 16A@380-415V 3ph


IEC-309 3P+N+G 3.0 meter 16A, 3P5W plug (Type 516P6W)
32A (32A / Phase) 380-415V Three Phase Wye
48A Total Circuit Capacity

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 516R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL516R6W
Matching connector listing 516C6W IP-67 HUBBELL, Hubbell connector P/N HBL516C6W

Female Sleeve Male Pin


L3
L2 L3 L3 L2 380- 415V 380- 415V 220- 240V
L2
L1 N N L1 220-240V
380-415V
N
G G
220- 240V
L1 SYS.
GR.
G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
Enterprise C13 Basic 39Y8941 47C2495 A3T1 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 47C2495 A3T3 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 47C2495 A3TC 1U
3 / C13 Back
Enterprise + - C13 Monitored 39M2816 47C2495 A3T2 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 47C2495 A3T5 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 47C2495 A3T4 1U
3 / C13 Back
0U 24 C13 Basic 46M4122 Attached 5922 24 / C13 Front 0U

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6653 39M5412 12 / C13 Front 1U
7188 Basic 39J1183 6653 39M5412 12 / C13 Front 1U
7189 Monitored 6 / C19 Front
42R8743 6653 39M5412 1U
3 / C13 Back

P a g e | 180 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

PDL 56P532 / Clipsal 56PA532 – 32A@415V 3ph


The IEC-309 3P+N+G may need to be replaced in AUS/NZ with Clipsal P/N 56PA532 or PDL P/N: 56P532 (5
Wire, Three Phase Wye) plug.

Female Sleeve Male Pin L3


415V 415V 240V
L2
L2 L2
415V 240V
L3 N L1 N N
240V
L1 L3
L1 SYS.
E E GR.
E

Earth
GR.

Used with:
IBM System x PDU Information International
Currently IBM System x does not have an available PDU to support this outlet. A suitable IBM Power
Systems PDU from the list below or a third party PDU will need to be used to connect this outlet.

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
69Y1619 /
7109 Monitored 44V3897 6667 12 / C13 Front 1U
69Y1615
69Y1619 /
7188 Basic 39J1183 6667 12 / C13 Front 1U
69Y1615
7189 Monitored 69Y1619 / 6 / C19 Front
42R8743 6667 1U
69Y1615 3 / C13 Back

P a g e | 181 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC 309 3P+N+G – 32A@380-415V 3ph


IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W)
32A (32A / Phase) 380-415V Three Phase Wye
96A Total Circuit Capacity

Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section
“IEC 309 Pin & Sleeve Plug Decode” on page 188 in this document for further details on IEC309.

Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N HBL532C6W

Female Sleeve Male Pin


L3

L2 L3 L3 L2 380- 415V 380- 415V 220- 240V


L2
N 380-415V 220-240V
L1 N L1
N
G 220- 240V
G
L1 SYS.
GR.
G

EQUIP.
GR.

Used with:
IBM System x PDU Information International

Line Cord PDU + Number /


PDU Part Part Line Type of Form
PDU Name Number Number Cord FC Outlet Factor
Enterprise C13 Basic 39Y8941 40K9611 6016 12 / C13 Front 1U
DPI Enterprise Basic 39Y8948 40K9611 6066 6 / C19 Front 1U
9 / C19 Front
DPI Ultra Density Enterprise Basic 71762NX 40K9611 6504 1U
3 / C13 Back
12 / C19 Front
0U 12 C19 / 12 C13 Basic 46M4143 Attached 5927 0U
12 / C13 Back
Enterprise + - C13 Monitored 39M2816 40K9611 6036 12 / C13 Front 1U
1U 12 C13 Switched & Monitored 46M4004 40K9611 5912 12 / C13 Front 1U
9 / C19 Front
1U 9 C19 / 3 C13 Switched & Monitored 46M4002 40K9611 5905 1U
3 / C13 Back
12 / C19 Front
0U 12 C19 / 12 C13 Switched & Monitored 46M4137 Attached 5932 0U
12 / C13 Back

