Вы находитесь на странице: 1из 17

Electric Power Components and Systems, 43(5):491–507, 2015

Copyright C Taylor & Francis Group, LLC

ISSN: 1532-5008 print / 1532-5016 online


DOI: 10.1080/15325008.2014.992499

A Novel Fault Phase Selection Scheme Utilizing Fault


Phase Selection Factors
Jing Ma, Wei Ma, Xiangsheng Zhu, Xiang Gao, Yinan Li, Xi Wang, Zengping Wang,
and Qixun Yang
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power
University, Beijing, China

CONTENTS
Abstract—A new fault phase selection method for transmission lines
1. Introduction is proposed in this article. First, fault phase selection factors are
2. Fault Phase Selection Based on FPSFS constructed based on the relationship between the fault current of each
phase and the fault current difference of the other two phases at a relay
3. Performance Analysis point. By analyzing different characteristics of fault phase selection
4. Simulation Verification and Analysis factors in the case of different fault types, fault phase selection criteria
5. Conclusion are proposed. Simulation results show that fast and accurate selection
of the fault phase can be achieved within a period cycle after fault
Acknowledgments
occurs. Also, it is verified that the method bears a high sensitivity to
Funding all types of faults and is immune to the impact of fault resistance,
References fault inception angle, fault location, load current, and high-voltage
Appendixes DC lines, which makes it relatively reliable. Even when a developing
fault occurs, good selectivity is secure with this method. Furthermore,
the method provides sufficient sensitivity for phase selection on the
weak-infeed side and parallel lines.

1. INTRODUCTION
For high-voltage transmission lines, the current differential
relaying and distance relaying are applied as double primary
protection. The three-segment distance relaying is used for
backup protection in addition to an auto-reclosing device. Ac-
curate phase selection is needed for accurate operation of the
distance protection component and the auto-recloser. A false
phase selection result will lead to mal-operation of the two
devices and may even threaten the safety and stability of the
system [1–4].
Currently, fault phase selection mainly utilizes frequency-
domain techniques, time–frequency techniques, and time-
Keywords: fault phase selection, fault current, fault phase selection factors, domain techniques. Fault phase selection methods based on the
fault resistance, fault inception angle, fault location, developing fault, frequency domain [5] utilize the natural frequency characteris-
weak-infeed side
tic of the high-frequency component caused by the distributed
Received 2 October 2012; accepted 28 October 2014
Address correspondence to Dr. Jing Ma, State Key Laboratory of Alternate capacitance after the fault and identify the fault type by an-
Electrical Power System with Renewable Energy Sources, North China alyzing the spectral characteristics. Frequency-domain-based
Electric Power University, 102206 Beijing, China. E-mail:
hdmajing@163.com
phase selectors are immune to the fault location, fault time,
Color versions of one or more of the figures in the article can be found online fault resistance, power swing, and current transformer (CT)
at www.tandfonline.com/uemp. error. However, these methods may be affected by system

491
492 Electric Power Components and Systems, Vol. 43 (2015), No. 5

operation mode, noise disturbance, and fault inception time


[6]. Besides, when grounding faults occur at the end of long
lines with high fault resistance, the natural frequency is
very small in amplitude and the possibility of false selection
may increase. Fault phase selection methods based on the FIGURE 1. Model of a dual-source power system.
time–frequency characteristics [7, 8] utilize the fault type
information identified in the transient traveling wave by the
wavelet transformation method to select the fault phase. This the method provides sufficient sensitivity for phase selection
kind of method is accurate and reliable and is not affected by on the weak-infeed side and parallel lines.
the system operation mode, fault resistance, fault type, fault
location, CT error, or voltage transformer error [9, 10]. How-
ever, the traveling wave can be influenced by some elements,
such as fault electric arc, initial angle, and reflected wave, 2. FAULT PHASE SELECTION BASED ON FPSFS
which may increase the possibility of an unwanted phase [11, To simplify analysis, a dual-source power system, shown in
12]. Besides, in view of the computational burden and high- Figure 1, is used as the model in this article. The system volt-
frequency sampling, a specialized hardware processor chip is ages of side M and side N are Ė M and Ė N , and the equivalent
required for fast selection [13]. Fault phase selection based impedances are ZMS and ZNS respectively.
on the time domain mainly utilizes the combined method of Suppose a fault occurs at point F on line MN. The sequence
steady-state variable selection and mutation variable selec- network is shown in Figure 2, where Z MSi and Z NSi represent
tion. Steady-state variable selection mainly includes selection the equivalent sequence impedances of the system on sides M
methods based on current, voltage, and sequence components and N ,respectively. I˙Mi and I˙Ni represent the sequence currents
[14, 15]. Mutation variable selection methods mainly include on sides M and N, respectively. I˙Fi represents the sequence
phase current difference mutation selection, phase voltage current at fault location F. Rg is the transition resistance i =
difference mutation selection, and integrated current and 1, 2, 0.
voltage mutation selection [16]. Time-domain-based phase The sequence current distribution coefficient on side M is
selection methods have several merits, such as successful defined as
application to periodic signals [17], common sampling fre-
I˙Mi Z NSi + (1 − p) Z MNi
quency [11], and ease of implementation for digital protection Ci = = , (1)
relaying (DPR) [16]. However, these methods have difficulty
˙IFi Z MSi + Z MNi + Z NSi
accelerating the protection speed and escaping the impacts of where ZMNi is the sequence impedance of line MN, and p
some factors, such as fault type, fault resistance, developing represents the percentage of the distance from fault location F
fault, and weak feed-side fault [8]. The merits and limitations to bus M in the line length. For high-voltage system, it can be
of the frequency-/time–frequency-/time-domain-based phase approximately viewed that C 1 , C 2 , and C 0 are all real values
selectors can been seen in the Appendix. [15]. Meanwhile, the positive-sequence and negative-sequence
A new fault phase selection method based on fault phase impedances are approximately the same, thus C 1 = C 2 .
selection factors (FPSFs) is proposed in this article. First, ac- The fault phase currents at the relaying point of bus M are
cording to the proportion relation between the fault current ⎧
of each phase and the fault current difference of the other ⎨ I˙Ma = C1 I˙Fa1 + C2 I˙Fa2 + C0 I˙Fa0
two phases at the relaying point, the FPSFs are constructed. I˙ = α 2 C1 I˙Fa1 + αC2 I˙Fa2 + C0 I˙Fa0 , (2)
⎩ ˙Mb
Then, by analyzing different characteristics of FPSFs in the IMc = αC1 I˙Fa1 + α 2 C2 I˙Fa2 + C0 I˙Fa0
case of different fault types, the fault phase selection method
is proposed. Simulation results show that with the proposed
method, fast and accurate selection of the fault phase can be
achieved within a period cycle after the fault occurs. Also, it
is verified that the proposed method bears a high sensitivity to
all types of faults and is immune to the impacts of fault resis-
tance, fault inception angle, fault location, load current, and
high-voltage DC (HVDC) lines, thus being relatively reliable.
This method of fault detection is effective even when there is
an uncommon fault, such as a developing fault. Furthermore, FIGURE 2. Sequence network of internal fault.
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 493


