Академический Документы
Профессиональный Документы
Культура Документы
Example configuration
Energy Automation
3∼ 220 kV
7UT613
1000/1A M1
5P20, 20VA
Rct=4Ω
3~ 110 kV 3~ 10 kV
5
IDiff =│I1 +I2│ Trip Block
IRest =│I1│+│I2│ 4
*)
3
2
1241A Add-on
SLOPE 1 Stabilization
1
1221 IDiff>
0
0 2 4 6 8 10 12 14 16 I Rest
1242A 1261A *) Slope for Add-on Stabilization: InO
BASE POINT 1 I-ADD ON STAB 7UT6 Æ Slope 1
1244A
BASE POINT 2
PTD EA13 NM 7UT6 Transf.Diff.Sett. 11/2007 No: 3
Power Transmission and Distribution
>
with this:
Imax = SN /(√3·Umin) = 250000 kVA/(√3·187 kV) = 771.9 A
Imin = SN /(√3·Umax) = 250000 kVA/(√3·236.5 kV) = 610.3 A
InO1p = SN /(√3·USet) = 250000 kVA/(√3·208.9 kV) = 691.1 A
and:
Id tc Imax = (Imax – InO1p) /InO1p = (771.9-691.1) /691.1 = 0.1169 [I/InO1p]
Id tc Imin = (InO1p- Imin ) /InO1p = (691.1-610.3) /691.1 = 0.1169 [I/InO1p]
With the above formula for USet the additional differential current due to the
tap changer is equal for both end positions !!
The lowest uT(1-2) = 12% will result to IDiff>> > 100%/12% I/InO
= 8.33 I/InO
selected: IDiff>> = 9.0 I/InO
0
0 1 2 I Rest InO PTD EA13 NM 7UT6 Transf.Diff.Sett. 11/2007 No: 9
Power Transmission and Distribution
The inrush current flows into the protected object from a single side and appears as
an internal fault. The transformer differential protection must therefore be stabilised
against this phenomenon.
I m (ν )
%
The large amount of I m(1)
second harmonic during 100
an inrush is used to block
the differential element. B
80 B
Figure 1
Harmonic components
50Hz part of the
magnetisation current
and dominant
Harmonics at Over flux
for a 50Hz Transformer
with
UN = 78kV and
SN = 60MVA
Idiff>