IBM Power Systems PDU Information International

PDU Line Cord Line Number / Form


Part Feature Cord Part Type of Factor
PDU Feature Code Number Code Number Outlet
7109 Monitored 44V3897 6489 39M5413 12 / C13 Front 1U
7188 Basic 39J1183 6489 39M5413 12 / C13 Front 1U
7189 Monitored 6 / C19 Front
42R8743 6489 39M5413 1U
3 / C13 Back

P a g e | 182 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IBM Flex System Power & Cooling Part Numbers


IBM System x Flex System Power & Cooling Part Numbers
G8264R Rack & Rear Door Heat Exchanger (RDHx)
G8052R PDUs North America
Flex System Enterprise Chassis PDUs International

G8264R – IBM System x PureFlex Part Numbers


P/N: 39Y7917 FC: 6212 2.8m (9ft) 10A/230V C13 to CEE7-VII (Europe)
P/N: 39Y7918 FC: 6213 2.8m (9ft) 10A/250V C13 to DK2-5a (Denmark)
P/N: 39Y7919 FC: 6216 2.8m (9ft) 10A/250V C13 to SEV1011-S24507 (Switzerland)
P/N: 39Y7920 FC: 6218 2.8m (9ft) 10A/250V C13 to SI 32 (Israel)
P/N: 39Y7922 FC: 6214 2.8m (9ft) 10A/250V C13 to SABS 164 (South Africa)
P/N: 39Y7923 FC: 6215 2.8m (9ft) 13A/250V C13 to BS 1363/A (UK)
P/N: 39Y7924 FC: 6211 2.8m (9ft) 10A/250V C13 to AS/NZ 3112 (Australia/NZ)
P/N: 39Y7925 FC: 6219 2.8m (9ft) 10A/220-240V C13 to KETI (South Korea)
P/N: 39Y7927 FC: 6269 2.8m (9ft) 10A/250V C13 to IS6538 (India)
P/N: 39Y7928 FC: 6210 2.8m (9ft) 10A/220-240V C13 to GB 2099.1 (China)
P/N: 39Y7929 FC: 6223 2.8m (9ft) 10A/250V C13 to NBR 14136 (Brazil)
P/N: 39Y7930 FC: 6222 2.8m (9ft) 10A/250V C13 to IRAM 2073 (Argentina)
P/N: 39Y7932 FC: 6263 4.3m (14ft) 10A/100-250V C13 to C14 (World Wide)
P/N: 39Y7937 FC: 6201 1.5m (5ft) 10A/100-250V C13 to C14 (World Wide)
P/N: 39Y7938 FC: 6204 2.8m (9ft) 10A/100-250V C13 to C20 (World Wide)
P/N: 46M2592 FC: A1RF 2.8m (9ft) 10A/250V C13 to NEMA 6-15P (US)
P/N: 46M2593 FC: A1RE 2.8m (9ft) 10A/100V C13 to JIS C-8303 (Japan)
P/N: None FC: 6568 1.8m 10A/100-250V, 2xC13PM to IEC 320-C14 (World Wide)
P/N: None FC: 6311 2.8m (9ft) 10A/100-250V C13 to C14 (World Wide)