where α = ej120 . I˙Ma , I˙Mb , and I˙Mc are the fault currents of current of phase A are
phases A, B, and C measured at bus M. I˙Fa1 , I˙Fa2 , and I˙Fa0 are 
I˙Fa1 = − I˙Fa2
the sequence components of the fault current of phase A at . (9)
fault location F. I˙Fa0 = 0
According to the proportion relation between the fault cur- Applying Eq. (9) to Eq. (2) results in
rent of each phase and the fault current difference of the other

two phases at the relaying point, the FPSFs are defined as ⎨ I˙Ma = C1 I˙Fa1 +C2 I˙Fa2 +C0 I˙Fa0 = (C1 −
 C
˙
2 ) IFa1 
      I˙Mb = α C1 I˙Fa1 +αC2 I˙Fa2 +C0 I˙Fa0 =  α C1 − αC2 I˙Fa1 .
2 2
 I˙Ma   I˙Mb   I˙Mc  ⎩˙
S1 =   , S2 =   , S3 =   , (3) IMc = αC1 I˙Fa1 +α 2 C2 I˙Fa2 +C0 I˙Fa0 = αC1 − α 2 C2 I˙Fa1
 I˙Mb − I˙Mc   I˙Mc − I˙Ma   I˙Ma − I˙Mb 
(10)
where (S 1 , S 2 , S 3 ) is a group of FPSFs. Thus, the FPSFs can be gained as follows:
  √
 I˙Ma  3 |C1 − C2 |
2.1. Characteristics of FPSFs for Different Fault Types S1 =  = , (11)
 I˙Mb − I˙Mc  3 |C1 +C2 |
2.1.1. Single-phase Grounding Fault
When a phase-A-to-ground (AG) fault occurs, the fault cur-
 √ 
rents of phases B and C at fault point F are both zero, i.e.,    
 I˙Mb  − (C1 − C2 ) − j 3 (C1 +C2 )
I˙Fb = I˙Fc =0. It can be gained from fault analysis that the se- S2 =  =  √  = 1,
 I˙Mc − I˙Ma   
quence components of the fault current of phase A meet the − (C1 − C2 ) + j 3 (C1 +C2 )
following relationship: (12)
I˙Fa1 = I˙Fa2 = I˙Fa0 , (4)  
   √ 
Applying Eq. (4) to Eq. (2) results in  I˙Mc  − (C1 − C2 ) + j 3 (C1 +C2 )
S3 =  =  √  = 1,
⎧  I˙Ma − I˙Mb   
⎨ I˙Ma = (C (C1 − C2 ) + j 3 (C1 +C2 )
 1 + C2 + C0 IFa1


˙IMb = α 2 C1 +αC2 + C0 I˙Fa1 . (5) (13)
⎩˙  
IMc = αC1 +α 2 C2 + C0 I˙Fa1 Considering that C 1 is approximately equal to C 2 , the nu-
merator of the expression on the right side of Eq. (11) is nearly
Thus, the FPSFs can be gained as follows: zero. Therefore, S 1 is nearly zero. Besides, whatever values C 1
  √
 I˙Ma  3 |C1 + C2 + C0 | and C 2 may take, the relationship between S 2 and S 3 is S 2 =
S1 =  = , (6) S 3 = 1.
 I˙Mb − I˙Mc  3 |C1 − C2 |

    2.1.3. Phase-to-phase Grounding Fault


 I˙Mb  1 C21 + C22 + C20 − C1 C2 − C1 C0 − C2 C0 
S2 =   =  2  , When a phase-BC-to-ground (BCG) fault occurs, the fault
 I˙Mc − I˙Ma  3 C + C 2 + C 1 C 2 
1 2
(7) current of phase A at fault point F is zero. The sequence
components of the fault current of phase A are
    ⎧
 I˙Mc  1 C21 + C22 + C20 − C1 C2 − C1 C0 − C2 C0  Z0
S3 =   =  2  . ⎪
⎨ I˙Fa2 = − I˙Fa1
 I˙Ma − I˙Mb  3 C + C2 + C1 C2  Z2 +Z0
1 2
Z2 , (14)
(8) ⎪
⎩ I˙Fa0 = − I˙Fa1
Considering that C1 is approximately equal to C2 , thus the Z2 +Z0
denominator of the expression on the right side of Eq. (6)
where Z2 and Z0 are the negative- and zero-sequence inte-
is nearly zero. Therefore, S 1 is very large. Regardless of the
grated impedance, respectively.
values C 1 , C 2 , and C 0 may take, the relationship between S 2
Applying Eq. (14) to Eq. (2) results in
and S 3 is S 2 = S 3 .


⎪ I˙Fa1

⎪ I˙Ma = [(Z2 +Z0 ) C1 − Z0 C2 − Z2 C0 ]
2.1.2. Phase-to-phase Fault ⎪
⎪ Z2 +Z0

I˙Fa1
When a phase-B-to-C (BC) fault occurs, the fault currents of I˙Mb = α 2 (Z2 +Z0 ) C1 − αZ0 C2 − Z2 C0 .

⎪ Z2 +Z0
phases B and C at fault point F are equal in amplitude and ⎪



I˙Fa1
opposite in direction, and the fault current of phase A is zero, ⎩ I˙Mc = α (Z2 +Z0 ) C1 − α 2 Z0 C2 − Z2 C0
Z2 +Z0
i.e., I˙Fb = − I˙Fc , I˙Fa = 0. The sequence components of the fault (15)
494 Electric Power Components and Systems, Vol. 43 (2015), No. 5

Thus, the FPSFs can be gained as follows: fault current of phase A, i.e., I˙Fa = I˙Fb = I˙Fc = I˙Fa1 . Applying
  √
 I˙Ma  3 |Z2 (C1 − C0 ) +Z0 (C1 − C2 )| this expression to Eq. (2) results in
S1 =  = , ⎧
 I˙Mb − I˙Mc  3 |Z2 C1 +Z0 (C1 +C2 )| ⎨ I˙Ma = C1 I˙Fa1
(16) I˙ = α 2 C1 I˙Fa1 . (23)
⎩ ˙Mb
IMc = αC1 IFa1 ˙
 √ √ 
   1 
 I˙Mb   2 A − 23 B + j 12 C+ 23 D  Thus, the FPSFs can be gained as follows:
S2 =   =  √ √  , (17) √
 I˙Mc − I˙Ma   3 
 2 A+ 23 B + j 32 C − 23 D  S1 = S2 = S3 =
3
. (24)
3
 √ √ 
   1 
 I˙Mc   2 A+ 23 B + j 12 C − 23 D 
S3 =   =   , 2.2. Fault Phase Selection Criteria
√ √
 I˙Ma − I˙Mb   3 
 2 A − 23 B + j 32 C+ 23 D  Concerning the different characteristics of FPSFs in different
(18) fault types, the fault phase selection criterion is established.
where A = R2 (C1 +2C0 ) + R0 (C1 − C2 ), B = X2 C1 +
Criterion A: As shown in Eq. (25), when one factor in the group
X0 (C1 +C2 ), C = X2 (C1 +2C0 ) +X0 (C1 − C2 ), and
of FPSFs (S 1 , S 2 , S 3 ) exceeds threshold ε1 , and the absolute
D = R2 C1 +R0 (C1 +C2 ); A, B, C, and D are all real values.
value of the difference between the other two factors in
Whatever values C 1 , C 2 , and C 0 may take, it can be seen
the group divided by the minor of the two remains below
from Eqs. (16)–(18) that S 1 , S 2 , and S 3 differ from each other.
threshold ε2 , a single-phase grounding fault can be decided.
Because of this, the amplitudes of the fault currents can be
The fault phase is the one corresponding to the maximum
used to identify phase-to-phase-to-ground faults.
factor in the group of FPSFs;
According to Eq. (15), 
 
