8 LIGHTNING ARRESTOR
120KV 10KA rated (Discharge Class-3) Station Class Metal Oxide (gapless)
Surge Arresters having pressure release arrangement at both ends and along
i 1 1
with Surge Counters as per specifications enclosed. Creepage Distance
25mm/kV
9 ISOLATOR
132kV, 630 Amps, 31.5kA for 1 sec, Triple pole Gang Operated, Horizontal
i Double Break, motor operated isolator with Manual Operated Earth Switch. 1 1
Creepage Distance 25mm/kV
132kV, 630 Amps, 31.5kA for 1 sec, Triple pole Gang Operated, Horizontal
ii Double Break, motor operated isolator without Earth Switch. Creepage 3 3
Distance 25mm/kV
iii 132kV BPI for Isolator 36 36
10 CONTROL AND RELAY PANEL
33/132kV Bus Bay Control & Relay panel complete with Multifunctional
Numerical Feeder Distance Relay, Numerical Backup Overcurrent Relay,
Auxiliary Electromechanical Relay, MFM/TVM , TNC Switch, Semaphore 1 1
Indicator, Mimic Diagram etc. Numerical Relay Shall be of IEC 61850
Communication Protocol.
11 CT and PT's
132KV Class,31.5KA/1second Short Time Rating, single phase, Outdoor Oil
immersed Live Tank Hermetically sealed Protection & metering Current
i 3 3
Transformer of ratio 120/1A. Total five cores of which Core-1: 0.2S/5VA, Core-
2: 0.2S/5VA .Creepage Distance 25mm/kV
132KV Class, Outdoor, single phase, Oil immersed Hermetically sealed
Protection &metering Voltage Transformer of Electromagnetic type of ratio
ii 3 3
(132KV/√3) / (110V/√3) - (110V/√3), Three cores of Class 0.2/10VA, 0.2/10VA
and 0.2/10VA . Creepage Distance 25mm/kV
12 CIRCUIT BREAKERS
3 Pole, Gang Operated, SF6 Circuit Breaker of 132KV, 50Hz, 630Amps,
31.5KA/1-second, duty 0-3sec-CO-3min-CO, The Control Voltage is 110V DC. 1 1
Creepage Distance shall be 25mm/kV
132KV Class, Outdoor, single phase, Voltage Transformer of Capacitive
type , Having " 3" Nos of cores with necessary Metering & Protection Core 1 1
arrangement ( 1 No of 0.2 Metering Core & 2 No of 3P Protection Core )
132kV , 1250A, 40kA, 0.5mH Wave Trap 1 1
Metering Bay
13 CT and PT's
132KV Class,31.5KA/1second Short Time Rating, single phase, Outdoor Oil
immersed Live Tank Hermetically sealed Tariff metering Current Transformer
i 6 6
of ratio 150-350/1-1A. Total Two cores of which Core-1: 0.2S/5VA, Core-2:
0.2S/5VA .Creepage Distance 25mm/kV
132KV Class, Outdoor, single phase, Oil immersed Hermetically sealed Tariff
metering Voltage Transformer of Electromagnetic type of ratio (132KV/√3) /
ii 6 6
(110V/√3) - (110V/√3), Two cores of Class 0.2/10VA and 0.2/10VA . Creepage
Distance 25mm/kV
132KV Class,31.5KA/1second Short Time Rating, single phase, Outdoor Oil
immersed Live Tank Hermetically sealed Current Transformer of ratio 150-
iii 3 3
300/1-1-1-1A. Total four cores of which Core-1: 0.2/20VA, Core-2: 5P20/20VA,
Core-3: PS, and Core-4 : PS . Creepage Distance 25mm/kV
Tariff metering Kioskwith 2Nos of ABT Meter (Main, Check, Standby) having
0.2S Accuracy Class with IM/EX Feature, TOD Feature etc complete with
iv 3 3
Necessary metering Software & its Hardwware Accessories for Proper
Functioning as per utility Standard
8 BATTERY AND BATTERY CHARGER ( Pooling Substation) (SETC)
220VDC, 50A , Thyristor based FCBC Battery Charger with inbuilt DCDB
i 1 Set.
having Necessary Outgoing Feeders
ii 220V DC, 200AH VRLA Maintenance Free Lead Acid Battery 1 Set
48V DC , 25A, Float Cum Boost Charger with inbuilt DCDB with Necessary
iii 1 Set.