G8052R – IBM System x PureFlex Part Numbers


P/N: 39Y7917 FC: 6212 2.8m (9ft) 10A/230V C13 to CEE7-VII (Europe)
P/N: 39Y7918 FC: 6213 2.8m (9ft) 10A/250V C13 to DK2-5a (Denmark)
P/N: 39Y7919 FC: 6216 2.8m (9ft) 10A/250V C13 to SEV1011-S24507 (Switzerland)
P/N: 39Y7920 FC: 6218 2.8m (9ft) 10A/250V C13 to SI 32 (Israel)
P/N: 39Y7922 FC: 6214 2.8m (9ft) 10A/250V C13 to SABS 164 (South Africa)
P/N: 39Y7923 FC: 6215 2.8m (9ft) 13A/250V C13 to BS 1363/A (UK)
P/N: 39Y7924 FC: 6211 2.8m (9ft) 10A/250V C13 to AS/NZ 3112 (Australia/NZ)
P/N: 39Y7925 FC: 6219 2.8m (9ft) 10A/220-240V C13 to KETI (South Korea)
P/N: 39Y7927 FC: 6269 2.8m (9ft) 10A/250V C13 to IS6538 (India)
P/N: 39Y7928 FC: 6210 2.8m (9ft) 10A/220-240V C13 to GB 2099.1 (China)
P/N: 39Y7929 FC: 6223 2.8m (9ft) 10A/250V C13 to NBR 14136 (Brazil)
P/N: 39Y7930 FC: 6222 2.8m (9ft) 10A/250V C13 to IRAM 2073 (Argentina)
P/N: 39Y7932 FC: 6263 4.3m (14ft) 10A/100-250V C13 to C14 (World Wide)
P/N: 39Y7937 FC: 6201 1.5m (5ft) 10A/100-250V C13 to C14 (World Wide)
P/N: 39Y7938 FC: 6204 2.8m (9ft) 10A/100-250V C13 to C20 (World Wide)
P/N: 46M2592 FC: A1RF 2.8m (9ft) 10A/250V C13 to NEMA 6-15P (US)
P/N: 46M2593 FC: A1RE 2.8m (9ft) 10A/100V C13 to JIS C-8303 (Japan)
P/N: None FC: 6568 1.8m 10A/100-250V, 2xC13PM to IEC 320-C14 (World Wide)
P/N: None FC: 6311 2.8m (9ft) 10A/100-250V C13 to C14 (World Wide)

P a g e | 183 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Flex System Enterprise Chassis – IBM System x PureFlex Part Numbers


8721-A1x Flex System Enterprise Chassis
P/N: 43W9049 | FC: A0UD Additional 1x 2500W PSU (1x to 4x)
P/N: N/A | FC: A0UC Base 2500W PSUs (includes 2x PSUs)
P/N: 47C7633 | FC: A3JH Additional 1x 2100W PSU (1x to 4x)
P/N: N/A | FC: A3MP Base 2100W PSUs (includes 2x PSUs)
P/N: 43W9078 FC: A0UA 80mm Fan Module, Pair
P/N: 39Y7916 | FC: 6252 2.5m (8.2ft), 16A/100-240V, C19 to IEC 320-C20 (World Wide)
FC: 6292 2m (6.5ft), 16A/100-250V, C19 to IEC 320-C20 Rack Power Cable (World Wide)
P/N: 00D7195 | FC: 6566 2.5m (8.2ft), 15A/208V, C19 to NEMA 6-15P (US)
P/N: 00D7196 | FC: 6537 1.8m (6ft), 15A/208V, C19 to NEMA 6-15P (US)
P/N: 00D7197 | FC: A1NV 4.3m (14ft), 15A/250V, C19 to NEMA 6-15P (US)
P/N: 40K9772 | FC: 6275 4.3m (14ft), 16A/208V, C19 to NEMA L6-20P Line Cord
P/N: 00D7192 | FC: A2Y3 4.3m (14ft) 30A @ 208V 3 phase Delta Line Cord
NEMA L15-30P - (3P+Gnd) to 3x IEC 320 C19
P/N: 00D7193 | FC: A2Y4 4.3m (14ft) 32A@380-415V 3 phase Wye Line Cord
International IEC309 3P+N+G to 3X IEC 320 C19
P/N: 00D7194 | FC: A2Y5 4.3m (14ft) 32A@415V 3 phase Wye Line Cord
Australia & New Zealand PDL/Clipsal 32A (3P+N+Gnd) to 3X IEC 320 C19

Rack & Rear Door Heat eXchanger (RDHx) – IBM System x PureFlex Part Numbers
9363-4CX IBM PureFlex System 42U Rack
9363-4DX IBM PureFlex System 42U Expansion Rack
44X3132 IBM PureFlex System Rack Door Kit
1756-42X IBM Rear Door Heat eXchanger

IBM Power Systems Flex System Power & Cooling Part Numbers
v7000 Rack & Rear Door Heat eXchanger (RDHx)
G8264R PDUs North America
G8052R PDUs International
Flex System Enterprise Chassis

Storwize V7000 (External) – IBM Power Systems PureFlex Part Numbers


FC: 9730 Power cord 100-240V 10A C13 to C14 (includes 2x power cords)
FC: 9801 PSUs (includes 2x PSUs)