   √   max  (S1 , S2 , S3 ) ≥ ε1  , (25)
 I˙Mb  C1 −α 2 + j 3 ZZ0 +C   S1 −S2   S2 −S3   S3 −S1 
  = 
2

0
 = 1, min  min(S1 ,S2 )  ,  min(S2 ,S3 )  ,  min(S3 ,S1 )  ≤ ε2
 I˙Mc   √ 
(19)
C1 −α − j 3 ZZ0 2
+C 0  where ε1 = 50 and ε2 = 0.1.
    Criterion B: As shown in Eq. (26), when the minimum factor
     C0 
 I˙Ma  (C1 − C0 ) + ZZ0 (C 1 − C2 )   C1
− 1  in the group of FPSFs (S 1 , S 2 , S 3 ) does not surpass threshold
 = < .
2

 √   C0
(20) ε3 , and the differences of the other two factors between one
 I˙Mb 
C1 −α 2 + j 3 ZZ0 +C   − α 2 
2
0 C1 are both smaller than threshold ε4 , a phase-to-phase fault can
Letting be decided, and the selected phase is the one corresponding
  to the minimum factor in the group;
 C0 
 C1 − 1 ⎧
Y =  , ⎨ min (S1 , S2 ,S3 ) ≤ ε3
 C0 
 C1 − α 2  |Sm1 − 1| ≤ ε4 , (26)

|Sm2 − 1| ≤ ε4
Y can then be written as a function of x:
 1−x where ε3 = 0.1 and ε4 = 0.2. S m1 and S m2 are the other two

x 2 +x+1
0≤x ≤1
Y = , (21) factors in the FPSFs group, which have higher values.
√ x−1
x 2 +x+1
x >1
Criterion C: As shown in Eq. (27), when the zero-sequence
where x = CC01 . current exceeds threshold ε0 , and the absolute value of the
Consider that C 1 , C 2 , and C 0 can all be approximately difference between any two factors in the group divided by
viewed as positive real values. Therefore, x can also be seen the minor of the two surpasses threshold ε5 , a phase-to-
as a positive real value. According to Eq. (21), when x = 0 or phase-to-ground fault can be decided. Meanwhile, accord-
x → +∞, Y has the maximum value 1; when 0 < x < +∞, Y ing to Eq. (22), the fault phases are the two with higher fault
is always below 1. Thus, for BCG faults, it is always true that currents;
           
 I˙Ma  <  I˙Mb  =  I˙Mc  .  S1 − S2   S2 − S3   S3 − S1 
(22) min    ,   ,   > ε5 ,
min(S1 ,S2 )   min(S2 ,S3 )   min(S3 ,S1 ) 
(27)
3.1.4. Three-phase (ABC) Fault where ε0 = 30 A and ε5 = 0.2.
When an ABC fault occurs, the fault currents of phases A, B, Criterion D: As shown in Eq. (28), when the absolute value of
and C at fault point F are all the same as the positive-sequence the difference between any two factors in the group divided
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 495

by the minor of the two does not surpass threshold ε6 , an remain the same. Therefore, the proposed method is
ABC fault can be decided; not affected by the fault location, and it is applicable
      to fault phase selection on the weak-infeed side (the
 S1 − S2   S2 − S3   S3 − S1 
max    ,   ,   < ε6 , weak-infeed side means the system impedance is big).
min(S1 ,S2 )   min(S2 ,S3 )   min(S3 ,S1 ) 
(28) 2) The proposed method is unaffected by the fault ini-
where ε6 = 0.1. tial phase angle. According to analysis of different
fault types, for a single-phase-to-ground fault, phase-
to-phase fault, and ABC fault, the FPSFs are only re-
3. PERFORMANCE ANALYSIS lated with the current distribution coefficients; for a two-
In the algorithm flow shown in Figure 3, phasor measurements phase-to-ground fault, the FPSFs have to do with the cur-
of the current mutation variable are used to select the fault rent distribution coefficients and the negative- and zero-
phases. When the system operates in the stable and steady state, sequence integrated impedances. Since the current dis-
the current mutation at the relaying point is nearly zero. Once a tribution coefficients and negative- and zero-sequence
fault occurs, the current mutation value increases significantly. integrated impedances are not related with the fault in-
The starting threshold value is set to be istart = 0.13Ie (the stant, the proposed method is not affected by the fault
operating value of the mutation phase selector is usually set initial phase angle.
to be istart = 0.1–0.15Ie in real relay protection devices [16]), 3) The proposed method is applicable for fault identifica-
where Ie represents the rated current. When the maximum tion of a developing fault. A developing fault refers
current mutation value of different phases exceeds istart , the to a single-phase-to-ground fault developing into a
fault phase selection scheme embedded in DPR starts (see two-phase-to-ground fault (including the former sin-
Appendix). gle phase) at the same fault location [16]. Comparative
The proposed method has the following characteristics. analysis shows that the phase selection criterion of a
single-phase-to-ground fault (Criterion A) is obviously
1) The proposed method is unaffected by the transition re-
different from the phase selection criterion of a two-
sistance and fault location, and it is applicable to fault
phase-to-ground fault (Criterion C). Thus, in the case
phase selection on the weak-infeed side. According to
of a developing fault, the proposed method has good
Eq. (1), the current distribution coefficients are not re-
selectivity.
lated with the transition resistance. Thus, however big
the transition resistance is, the proposed method is able 4) The proposed method is applicable to fault phase se-
to select the fault phase correctly. Additionally, although lection of double-circuit lines. For double-circuit trans-
the current distribution coefficients are affected by the mission lines on the same tower, if any type of fault
system impedance, line impedance, and fault location, occurs on one line, the phase electrical variables on the
no matter what values C 1 , C 2 , and C 0 take, the character- two lines at the fault location are independent from each
istics FPSFs demonstrate in different fault types always other, thus the relationship between sequence currents
is the same as in a single-circuit transmission line [18].
Therefore, the proposed method is applicable to fault
phase selection of a double-circuit line.
5) The proposed method is not affected by a thyristor
controlled series compensation (TCSC) and unified
power flow controller (UPFC), and is applicable to
the rectifier side in an AC/DC hybrid system. When
a thyristor controlled series compensation (TCSC) or
unified power flow controller (UPFC) is installed on the
transmission line, the positive- and negative-sequence
impedances are still the same, thus C 1 ≈ C 2 . Also, the
FPSFs are not related with the values of the current dis-
tribution coefficients. Therefore, the proposed method
is not affected by a TCSC and UPFC. For an AC/DC
FIGURE 3. Flowchart of the fault phase selection method. hybrid system, when a short-circuit fault occurs on the
496 Electric Power Components and Systems, Vol. 43 (2015), No. 5

rectifier-side AC line, usually there is no commutation


failure; thus the phase/sequence components “felt” at
two ends of the fault line are the same as those in an
ordinary AC line. In this case, false identification will
not happen. On the other hand, when a short-circuit
fault occurs on the inverter-side AC line, due to the
influence of commutation failure, the positive- and
negative-sequence impedances of the backside system
“felt” by the inverter-side relay protection during the
fault transient can be much different. In this case, false FIGURE 5. FPSFs when an AG fault occurs via a 300- fault
identification may result. resistance.

