Вы находитесь на странице: 1из 3

TM

PROTON

Perfect protection
for your motor
MPU-VI MPU-I
Motor Protection Unit - VI Motor Protection Unit - I

Fully programmable.
n Fully programmable.
n

LED display for Digital Ammeter & Voltmeter.


n LED display for Digital Ammeter.
n

All set points programmable from keypad.


n All set points programmable from keypad.
n

Auto scanner for 3 phase Current & Voltage.


n Auto scanner for 3 phase Current.
n

Hold facility for pausing display in run mode.


n Hold facility for pausing display in run mode.
n

Simple 3 keys for on site programming.


n Simple 3 keys for on site programming.
n

Password protection for controller.


n Password protection for controller.
n

MPU is available in two wide range from 1 to 30Amp with inbuilt


n MPU is available in two wide range from 1 to 30Amp with inbuilt
n

CTs and with external CTs from 5 to 999Amps. CTs and with external CTs from 5 to 999Amps.
Complete protection from unhealthy conditions, both Current &
n Complete protection from unhealthy conditions, both Current
n

Voltage sensing. sensing only.


3 CTs for 3 phase current measurement.
n 3 CTs for 3 phase current measurement.
n

Inverse time characteristics for over load.


n Inverse time characteristics for over load.
n

Technical specifications Technical specifications


Supply voltage : 3 Phase 440 VAC + 15% Supply voltage : 3 Phase 440 VAC + 15%
Output contact rating : 7Amp. at 250 V for relay 1 contact. Output contact rating : 7Amp. at 250 V.
7 Amp. at 250 V for relay 2 contact. Front Panel : 1. 3 Key for programming.
Front panel : 1. 3 Key for programming. 2. Relay ON indication with green LED.
2. Relay 1 ON indication with green LED. 3. Fault indication by red LED.
3. Alarm indication by red LED. Sensing : Inbuilt current sensing.
Sensing : 1. Inbuilt current sensing. Protections : 1. Overload protections set point user
2. Inbuilt voltage sensing. selectable.
Protections : 1. Overload protections set point user 2. Underload protection set point user
selectable. selectable.
3. Single phasing.
2. Underload protection set point user
4. Reverse Phasing.
selectable. 5. Unbalance protection.
3. Single phasing, Unbalance protection.
Operating temperature : 0 to 50 Deg.C.
4. Over/Under voltage protection. Range
Operating temp. range : 0 to 50 Deg. C.
Relative Humidity : 10 to 95%.
Relative humidity : 10 to 95%.
Mounting : Door Mounting.
Mounting : Door mounting.
Cutout : 96 x 96. Cutout : 96 x 96.

Wiring diagram Wiring diagram


104

C1 5
C1
2
MPU R
R 103
Motor Y Motor
Y 5
B
B 2
N 102
TIME

N NC C NO
N/V N/V 5
S1 S2 S1 S2 S1 S2
P.B. OFF

2 30C
C1 C1 20C
101 15C

T
MPU C
T 5 10C

Trip lamp ON P.B. NO P.B. OFF ON P.B. 5C


2 2C
NC 0
Trip lamp
.7.8.91 1.5 2 3 4 5 6 7 8 9 10
With inbuilt CTs. Upto 20HP motor in D-O-L configuration With external CTs. Upto 1000/5 Amp. X SET CURRENT
VMR-3P VFR
Voltage Monitoring Relay Voltage & Frequency Relay

Fully Programmable.
n Fully Programmable.
n

LED display for Digital Voltmeter & Fault Annunciation.


n LED display for Digital Voltmeter & Fault Annunciation.
n

All set points programmable from keypad.


n All set points programmable from keypad.
n

Auto Scanner for 3 phase Voltage.


n Auto Scanner for 3 phase Voltage and R Phase Frequency.
n

Hold facility for pausing display in run mode.


n Hold facility for pausing display in run mode.
n

Simple 3 keys for on site programming.


n Simple 3 keys for on site programming.
n

Trip delay for Under / Over Voltage & Unbalance is settable.


n Trip delay for Under / Over Voltage & Unbalance is settable.
n

Complete protection from unhealthy conditions for Voltage such


n Complete protection from unhealthy conditions for Voltage such
n

as UV, OV, SPP, Reverse Phase and UB. as UV, OV, SPP, Reverse Phase and UB, UF, OF.
Indication for Low Voltage, High Voltage, SPP & Relay ON.
n Indication for Low Voltage, High Voltage, SPP & Relay ON.
n

Message Display for SPP, Reverse Phasing & Unbalance fault.


n Message Display for SPP, Reverse Phasing, Unbalance, UF and
n

On Delay settable.
n OF fault.
On Delay settable.
n

Technical specifications
Supply voltage : 3 Phase 415 VAC + 15% Technical specifications
Output contact rating : 2 C/O, 5Amp. at 230 VAC. Supply voltage : 3 Phase 415 VAC + 15%
Front Panel : 1. 3 Key for programming. Output contact rating : 2 C/O, 5Amp. at 230 VAC.
2. Relay ON indication with green LED. Front Panel : 1. 3 Key for programming.
3. Fault Message on display. 2. Relay ON indication with green LED.
Sensing : Inbuilt voltage sensing. 3. Alarm indication by red LED.
Protections : 1. Over Voltage protection set point user Sensing : Inbuilt voltage sensing.
selectable. (upper limit is 500 V) Protections : 1. Over Voltage protection set point user
2. Under Voltage protection set point selectable. (upper limit is 500 V)
user selectable. (lower limit is 300 V) 2. Under Voltage protection set point
3. Single phasing. user selectable. (lower limit is 300 V)
4. Reverse phasing. 3. Single phasing.
5. Unbalance protection. 4. Reverse phasing.
Operating temp. range : 0 to 50 Deg. C. 5. Unbalance protection.
6. Under Frequency 40 to 49 Hz.
Relative humidity : 10 to 95%.
7. Over Frequency 51 to 61 Hz.
Mounting : Din rail mounting & Door Mounting.
Operating temp. range : 0 to 50 Deg. C.
55(W)* 65(L)* 125(D)mm
Relative humidity : 10 to 95%.
Cutout : 92 x 92 x 88 mm
Mounting : Din rail mounting
55(W)* 65(L)* 125(D)mm

Wiring diagram
Wiring diagram
C1 C1
R R

Y Y
B B

N N

N/V N/V

VMR-3P VMR-3P
RYBN C NO C1 RYBN C NO C1

T T
P.B. OFF ON P.B. P.B. OFF ON P.B.