G8264R – IBM Power Systems PureFlex Part Numbers


1455-64C Base unit (Comes with 2x PSUs by default)
FC: 6458 4.3m (14ft) 100-240V C13 to C14 World Wide
FC: 6469 4.3m (14ft) 200-240V 15A C13 to NEMA 6-15P US #5
FC: 6470 1.8m (6ft) 100-127V 15A C13 to NEMA 5-15P #4
FC: 6471 2.7m (9ft) 125V 15A C13 to NBR 14136 Brazil
FC: 6472 2.7m (9ft) 250V 16A C13 to Schuko plug #18
FC: 6473 2.7m (9ft) 250V 10A C13 to CEE wall plug #19
FC: 6474 2.7m (9ft) 250V 13A C13 to BS 1364 A plug #23
FC: 6475 2.7m (9ft) 250V 16A C13 to SII 32-1971 Isreal#32
FC: 6476 2.7m (9ft) 250V 10A C13 to SEV24507 wall plug #24
FC: 6477 2.7m (9ft) 250A 16A C13 to SABS164 #22
FC: 6488 2.7m (9ft) 125V 15A or 250V 10A C13 to IRAM 2079 #2
FC: 6493 2.7m (9ft) 250V 10A C13 to GB 53 plug China #62
FC: 6494 2.7m (9ft) 250V 10A C13 to IS 6538 plug
FC: 6577 Various Lengths * 200-240V 10A C13 to C14 World Wide
FC: 6660 4.3m (14ft) 125V 15A C13 to NEMA 5-15P US #59
FC: 6665 3.0m (10ft) 100-240V 10A C13 to C20 World Wide

P a g e | 184 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

FC: 6671 2.7m (9ft) 100-240V 10A C13 to C14 World Wide
FC: 6672 1.5m (5) 100-240V 10A C13 to C14 World Wide
FC: 6680 2.7m (9ft) 250V 10A C13 to AS3112-1964 and NZS 198 wall plug #6

* - For this feature, IBM Manufacturing chooses the optimum cord length when assembling systems into a
rack - 1.5m (5 ft), 2.7m (9 ft), or 4.2m (13.8 ft)

G8052R – IBM Power Systems PureFlex Part Numbers


1445-48E Base unit (Comes with 2x PSU by default)
FC: 6458 4.3m (14ft) 100-240V C13 to C14 World Wide
FC: 6469 4.3m (14ft) 200-240V 15A C13 to NEMA 6-15P US #5
FC: 6470 1.8m (6ft) 100-127V 15A C13 to NEMA 5-15P #4
FC: 6471 2.7m (9ft) 125V 15A C13 to NBR 14136 Brazil
FC: 6472 2.7m (9ft) 250V 16A C13 to Schuko plug #18
FC: 6473 2.7m (9ft) 250V 10A C13 to CEE wall plug #19
FC: 6474 2.7m (9ft) 250V 13A C13 to BS 1364 A plug #23
FC: 6475 2.7m (9ft) 250V 16A C13 to SII 32-1971 Isreal#32
FC: 6476 2.7m (9ft) 250V 10A C13 to SEV24507 wall plug #24
FC: 6477 2.7m (9ft) 250A 16A C13 to SABS164 #22
FC: 6488 2.7m (9ft) 125V 15A or 250V 10A C13 to IRAM 2079 #2
FC: 6493 2.7m (9ft) 250V 10A C13 to GB 53 plug China #62
FC: 6494 2.7m (9ft) 250V 10A C13 to IS 6538 plug
FC: 6577 Various Lengths * 200-240V 10A C13 to C14 World Wide
FC: 6660 4.3m (14ft) 125V 15A C13 to NEMA 5-15P US #59
FC: 6665 3.0m (10ft) 100-240V 10A C13 to C20 World Wide
FC: 6671 2.7m (9ft) 100-240V 10A C13 to C14 World Wide
FC: 6672 1.5m (5) 100-240V 10A C13 to C14 World Wide
FC: 6680 2.7m (9ft) 250V 10A C13 to AS3112-1964 and NZS 198 wall plug #6

* - For this feature, IBM Manufacturing chooses the optimum cord length when assembling systems into a
rack - 1.5m (5 ft), 2.7m (9 ft), or 4.2m (13.8 ft)