fault phase selection. The different types of faults via fault


4. SIMULATION VERIFICATION AND ANALYSIS resistance, including a single-phase grounding fault, a phase-
to-phase grounding fault, a phase-to-phase fault, and an ABC
In reference to the Beijing-Tianjin-Tangshan 500-kV ultra- fault, are simulated to estimate of the influence of fault resis-
high-voltage transmission line parameters, a 300-km transmis- tance on the performance of the proposed method.
sion line model with distributed parameters are constructed in When t = 0.40 sec, an AG fault occurs at the middle point
this study by PSCAD/EMTDC (Manitoba HVDC Research of the line via a 300- fault resistance. After the fault occurs,
Center, Winnipeg, Manitoba, Canada), shown in Figure 4. The the fault phase selector immediately starts to calculate the
system rated power is SN = 100 MVA, rated voltage is UN FPSFs. As shown in Figure 5, S 1 increases rapidly, while S 2
= 500 kV, and fundamental frequency is f = 50 Hz. System and S 3 remain approximately the same. According to Criterion
parameters are LM0 = 0.0926 H, RM0 = 0.6 , LM1 = 0.13743 A, an AG fault can be decided. The time taken to make such a
H, RM1 = 1.0515 , LN0 = 0.11927 H, RN0 = 20 , LN1 judgment is 4 ms.
= 0.14298 H, and RN1 = 26 . Parameters for the transmis- When t = 0.40 sec, a BC fault occurs at the middle point
sion line are r1 = 0.02083 /km, l1 = 0.8948 mH/km, C 1 of the line via a a 300- fault resistance. The variation curves
= 0.0129 μF/km, r0 = 0.1148 /km, l0 = 2.2886 mH/km, of the FPSFs are shown in Figure 6. It can be seen that S 1 is
and C 0 = 0.00523 μF/km. The compensation degree of the nearly zero, while S 2 and S 3 are next to 1. Therefore, according
shunt reactor is set to be 70% with LL = 7.4803 H and LN = to Criterion B, a BC fault can be decided. The time used for
2.4934 H. The full-wave Fourier algorithm is used to extract the selection process is 2.5 ms.
the phasor with a sampling frequency of 2000 Hz. When t = 0.40 sec, a BCG fault occurs at the middle point
The fault phase selector is installed at bus M. Five locations of the line via a 300- fault resistance. The FPSFs curves are
for fault simulation are chosen, i.e., d 1 , d 2 , d 3 , d 4 , and d 5 , shown in Figure 7. It can been seen that S 1 , S 2 , and S 3 are
with their distance from bus M being 0, 75, 150, 225, and different from each other and that the zero-sequence current is
300 km, respectively. Since the statistical maximum grounding relatively large. However, it can be noted that the fault currents
resistance for 500-kV lines is 300  [16], the fault resistance of phases B and C are higher than the fault current of phase A.
of high-resistance faults is set to be 300  in this study. Thus, according to Criterion C, a BCG fault can be decided.
Time for identification is 2.5 ms.
4.1. Simulation of Fault Resistance
In real system operation, fault usually occurs via a certain
transition resistance, which will weaken the fault character-
istics of the power grid and exert unfavorable influence on

FIGURE 4. Simulation model of high-voltage transmission FIGURE 6. FPSFs when a BC fault occurs via a 300- fault
line. resistance.
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 497

Fault FPSFs
resistance Selection
Fault type () S1 S2 S3 result
AG 0 3292.3 0.0348 0.0349 AG
300 1820.6 0.0145 0.0151 AG
BC 0 0.0000 1.0000 1.0000 BC
300 0.0001 1.0002 0.9998 BC
BCG 0 0.0013 0.8906 1.1095 BCG
300 0.0059 0.6932 1.4436 BCG
FIGURE 7. FPSFs when a BCG fault occurs via a 300- fault ABC 0 0.5724 0.5751 0.5774 ABC
resistance. 300 0.5740 0.5773 0.5723 ABC

When t = 0.40 sec, an ABC symmetrical fault occurs at TABLE 1. Results of fault phase identification at the middle point of
the line via different fault resistances
the middle point of the line. The FPSF curves are shown in
Figure 8. It can be seen that S 1 , S 2 , and S 3 are very close to
one another. In accordance with Criterion D, an ABC fault can effect of the fault inception angle on the proposed method is
be decided. simulated. Table 2 shows the values of the FPSFs at a cycle
For different types of faults, the values of the FPSFs at after the fault phase selector starts and the selection results. It
a cycle after the fault phase selector starts and the selection can be seen that the proposed method has satisfactory perfor-
results are shown in Table 1. It can be seen that for either mance for identifying the fault type and phase occurring under
metallic or high-resistance faults, accurate identification of different fault inception angles.
the fault type and selection of the fault phases is possible with
the proposed method. This method is highly sensitive to all 4.3. Simulation of Different Fault Locations
types of faults, especially for phase-to-phase grounding faults, The fault phase selector should be able to distinguish accu-
when the fault resistance changes from 0 to 300 . In this case, rately the fault phase when a fault occurs at any location in
the FPSFs do not vary much; rather it remains significantly the protection area [16]. To evaluate the proposed method, a
distinct from the cases of the other fault types. Thus, Criterion
C will never lose its applicability in deciding a phase-to-phase
grounding fault. Fault FPSFs
inception Selection
4.2. Simulation of Fault Inception Angle angle Fault type S1 S2 S3 result

The fault inception angle, especially for a voltage zero- 0◦ AG 1956.5 0.0185 0.0177 AG
BC 0.0002 0.9994 1.0006 BC
crossing situation, is one of the most frequent problems found BCG 0.0118 0.8291 1.1826 BCG
in fault phase selection schemes for which the performance is ABC 0.5719 0.5708 0.5723 ABC
based on traveling waves or on superimposed quantities due 45◦ AG 1873.6 0.0192 0.0184 AG
to the small traveling waves generated by the fault [7]. When BC 0.0002 0.9992 1.0008 BC
BCG 0.0134 0.7523 1.2995 BCG
faults occur at middle point of the line under a wide range
ABC 0.5745 0.5763 0.5756 ABC
of fault inception angles varying between 0◦ and 180◦ , the 90◦ AG 1905.2 0.0197 0.0188 AG
BC 0.0002 0.9992 1.0008 BC
BCG 0.0114 0.6510 1.5142 BCG
ABC 0.5747 0.5752 0.5763 ABC
135◦ AG 1808.2 0.0223 0.0208 AG
BC 0.0002 0.9992 1.0008 BC
BCG 0.0104 0.8167 1.2071 BCG
ABC 0.5751 0.5751 0.5785 ABC
180◦ AG 1892.6 0.0234 0.0219 AG
BC 0.0003 0.9987 1.0013 BC
BCG 0.0155 0.9438 1.0299 BCG
ABC 0.5790 0.5781 0.5741 ABC

FIGURE 8. FPSFs when an ABC fault occurs via a 300- TABLE 2. Influence of fault inception angle to fault phase identifi-
fault resistance. cation results
498 Electric Power Components and Systems, Vol. 43 (2015), No. 5