Incoming & Outgoing Feeder
48V DC, 100AH VRLA Battery with Necessary supporting Racks
iv 1 Set
Interconnecting cables , Terminal Connector etc
v Power Line Carrier Communication Equipment as per MSETCL Standard 2 Set
MOUNTING SUPPORT STRUCTURES FOR 132KV SWITCHYARD
9
EQUIPMENT . ( All Structure & hardwares shall be HDG to 610 Gm/M2 )
i 132 KV Lightning Arrester 180 1800
ii 132 KV Isolators 760 9880
iii 132 KV Current Transformer 165 3465
iv 132 KV Voltage Transformers 200 3600
v 132kV Station Towers 1500 33300
vi 132kV Station Gantry 700 2800
vii 132kV Post Insulator 220 2640
HARDWARES FOR SWITCHYARD EQUIPMENTS (Bolts ,Nuts and
10
Washers)
i GI Foundation bolts, Nuts, Washers for Towers and Equipment structures 2875
9Mtr height Stepped Steel Tubular Pole as per IS 2713 Part2 complete with
i 15
250W HPSV Floodlight Fitting , Control Gear , JB etc
Outdoor Wall Mounted LDB ( Located in Outdoor LM Switchyard ) with 1 Nos
of 32A FP MCB as incomer, 3 nos of 25A DP MCB connected in series with
25A DP ELCB having 30mA Leakage Current segregated in R,Y&B Phase,
ii Having 5 Nos of 10A SP MCB in R Phase + 5 Nos of 10A SP MCB in Y Phase 1
+ 5 Nos of 10A SP MCB in B Phase. The complete LDB is fabricated with IP
55 Degree of Protection with Canopy , gasket, earth bus Cu Flat Pad locking
Facility with Timer on incomer controlling the Outgoing SP feeder .
iii3C X 2.5 Sqmm Flexible PVC Copper Cable 150
Cable Trays with minimum Thickness of Trays shall be 2 mm
19
(Galvanisation Thickness 460gm/m2)
i 600mm Wide ladder Type Trays, 75mm Height 100
ii 450mm Wide Ladder Type Trays, 75mm Height 250
iii 300 mm Wide Ladder Type Trays,75mm Height 250
iv 150 mm Wide Ladder Type Trays, 50mm Height 100
v 100mm Dia PVC Pipe 300
vi MS Angles, Plate & other Hardwares ( HDG) 2000
vii Cable Sealing Compound 1
20 ACDB, BMK & JBs
Structure Mounted Outdoor Weather proof, IP 55, CT Junction box having
thickness of Sheet steel 3mm & Gland Plate Thickness of 3 mm. 60 Nos of
i 10 Sqmm Disconnecting Type Terminal Blocks suitable for Ring Type Lugs 2
with Copper Flat earth Bus , Necessary Padlocking facility , gasket etc to be
considered as per Specification
Structure Mounted Outdoor Weather proof, IP 55, PT Junction box having
thickness of Sheet steel 2.5mm & Gland Plate Thickness of 3 mm. 45 Nos of
ii 10 Sqmm Stud Type Terminal Blocks suitable for Ring Type Lugs with Copper 2
Flat earth Bus , Fuses , Necessary Padlocking facility , gasket etc to be
considered as per Specification.
Outdoor Weather proof (IP 55) Bay Marshalling Kiosk having Stainless Steel
Thickness of 2mm with 3mm Thick Gland plate, Free Standing with canopy for
rain protection, complete with Following Accessories. i) 100 Nos of 6 Sqmm
Stud Type TB suitable for Stranded Copper Cable interlocking purpose. ii) One
iii 1
No of 63A TPN MCB as incomer with 3 Nos 32ATPN MCB as Outgoing + two
Nos of 16A DP MCB as Outgoing + 3 Nos of 16A TPN MCB as Outgoing iii)
Panel Illumination , 5A Power Socket with switch, Space heater , thermostat,
necessary Copper Earth Flat etc
* The above quanties are estimated in the absence of approved scheme and will vary if
respective utility proposes a different scheme than our consideration
Unit Remark/Disclaimer
Nos
Nos
Set
Nos
Set
Set
Nos
Nos
Nos
Nos
Nos
Nos
Set
Set
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Nos
Set
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Kg
Mtr
Mtr
Nos.
Nos
Mtr
Mtr
Nos.
Mtr
Nos
Nos
Nos
Nos
Lot
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Only 132kV switchyard Equipment Control
& Power Cabling are Considered.
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Mtr
Nos
Lot
Nos
Lot
Lot
Illumination & any Other Electrical wiring
Pertaining to Control Room are not
considered since we are using Existing EB
Substation Control Room Building
Nos
Set
Mtr
Mtr
Mtr
Mtr
Mtr
RM
Kg
Lot
Set
Set
Set
Set
Set
Set
Set
Set
Set
Only Rework & Extension of Fence work
Lot
for Proposed Bay is considered
Set
Set
Set
Nos
Nos
Nos
Set
Nos
Lot
Lot
Lot
Sqm
Nos
Nos
Nos.
Nos.
Nos.
Nos.
Pairs
Set
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Set
Set
This will vary as per actual route
kM
survey