Flex System Enterprise Chassis – IBM Power Systems PureFlex Part Numbers
7893-92X Flex System Enterprise Chassis
FC: 3590 Additional 1x 2500W PSU (1x to 4x)
FC: 9059 Base 2500W PSUs (includes 2x PSUs)
FC: 7805 Additional 2x 80mmFans
FC: 9038 Base 4x 80mm Fans
FC: 1452 4.3m (14ft) 200-240V 15A C19 to NEMA 6-15P US
FC: 3733 2.5m (8.2ft) 200-240V 15A C19 to NEMA 6-15P US
FC: 4558 2.5m (8.2ft) 200-240V 16A C19 to C20 World Wide
FC: 4560 4.3m (14ft) 200-240V 20A C19 to NEMA L6-20P US

Rack & Rear Door Heat eXchanger (RDHx) – IBM Power Systems PureFlex Part Numbers
7953-94X IBM PureFlex System 42U
FC: EC01 Rack Front Door (Black)
FC: EC02 Rack Rear Door
FC: EC03 Rack Side Cover
FC: EC04 Rack Suite Attachment Kit
FC: EC05 Rear Door Heat eXchanger Indicator
FC: EC06 Rack Front Door (Blue)
1164-95X IBM Rear Door Heat eXchanger

P a g e | 185 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Reference Material
IBM ToR Switches & IBM Storwize V7000 Power Numbers
Device Max # of PSUs Max Current Max Wattage Max BTU
G8264R Ethernet Switch 2* 1.74A 348W 1189 BTU/Hr
G8052R Ethernet Switch 2* 0.9A 180W 615 BTU/Hr
SAN24B-4 SAN Switch 1 0.41A 82W 280 BTU/Hr
Storwize V7000 Controller (2076-124) 2** 2.79A 558W 1906 BTU/Hr
Storwize V7000 Expansion (2076-224) 2** 1.08A 216W 738 BTU/Hr
* – Comes with 2x PSUs by default ** – Storwize FC: 9801 includes 2x PSUs

NOTE: Storwize V7000 is not orderable thru System x.

IBM Flex System Power Management Policies

IBM Flex Power Management Policies Overview


Below are the possible IBM Flex power management policies with simplified meanings.

AC Power Source Redundancy


Means N+N redundancy without nodes allowed to throttle due to a power fault

AC Power Source Redundancy with Compute Node Throttling Allowed


Means N+N redundancy with nodes allowed to throttle due to a power fault

Power Module Redundancy


Means N+1 redundancy without nodes allowed to throttle due to a power fault

Power Module Redundancy with Compute Nodes Throttling Allowed


Means N+1 redundancy with nodes allowed to throttle due to power fault

Basic Power Management


Means NO Redundancy

P a g e | 186 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

What is N+N and N+1 PSU Redundancy


N+N PSU redundancy is where N is the minimum number of PSUs need to keep the system operational, plus N
number of PSUs again for redundancy. Essentially, the number of PSUs are double of what is necessary to keep
the system operational. N+N is needed when a system needs to be power source redundant (See example “N+N
and N+1 Examples” diagram below).

N+1 PSU redundancy is where N is the minimum number of PSUs need to keep the system operational, plus one
PSU for redundancy. N+1 is used when a system needs only to tolerate a single PSU failure and stay operational
(See example “N+N and N+1 Examples” diagram below). Think of N+1 as having one PSU as a hot spare.

N+N and N+1 Examples


Notice in the N+1 diagrams below that there are two sources. Typically, N+1devices would be connected to one
power source since N+1devices do not derive any benefit from two power sources. It is shown here with two
power sources to demonstrate this lack of benefit for N+1devices.