FPSFs
Fault Fault Selection
location type S1 S2 S3 result
d1 AG 3834.9 0.0040 0.0037 AG
BC 0.0000 1.0000 1.0000 BC
BCG 0.0025 0.6616 1.0416 BCG
ABC 0.5799 0.5657 0.5635 ABC
d2 AG 2725.3 0.0068 0.0065 AG
BC 0.0000 1.0000 1.0000 BC
BCG 0.0032 0.6583 1.5219 BCG
ABC 0.5780 0.5676 0.5685 ABC
d4 AG 1217.0 0.0861 0.0868 AG
BC 0.0002 1.0000 1.0000 BC
BCG 0.0396 0.7701 1.2555 BCG
ABC 0.5753 0.5773 0.5794 ABC
d5 AG 586.10 0.3193 0.3206 AG
BC 0.0003 1.0000 1.0000 BC
BCG 0.2264 1.0626 0.6907 BCG
ABC 0.5774 0.5782 0.5750 ABC

TABLE 3. Influence of fault positions to fault phase identification


results

series of faults of different types with a 300- fault resistance


FIGURE 9. Results of fault phase identification with devel-
are simulated at several locations along the transmission line. oping fault: (a) AG developing to CAG and (b) AG developing
Table 3 shows the values of the FPSFs at a cycle after the fault to ABG.
phase selector starts and the selection results. It can be seen
that for faults at different locations along the line, the fault
type and phase can be identified reliably and with a relatively
high sensitivity using the proposed selection method. 4.5. Simulation on the Weak-infeed Side
The weak-infeed system often has relatively low values of fault
4.4. Simulation of Developing Fault
current availability [19]. Under a weak-infeed condition, the
The post-fault power system is under abnormal operating con- fault phase selector may have not enough sensitivity for fault
ditions, where a developing fault can easily occur. If the phase detecting. By reducing the capacity of the generator on side M
selector cannot identify the fault phases quickly and accurately, by 100 times, the generator on side N can be equivalent to an
mal-operation of protection may result. Therefore, research on infinite bus while the generator on side M becomes the weak-
a phase selector applicable to a developing fault is a key is- infeed system, and the performance of the proposed method
sue for high-voltage line protection [16]. Taking an AG fault is studied. When a fault occurs at different locations along the
as an example, the applicability of the proposed method to a line via different fault resistances, the values of the FPSFs at a
developing fault is verified. cycle after the fault, the zero-sequence current, and the phase
When t = 0.40 sec, an AG fault occurs at the middle point selection results are shown in Table 5.
of the line. After a cycle, the fault develops into a phase-CA-to-
ground (CAG) fault and a phase-AB-to-ground (ABG) fault,
respectively. Selection results of these developing faults using Numbering Selection result
the proposed method are shown in Figure 9. The fault type
0 Proposed method
codes are shown in Table 4.
does not start
As can be seen from Figure 9, 4 ms after the fault occurs, 1 AG
an AG fault can be accurately decided according to Criterion 2 CAG
A. After a cycle, the single-phase fault develops into a CAG 3 ABG
fault and an ABG fault, respectively, and this developing fault
is correctly identified using Criterion C within 5 ms. TABLE 4. Fault type codes
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 499

FPSFs
Fault resistance Zero-sequence
Fault location Fault type () S1 S2 S3 current i0 /A Selection result
d1 AG 0 25110 0.3358 0.3358 — AG
300 3307.1 0.3979 0.3976 — AG
BC 0 0.0000 1.0001 0.9999 — BC
300 0.0000 1.0002 0.9999 — BC
BCG 0 0.2406 0.9002 1.6515 832.74 BCG
300 0.2378 0.9389 1.3584 814.84 BCG
ABC 0 0.5662 0.5721 0.5718 — ABC
300 0.5589 0.5694 0.5758 — ABC
d3 AG 0 3242.1 0.3499 0.3499 — AG
300 1810.4 0.3110 0.3106 — AG
BC 0 0.0000 1.0001 0.9999 — BC
300 0.0001 1.0003 0.9997 — BC
BCG 0 0.0267 0.9058 1.0975 395.23 BCG
300 0.1088 0.5206 1.7229 299.02 BCG
ABC 0 0.5781 0.5758 0.5698 — ABC
300 0.5764 0.5782 0.5771 — ABC
d5 AG 0 8046.8 0.3025 0.3026 — AG
300 834.89 0.2941 0.2951 — AG
BC 0 0.0000 1.0001 0.9999 — BC
300 0.0003 1.0011 0.9989 — BC
BCG 0 0.1571 0.8901 0.9224 186.58 BCG
300 0.2040 0.8698 0.8415 105.91 BCG
ABC 0 0.5681 0.5717 0.5698 — ABC
300 0.5701 0.5728 0.5766 — ABC

TABLE 5. Results of fault phase identification at the weak-infeed side

It can be seen from Table 5 that it is convenient for the pro- results are shown in Figure 11. It can be seen from Figures 10
posed method to identify different kinds of faults sensitively on and 11 that the proposed method is not affected by the installa-
the weak-infeed side within one cycle of time. Meanwhile, it tion of TCSC and UPFC. It is still able to identify the fault type
is unaffected by fault location and fault resistance. Therefore, and fault phase fast and accurately and with high sensitivity.
the adaptability of the proposed method in phase selection on
the weak-infeed system is proven. 4.7. Simulation on the Double-circuit Lines
A high-voltage parallel transmission line has the advantages of
4.6. Simulation on the Effects of TCSC and UPFC high transmission capacity as well as great economic benefits.
TCSC and UPFC make control on a large-scale interconnected It is able to improve the security and stability of the power
power grid faster, more frequent, continuous, and flexible, thus system and has been widely applied in recent years [22]. To
improving the power grid stability level. However, the applica- minimize the power outage of double-circuit lines on the same
tion of such techniques also affects the relay protection [20]. tower when fault occurs, it is required that the fault phase
For example, the distance protection may refuse to operate in selector identify the fault phases correctly [23]. To examine the
the case of an in-zone fault and mal-operate in the case of a suitability of the proposed method for parallel lines, an extra
backward fault [21]. To examine the influence of TCSC and transmission line is added between bus M and bus N on the
UPFC on the proposed method, simulation tests are carried out basis of Figure 4, so that a parallel line results (see Figure 12).
based on the system model shown in Figure 4. When different types of faults occur at F 1 (which is 150 km
Suppose that TCSC is installed at bus N and that it com- from bus M) via a 300- fault resistance, the phase selection
pensates according to 30% of the line reactance. When fault results at relay R1 are shown in Figure 13. It can be seen that
occurs at the midpoint of line MN, the phase selection results in the case of a double-circuit line, the proposed method is
are shown in Figure 10. When a UPFC is installed on line MN, highly reliable in identifying different types of faults and fault
if there is fault at the midpoint of the line, the phase selection phases, unaffected by the fault resistance.
500 Electric Power Components and Systems, Vol. 43 (2015), No. 5

FIGURE 11. FPSFs when UPFC is installed on line MN: (a)


FIGURE 10. FPSFs when TCSC is installed at bus N: (a) AG AG fault, (b) BC fault, (c) BCG fault, and (d) ABC symmetrical
fault, (b) BC fault, (c) BCG fault, and (d) ABC symmetrical fault.
fault.

