WIND LOAD

AS PER ASCE 7-10


qz=0.613kz.kzt.kd.v^2
Topographic factor kzt= 1
Velocity pressure exposure coefficient kz= 1.09
Directionality factor kd= 0.85
building consider = CLOSED
exposure = c
internal pressure coefficient (Gcpi)= 0.55 (+,-)
v= 44.5m/s 160km/h
qz= 1124.672 1.124672 kn/m2
building height H= 15.8 m
horizental dimension parallel to wind direction L= 31 m
horizental dimension normal to wind direction B= 51 m
0Reduction Factor =
G= 0.85
wind ward wall
cp= 0.8
with -Gcpi
p=qGcp-qGcpi
p= 1.38 kn/m2
with +Gcpi
p=qGcp-qGcpi
p= 0.15 kn/m2
Side wall
cp= -0.7
L/B= 0.607843
with -Gcpi
p=qGcp-qGcpi
p= -0.05 kn/m2
with +Gcpi
p=qGcp-qGcpi
p= -1.29 kn/m2
Leeward wall
cp= -0.5
L/B= 0.607843
with -Gcpi
p=qGcp-qGcpi
P= 0.14
with +Gcpi
p=qGcp-qGcpi
P= -1.10

Roof
cp= -0.9 for 0-h
cp= -0.5 for h-2h
cp= -0.3 for> 2h
h/L 0.509677
with -Gcpi
p=qGcp-qGcpi
P1= -0.24 for 0-h
P1= 0.14 for h-2h
P1= 0.33 for> 2h
with +Gcpi
p=qGcp-qGcpi
P1= -1.48 for 0-h
P1= -1.10 for h-2h
P1= -0.91 for> 2h