N+N Examples N+1 Examples


No Failures No Failures

4x PSU Device (N=2) 4x PSU Device (N=3)

PSU
P
Device – 4x PSU
PSU PSU
P
Device – 4x PSU
PSU

PSU PSU PSU PSU

PDU PDU PDU PDU


Power Source A Power Source B Power Source A Power Source B

N Number of PSUs Fails No More Than One PSU Fails


Device still operational if no more than N PSU fails Device still operational if only one PSU fails

4x PSU Device (N=2) 4x PSU Device (N=3)

P P
PSU PSU PSU PSU

Device – 4x PSU Device – 4x PSU


PSU PSU PSU PSU

PDU PDU PDU PDU


Power Source A Power Source B Power Source A Power Source B

One Power Source Fails One Power Source Fails


Device still operational if one of the power sources fails Device NOT operational if one of the power sources fails

4x PSU Device (N=2) 4x PSU Device (N=3)

P
PSU PSU PSU PSU

Device – 4x PSU Device – 4x PSU


PSU PSU PSU PSU

PDU PDU PDU PDU


Power Source A Power Source B Power Source A Power Source B

One Power Source Fails


Device still operational if one of the power sources fails

2x PSU Device (N=1)

P
Device – 2x PSU
PSU PSU

PDU PDU
Power Source A Power Source B

P a g e | 187 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

IEC 320 Connectors


Name Connector AMP Rating Use
Laptop Power Supplies And Other Portable Power
C5 – Female
2.5A Supplies
C6 – Male
C7 – Female Laptop Power Supplies And Other Portable Power
2.5A
C8 – Male Supplies
C13 – Female
10A Desktop Computers, Monitors, Switches, And Servers
C14 – Male
C15 – Female Used In Hot Conditions Since It Is Rated To 1200 C
10A
C16 – Male (2480F), Unlike C13/C14 Which Is Rated To 700 C (1580 F)
C19 – Female Blade Chassis, Flex System, High-power Servers, UPSs,
16A
C20 – Male PDUs, And Other High Current Equipment
Note: IEC 320 has changed to IEC 60320

IEC 309 Pin & Sleeve Plug Decode


4 60 R 9 W Color Voltage Rating

Pin Configuration Amperage Device Type Polarization Environmental Rating Yellow 100V - 130V

Orange 125V/250V
3 - 2 Pole + G 20 30 32 P - Plug Clock W-WATERTIGHT
Blue 200V - 250V
4 - 3 Pole + G 60 63 100 C - Connector Position (SCREW CAP &
5 – 3 Pole + N + G R - Receptacle Of Female LOCKING RING) Gray 277V
B - Inlet Sleeve
Red 380V - 480V

Black 500V - 690V


Female Sleeve Male Pin
Example
o IEC309 3P+G Plug L3 L3 Pin Configuration Significance
o 60amp/250V three-phase
G L2 L2 G 3 Pins = 1ph
o Hubbell Connector listing
4 Pins = 3ph Δ
460C9W IP-67 L1 L1
5 Pins = 3ph Y
o P/N HBL460C9W

Female Ends Male Ends

Receptacle Connector Plug Inlet

P a g e | 188 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

Ingress Protection (IP) Decode


Code Letters First Number Second Number

Protection Against Ingress Protection Against Ingress of


Ingress Protection
of Solid Foreign Objects Water with Harmful Effects

IP 0 – No Protection 0 – No Protection
1 ≥ 50mm Diameter 1 – Vertically Dripping
2 ≥ 12.5mm Diameter 2 – Dripping At 15° Of Tilt
First Number: degree of protection 3 ≥ 2.5mm Diameter 3 – Spraying Up To 60° Of Tilt
for persons against access of
hazardous parts inside the enclosure 4 ≥ 1.0mm Diameter 4 – Splashing
and/or against foreign objects. 5 – Jetting
5 – Dust-Protected
Second Number: degree of 6 – Dust-Tight 6 – Power Jetting
protection of equipment inside
enclosures against damage from
7 – Temporary Immersion
ingress of water. 8 – Continuous Immersion
Ingress Protection (IP ) is defined in IEC 60529 Standard.

Example: IP67 = Ingress Protection / Dust-Tight / Temporary Immersion

60A Three Phase Delta Power Calculations


A IA
ELL = EAC = EBA = ECB = 208V
IL = 60A
IAC IBA
208V
PTotal = √3 x ELL x IL x pf
C IC
= √3 x 208 x 60 x 1 208V
= 21616W ICB
208V
PDerated = PTotal x 0.8
B IB
= 21616W x 0.8
= 17293W
Variables Defined
I = Phase Current
IL 60 IL = Line Current
I = IAC = IBA = ICB = = = 34.64A ELL = Line to Line Voltage
√3 √3
pf = Power Factor
IDerated = I x 0.8 = 34.64 x 0.8 = 27.7A P = Power In Watts