4.8. Simulation on AC-DC Hybrid System


HVDC transmission is widely applied due to its obvious
advantage in a long-distance large-capacity power trans-
mission and a large power grid interconnection. Compared
with a traditional AC power system, when fault occurs,
the AC-DC hybrid system will exhibit many new electrical
characteristics, which will exert unfavorable influence on
FIGURE 12. Double high-voltage transmission line.
the operation behavior of AC system relay protection [24].
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 501

FIGURE 14. Single-line diagram of the CIGRÉ benchmark


HVDC system.

in Figure 15, with the corresponding phase selection results


shown in Figure 16. The instantaneous phase currents at the
relaying point of bus Q are shown in Figure 17, and the cor-
responding phase selection results are shown in Figure 18. It
can be seen from Figures 15–18 that when fault occurs on the
AC line at rectifier side, the proposed method is highly reliable
in identifying the fault type and fault phase, unaffected by the
fault resistance.
In the case of an inverter-side AC line fault, suppose that
a metallic AG fault and an AG fault via fault resistance (300
) occur at the midpoint of line MN; the instantaneous phase
currents at the relaying point of bus M are shown in Fig-
ure 19, with the corresponding phase selection results shown
in Figure 20. The instantaneous phase currents at the relaying
point of bus N are shown in Figure 21, and the corresponding
phase selection results are shown in Figure 22. It can be seen

FIGURE 13. FPSFs when different types of faults occur at


F 1 : (a) AG fault, (b) BC fault, (c) BCG fault, and (d) ABC
symmetrical fault.

Simulation experiments are carried out in the laboratory


based on the CIGRÉ benchmark HVDC system (Paris,
France) (see Figure 14) established in the real-time digital
simulator (RTDS). The system parameters can be found
in [25].
When a metallic AG fault and an AG fault via fault resis- FIGURE 15. Phase currents at the relaying point of bus P
tance (300 ) occur at the midpoint of line PQ, the instanta- when line PQ is in fault: (a) metallic AG fault and (b) AG fault
neous phase currents at the relaying point of bus P are shown via fault resistance.
502 Electric Power Components and Systems, Vol. 43 (2015), No. 5

FIGURE 16. FPSFs at the relaying point of bus P when line FIGURE 18. FPSFs at the relaying point of bus Q when line
PQ is in fault: (a) metallic AG fault and (b) AG fault via fault PQ is in fault: (a) metallic AG fault and (b) AG fault via fault
resistance. resistance.

from Figures 19–22 that when a metallic fault occurs on the fault resistance occurs, due to the influence of the DC system,
inverter-side AC line, both line ends are able to identify the the fault type is mistakenly identified as an ABC fault at bus
fault type and fault phase accurately. However, when fault via M, while bus N fails to identify the fault phase.

FIGURE 17. Phase currents at the relaying point of bus Q FIGURE 19. Phase currents at the relaying point of bus M
when line PQ is in fault: (a) metallic AG fault and (b) AG fault when line MN is in fault: (a) metallic AG fault and (b) AG
via fault resistance. fault via fault resistance.
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 503

FIGURE 20. FPSFs at the relaying point of bus M when line FIGURE 22. FPSFs at the relaying point of bus N when line
MN is in fault: (a) metallic AG fault and (b) AG fault via fault MN is in fault: (a) metallic AG fault and (b) AG fault via fault
resistance. resistance.

According to the above simulation analysis, in the AC- identification may happen with the proposed method for faults
DC hybrid system, the proposed method is able to identify on the inverter-side AC line.
faults on the rectifier-side AC line accurately. However, false

FIGURE 21. Phase currents at the relaying point of bus N FIGURE 23. Results of traditional fault phase identification
when line MN is in fault: (a) metallic AG fault and (b) AG method: (a) AG developing to CAG and (b) AG developing to
fault via fault resistance. ABG.
504 Electric Power Components and Systems, Vol. 43 (2015), No. 5

     
Fault location  I˙Mab /A  I˙Mbc /A  I˙Mca /A Further tests are conducted to perform the comparisons be-
tween FPSFs and other fault phase selection methods, such
d1 4202.9 3771.1 4146.0
d3 4129.5 3353.7 3728.1 as wavelet energy (WE) [26] and wavelet modulus maxima
d5 2956.7 3740.0 3083.4 (WMM) [27], which both are based on wavelet transform
(WT). The tests under different conditions show that the worst
case for fault phase selection is the low-transient condition.
TABLE 6. Simulation results with different fault locations when an
ABC fault occurs at line MN Some of the worst-case classification results are shown in Ta-
ble 7. It can be seen that due to the very low transient mag-
nitude, the accuracies of the fault phase selections based on
WE and WMM are 13% and 60%, respectively. However, the
4.9. Comparisons with Other Fault Phase Selection
proposed method is unaffected by fault inception time and
Methods
fault resistance, and the accuracy is 100%.
Digital high-voltage line protection mainly applies the phase
current difference mutation phase selector after the protection
5. CONCLUSION
starts in China [16]. When fault occurs in the system, the am-
plitude characteristic of the phase current difference variation A new fault phase selection scheme is proposed in this article.
is used to select the fault phases (see Appendix). First, according to the proportion relation between the fault
In the simulation model shown in Figure 4, suppose an AG current of each phase and the fault current difference of the
fault occurs at the midpoint of line MN at t = 0.40 sec and other two phases at the relaying point, the FPSFs are con-
develops to a CAG fault and an ABG fault separately after structed. Then, by analyzing different characteristics of FPSFs
one cycle. The variation
  curves
 of phase current difference in the case of different fault types, the fault phase selection
mutations IMab , IMbc , and  I˙Mca  are shown in Figure 23.
 ˙   ˙  method is proposed. Simulation results show the following
It can be seen that it takes 15 ms for the traditional phase advantages of the proposed method:
current difference mutation phase selection scheme to identify
the developing fault. However, according to Figure 9, it takes 1) highly sensitive to all types of faults and immune to the
only 5 ms for the proposed phase selection scheme to identify impact of fault resistance, fault inception angle, fault
the fault, with high sensitivity and accuracy. location, load current, and HVDC lines;
Suppose the generator on M side is the weak-infeed side of 2) fast and accurate selection of the fault phase within a
the system. When an ABC fault occurs at different locations cycle after the fault occurs;
on line MN, the phase selection results of the traditional phase
3) selective and accurate identification of developing
current difference mutation method are shown in Table 6. It
faults; and
can be seen that false selection may occur with the traditional
phase current difference mutation method. For example, when 4) adaptable to phase selection on the weak-infeed side and
fault occurs at d3, it is falsely identified as a phase-A-to-B parallel lines.
fault; and when fault occurs at d5, it is falsely identified as a
BC fault. On the other hand, according to Table 5, in phase
selection on the weak-infeed side, the proposed method is able ACKNOWLEDGMENTS
to identify different types of line faults correctly, unaffected
Many faculties and students contributed greatly to this re-
by the fault location and the fault resistance.
search. The authors would like to thank Dr. James S. Thorp
and Dr. Arun G. Phadke.

Failed fault phase Accuracy


Conditions Number Methods selection (%) FUNDING
tA = 0◦ , d = 30 WE 26 13 This work was supported by The National Basic Research
100 km, Rg is WMM 12 60 Program of China (973 Program) (2012CB215200), National
from 10–300  FPSFs 0 100 Natural Science Foundation of China (51277193), the Chi-
(in 10- steps)
nese University Scientific Fund Project (2014ZZD02), the Sci-
TABLE 7. Comparison with other fault phase selection methods entific Research Foundation for the Returned Overseas Chi-
tA = fault inception angle of phase A, d = distance from fault point to nese Scholars, State Education Ministry ([2011] No. 1139),
bus M, Rg = fault resistance. Hebei Natural Science Foundation (E2012502034), Electric
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 505

Power Youth Science and Technology Creativity Foundation relaying,” IET Generat. Transm. Distrib., Vol. 4, No. 10, pp.
of CSEE ([2012] No. 46), the New-Star of Science and Tech- 1197–1212, October 2010.
nology supported by Beijing Metropolis Beijing Nova pro- [13] Noori, M. R., and Shahrtash, S., “Combined fault detector and
faulted phase selector for transmission lines based on adaptive
gram (Z141101001814012), the Excellent talents in Beijing
cumulative sum method,” IEEE Trans Power Deliv., Vol. 28,
City (2013B009005000001), and the Fund of Fok Ying Tung No. 3, pp. 1779–1787, July 2013.
Education Foundation (141057). [14] Wang, X. G., Huang, S. F., and Liu, Q. K., “A phase-selector
based on voltage model fault component,” Automat. Electr.
REFERENCES Power Syst., Vol. 32, No. 9, pp. 42–46, May 2008.
[15] Xu, Z. Y., Yan, X. Q., Ran, L., and Zhang, X., “Fault phase
[1] Upendar, J., Gupta, C. P., and Singh, G. K., “Fault classification selection scheme of EHV/UHV transmission line protection
scheme based on the adaptive resonance theory neural network for high-resistance faults,” IET Generat. Transm. Distrib., Vol.
for protection of transmission lines,” Electr. Power Compon. 6, No. 11, pp. 1180–1187, 2012.
Syst., Vol. 38, No. 4, pp. 424–444, January 2010. [16] Ge, Y. Z., Novel Principles and Techniques of Protection and
[2] Jamehbozorg, A., and Shahrtash, S. M., “A decision-tree-based Fault Location, Xi’an, China: Xi’an Jiaotong University Press,
method for fault classification in single-circuit transmission 2007, pp. 37–61.
lines,” IEEE Trans Power Deliv., Vol. 25, No. 4, pp. 2190–2196, [17] Ji, T. Y., Wu, Q. H., Jiang, L., and Tang, W. H., “Disturbance
October 2010. detection, location and classification in phase space,” IET Gen-
[3] Yusuff, A. A., Jimoh, A. A., and Munda, J. L., “Determinant- erat. Transm. Distrib., Vol. 5, No. 2, pp. 257–265, Februayr
based feature extraction for fault detection and classification for 2011.
power transmission lines,” IET Generat. Transm. Distrib., Vol. [18] Li, B. T., Li, Y. L., Li, H. B., Su, B., and Li, Y. Y., “New method
5, No. 12, pp. 1259–1267, December 2011. for short-circuit fault analysis on double-circuit transmission
[4] Dasgupta, A., Nath, S., and Das, A., “Transmission line fault line based on interconnection of sequence networks,” Automat.
classification and location using wavelet entropy and neural Electr. Power Syst., Vol. 35, No. 9, pp. 53–58, May 2010.
network,” Electr. Power Compon. Syst., Vol. 40, No. 15, pp. [19] IEEE, “IEEE guide for protective relay applications to trans-
1676–1689, October 2012. mission lines,” IEEE Standard C37.113TM, 1999.
[5] Huang, S. F., and Wang, X. G., “Natural frequency characteristic [20] Dash, P. K., Pradhan, A. K., and Panda, G., “Apparent
analysis of UHV transmission line and its application in pro- impedance calculations for distance-protected transmission
tection,” Proc. CSEE, Vol. 29, No. 31, pp. 95–102, November lines employing series-connected FACTS devices,” Electr.
2009. Power Compon. Syst., Vol. 29, No. 7, pp. 577–595, July 2001.
[6] Li, S., Mei, J. T., Chen, S., Zheng, Z. Y., and Qian, Q. Q., “Fault [21] Khederzadeh, M., and Sidhu, T. S., “Impact of TCSC on the
detection and faulty phase determination of transmission lines protection of transmission lines,” IEEE Trans Power Deliv.,
based on time-frequency characteristics of transient travelling Vol. 21, No. 1, pp. 80–87, January 2006.
waves,” Power Syst. Technol., Vol. 36, No. 7, pp. 48–53, July [22] Bhalja, B., and Purohit, S., “Protection of double-circuit trans-
2012. mission line using superimposed current,” Electr. Power Com-
[7] Dong, X. Z., Kong, W., and Cui, T., “Fault classification and pon. Syst., Vol. 39, No. 6, pp. 590–604, April 2011.
faulted-phase selection based on the initial current traveling [23] Jamehbozorg, A., and Shahrtash, S. M., “A decision tree-based
wave,” IEEE Trans Power Deliv., Vol. 24, No. 2, pp. 552–559, method for fault classification in double-circuit transmission
April 2009. lines,” IEEE Trans. Power Deliv., Vol. 25, No. 4, pp. 2184–2189,
[8] He, Z. Y., Fu, L., Lin, S., and Bo, Z. Q., “Fault detection and October 2010.
classification in EHV transmission line based on wavelet sin- [24] He, L. N., Liu, C. C., Pitto, A., and Cirio, D., “Distance protec-
gular entropy,” IEEE Trans Power Deliv., Vol. 25, No. 4, pp. tion of AC grid with HVDC-connected offshore wind genera-
2156–2163, October 2010. tors,” IEEE Trans Power Deliv., Vol. 29, No. 2, pp. 493–501,
[9] De Souza Gomes, A., Costa, M. A., DeFaria, T. G. A., and Cam- April 2014.
inhas, W. M., “Detection and classification of faults in power [25] Faruque, M. O., Zhang, Y. Y., and Dinavahi, V., “De-
transmission lines using functional analysis and computational tailed modeling of CIGRÉ HVDC benchmark system using
intelligence,” IEEE Trans Power Deliv., Vol. 28, No. 3, pp. PSCAD/EMTDC and PSB/SIMULINKs,” IEEE Trans Power
1402–1413, July 2013. Deliv., Vol. 21, No. 1, pp. 378–387, January 2006.
[10] Livani, H., and Evrenosoğlu, C. Y., “A fault classification [26] Megahed, A. I., Moussa, A. M., and Bayoumy, A. E., “Usage
and localization method for three-terminal circuits using ma- of wavelet transform in the protection of series-compensated
chine learning,” IEEE Trans Power Deliv., Vol. 28, No. 4, pp. transmission lines,” IEEE Trans. Power Deliv., Vol. 21, No. 3,
2282–2290, October 2013. pp. 1213–1221, July 2006.
[11] Mahamedi, B., and Zhu, J. G., “Fault classification and [27] Su, Q. L., Dong, X. Z., Bo, Z. Q., and Jiang, F., “New approach
faulted phase selection based on the symmetrical compo- of fault detection and fault phase selection based on initial
nents of reactive power for single-circuit transmission lines,” current traveling waves,” Proc. IEEE Power Eng. Soc. Summer
IEEE Trans Power Deliv., Vol. 28, No. 4, pp. 2326–2332, Mtg., Vol. 1, pp. 393–397, 2002.
October 2013. [28] Valsan, S. P., and Swarup, K. S., “High-speed fault classification
[12] Upendar, J., Gupta, C. P., Singh, G. K., and Ramakrishna, in power lines: theory and FPGA-based implementation,” IEEE
G., “PSO and ANN-based fault classification for protective Trans. Ind. Electron/, Vol. 56, No. 5, pp. 1397–1800, May 2009.
506 Electric Power Components and Systems, Vol. 43 (2015), No. 5