P a g e | 189 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

50A Three Phase Delta Power Calculations


IA
ELL = 208V
IL = 50A
IAC IBA
208V
PTotal = 3 x ELL x IL x PF
IC
= 3 x 208 x 50 x 1 208V
= 18013W ICB
208V
PDerated = PTotal x 0.8
IB
= 18013W x 0.8
= 14410W
Variables Defined
I = Phase Current
IL 50 IL = Line Current
IAC = IBA = ICB = = = 28.86A ELL = Line to Line Voltage
3 3 PF = Power Factor
P = Power In Watts
IDerated = I x 0.8 = 28.86 x 0.8 = 23.09A
30A Three Phase Delta Power Calculations
A IA
ELL = EAC = EBA = ECB = 208V
IL = 30A
IAC IBA
208V
PTotal = √3 x ELL x IL x PF
C IC
= √3 x 208 x 30 x 1 208V
= 10808W ICB
208V
PDerated = PTotal x 0.8
B IB
= 10808W x 0.8
= 8646W
Variables Defined
I 30 I = Phase Current
I = IAC = IBA = ICB = L = = 17.32A IL = Line Current
√3 √3 ELL = Line to Line Voltage
PF = Power Factor
IDerated = I x 0.8 = 17.32 x 0.8 = 13.85A P = Power In Watts

32A Three Phase Wye Power Calculations


IA = IB = IC = IL = I 32A IA

P =E Y xI Y x pf (W) A

E 220V
PTOTAL = 3 x P
EL 380V I
= 3 x EL/√3 x I x pf
= √3 x EL x IL x pf N
EL 380V
= √3 x 380V x 32A x 1
= 21061W B IB

EAN = EBN = ECN = E


EL 380V
EL 380 C
= = = 220V IC
√3 √3

P a g e | 190 © IBM Corporation 2013


IBM Flex System Enterprise Chassis Power Requirements Guide

16A Three Phase Wye Power Calculations


IA = IB = IC = IL = I A IA

P =E Y xI Y x pf (W) A

E 220V
PTOTAL = 3 x P
EL 380V I
= 3 x EL/√3 x I x pf
= √3 x EL x IL x pf N
EL 380V
= √3 x 380V x 16A x 1
= 10530W B IB

EAN = EBN = ECN = E


EL 380V
EL 380 C
= = = 220V IC
√3 √3

IBM Flex System & PureFlex System Documents


IBM Flex System & PureFlex System Product Manuals
http://publib.boulder.ibm.com/infocenter/flexsys/information/index.jsp?topic=%2Fcom.ibm.acc.common.nav.doc%2Fic-
homepage.html

IBM Flex System & PureFlex System at a Glance Guides


http://www.redbooks.ibm.com/Redbooks.nsf/portals/puresystems?Open&page=ataglance&count=999

IBM Flex System Interoperability Guide


http://www.redbooks.ibm.com/Redbooks.nsf/RedbookAbstracts/redpfsig.html?Open

Helpful Links
The latest copy of this document
http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/WP102111

Other resources related to power and cooling


http://www.ibm.com/support/techdocs/atsmastr.nsf/WebIndex/PRS4401

Hubbell - Twist Lock Plug/Outlet Catalog (Includes NEMA Outlets)


http://www.hubbellcatalog.com/wiring/catalogpages/section-b.pdf

Hubbell - Pin & Sleeve Plug/Outlet Catalog (Includes IEC309 Outlets)


http://www.hubbellcatalog.com/wiring/catalogpages/section-E.pdf

IBM System x® Configuration and Options Guide


http://www.ibm.com/systems/xbc/cog/

IBM BladeCenter and System x Reference Sheets


http://www.redbooks.ibm.com/Redbooks.nsf/pages/xref?Open

Official IBM Visio Stencils


http://www.visiocafe.com/ibm.htm

IBM, the IBM Logo, IBM Flex System, BladeCenter, DPI, IntelliStation, iDataPlex, and System x are registered trademarks or
trademarks of International Business Machines Corporation in the United States, other countries or both. For a list of
additional IBM trademarks, please see http://ibm.com/legal/copytrade.shtml.