APPENDIX A

Methods Merits Limitations


Frequency- Fast; immune to fault Affected by system
domain resistance, fault operation mode, noise
method type, disturbance, and fault
power swing, and inception time
CT error
Time–frequency- Accurate and reliable; Complexity;
domain method varying time data computational burden;
windows; high-frequency
immune to system sampling; traveling
operation mode, wave can be
fault resistance, influenced by some
FIGURE B1. Simplified schematic diagram of the digital pro-
fault type, fault elements, such as fault
tection relaying.
location, CT error, electric arc, initial
or voltage angle, and reflected
transformer error wave user so that manual operating and debugging of the protection
Time-domain Successful Fixed time data window; devices are possible, as well as acquiring the feedback infor-
method application to difficult to accelerate mation. The function of the digital output (DO) is to provide
periodic signals; protection speed and
the output channel to send the switch operation command cor-
common sampling escape impacts of
rectly and to realize electrical isolation between the internal
frequency; smaller some factors, such as
amount of fault type, fault and external of DPR.
computations; ease resistance, developing Through the CTs (CTA , CTB , CTC ), the three phase currents
of implementation fault, and weak feed I˙Ma , I˙Mb , and I˙Mb are transmitted to the analog signal process-
side fault ing component for the ALF, S/H, and A/D. The output digital
signals are then transmitted to the digital core component,
TABLE A1. Merits and limitations of the frequency- where FPSFs are calculated.
/time–frequency/time-domain-based phase selectors
APPENDIX C
APPENDIX B
According to Eq. (2), the phase current difference mutation
With the wide application of DPR in power systems, phase at the relaying point is
selection schemes based on the three-phase currents are easy ⎧
⎨ I˙Mab = I˙Ma − I˙Mb = (1 − α )C1 I˙Fa1 + (1 − α)C2 I˙Fa2
2
to implement [7, 28]. The simplified schematic diagram of
˙IMbc = I˙Mb − I˙Mc = (α 2 − α)C1 I˙Fa1 + (α − α 2 )C2 I˙Fa2 .
DPR is shown in Figure B1. Analog signal processing is the ⎩˙
first stage for DPR. The main components of signal processing IMca = I˙Mc − I˙Ma = (α − 1)C1 I˙Fa1 + (α 2 − 1)C2 I˙Fa2
(C1)
are as follows: (1) transducers and isolation, the transducers
Suppose that Im is the amplitude of the fault phase current
here are the CT, which also provide the necessary isolation; (2)
mutation and that the positive-sequence and negative-sequence
an analog low-pass filter (ALF), which can suppress the high-
current distribution coefficients are the same. The amplitude
frequency components in the input signals that are useless for
characteristics of the phase current difference mutation at the
protection; (3) sample and hold (S/H); and (4) an analog-to-
relaying point in different cases of short-circuit faults can be
digital converter (A/D).
analyzed, as shown in Table C1.
The function of the digital core component is to run the relay
protection program and command the operation of various pe-
Phase selection can be conducted in the following steps:
ripheral interface components so that protective relaying could
be realized. Therefore, the FPSF program is embedded into the Step 1: Calculate and compare the  amplitudes
   of three
 phase
digital core component. The function of the communication in- current difference mutations: IMab , IMbc , and  I˙Mca . If
 ˙   ˙ 
terface (CI) is to provide the communication channel with the the three values are basically the same, and are bigger than
computer communication network and the telecommunication a set value, then it is identified as an ABC fault.
network. The function of the man–machine interface (MMI) Step 2:
 Otherwise,
 select the minimum value  among
  the three.

is to establish the information contact between DPR and the If IMab is the minimum value, and IMab <<  I˙Mbc  and
 ˙   ˙ 
Ma et al.: A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors 507

     
Fault type  I˙Mab   I˙Mbc   I˙Mca  China Electric Power University, China. His interests mainly
include power system protection and power restoration.
AG Im 0 Im
Phase-B-to-ground Im Im 0
AG 0 Im Im Xiangsheng Zhu received the B.S. degree from Northeast Dili
Phase-C-to-ground 2Im Im Im University in 2012. He is currently pursuing the M.S. degree
BC Im 2Im Im in the School of Electrical and Electronic Engineering, North
Phase-C-to-A Im Im 2Im China Electric Power University, China. His interests mainly
ABC Im Im Im include wide area measurements, and small signal analysis and
control.
TABLE C1. Amplitude of phase current difference mutation in dif-
ferent kinds of short circuits Xiang Gao received the B.S. degree from Guangxi University
in 2012. He is currently pursuing the M.S. degree in the School
of Electrical and Electronic Engineering, North China Electric
    Power University, China. His interests mainly include wide
 I˙Mab  <<  I˙Mca  , then it is identified as a phase-C-to-
area measurements, and small signal analysis and control.
ground fault.
 
Step ˙ 
 3: If IMab is the minimum   value
 among  the three, but
Yinan Li received her B.S. from North China Electric Power
 I˙Mab  is not far less than  I˙Mbc  or  I˙Mca , then it is identified
University, China, in 2013. She is currently a master student
as a phase-to-phase fault. In this  case, select the maximum in the School of Electrical and Electronic Engineering, North
value among the three. If  I˙Mbc  is the maximum value, then
China Electric Power University, China. Her interests mainly
it is identified as a BC fault. As to whether it is a grounding
include power system protection and power restoration.
fault, this could be judged according to the zero-sequence
voltage.
Xi Wang received his M.S. from North China Electric Power
According to the above phase selection steps, if the calcu- University, China, in 2012 and his B.S. from Shanghai Uni-
lated amplitudes of three phase current difference mutations versity of Electric Power, China, in 2009. He is currently an
are all big and basically the same, then theoretically it is iden- engineer working in the State Grid Beijing Electric Power
tified as an ABC short-circuit fault; otherwise, continue to Bureau, Beijing, China. His interests mainly include power
determine the fault type. system analysis and wide-area protection.

BIOGRAPHIES Zengping Wang received the B.S. and M.S. degrees in elec-
Jing Ma received his B.S. and Ph.D. from North China Electric tric engineering from North China Electric Power University,
Power University, China, in 2003 and 2008, respectively. He China, in 1985 and 1988, respectively. He received the Ph.D.
is currently an associate professor in the School of Electrical degree from Harbin Institute of Technology, China, in 1997.
and Electronic Engineering, North China Electric Power Uni- He is a Professor and the Dean of the School of Electrical and
versity, China. He has been a visiting scholar in the Bradley Electronic Engineering at North China Electric Power Uni-
Department of Electrical and Computer Engineering, Virginia versity. His special fields of interest include relay protection,
Polytechnic Institute and State University, Blacksburg, VA, accident analysis and system security protection.
from 2008–2009. His major interests include power system
modeling, wide-area monitoring, small-signal stability, and Qixun Yang received the Ph.D. degrees from The University
control. of New South Wales, Australia. Currently, he is a Chinese aca-
demician of engineering and a Professor at North China Elec-
Wei Ma received his B.S. from North China Electric Power tric Power University, Beijing, China. His research interests
University, China, in 2012. He is currently a master student include power system protection and control, and substation
in the School of Electrical and Electronic Engineering, North automation.

Вам также может понравиться