Customer order number: 3007960273

Customer drive number: 16905


Comments:
___________________________________________________________________________________
___________________________

11/08/19 08:34:07.086 Log deleted


4/12/20 11:11:52.000 Event Log started
11/08/19 08:34:19 Fault - Power Supply
4/12/20 11:11:55.000 CPU Watchdog enabled
4/12/20 11:11:55.000 Alarm - Int AI1 Loss of Signal
4/12/20 11:11:55.000 User Alarm - Alarma Bajo Flujo Aire
4/12/20 11:11:55.000 User Fault - Aislamiento del Trafo
4/12/20 11:11:55.000 User Fault - VFD Inhibit Active
4/12/20 11:11:55.000 User Alarm - Air Flow Low Alarm
4/12/20 11:11:55.000 User Alarm - Perdida Ref1 Analog Vel
4/12/20 11:11:55.000 User Alarm - Analog Speed Ref1 Lost
4/12/20 11:11:56.000 User Alarm - VDF Apagado
4/12/20 11:11:56.000 User Alarm - VFD Off Switch Active
4/12/20 11:11:56.360 System started
4/12/20 11:11:56.360 Ver 6.8.1 09-25-19
4/12/20 11:11:56.360 FPGA version 1.5.0.25 2-16-18
4/12/20 11:11:56.360 Glue version 1.1.0.2 5-23-17
4/12/20 11:11:56.360 Network 1 module type: Anybus Ethernet
4/12/20 11:11:56.360 Network 2 module type: Siemens Modbus
4/12/20 11:17:50.000 Event Log started
4/12/20 11:15:06 Fault - Power Supply
4/12/20 11:17:53.000 CPU Watchdog enabled
4/12/20 11:17:53.000 Alarm - Int AI1 Loss of Signal
4/12/20 11:17:54.000 User Fault - Aislamiento del Trafo
4/12/20 11:17:54.000 User Fault - VFD Inhibit Active
4/12/20 11:17:54.000 User Alarm - Alarma Bajo Flujo Aire
4/12/20 11:17:54.000 User Alarm - Air Flow Low Alarm
4/12/20 11:17:54.000 User Alarm - Perdida Ref1 Analog Vel
4/12/20 11:17:54.000 User Alarm - Analog Speed Ref1 Lost
4/12/20 11:17:54.360 System started
4/12/20 11:17:54.360 Ver 6.8.1 09-25-19
4/12/20 11:17:54.360 FPGA version 1.5.0.25 2-16-18
4/12/20 11:17:54.360 Glue version 1.1.0.2 5-23-17
4/12/20 11:17:54.360 Network 1 module type: Anybus Ethernet
4/12/20 11:17:54.360 Network 2 module type: Siemens Modbus
4/12/20 11:17:54.532 User Alarm - VDF Apagado
4/12/20 11:17:54.532 User Alarm - VFD Off Switch Active
4/12/20 11:22:44.000 Event Log started
4/12/20 11:18:58 Fault - Power Supply
4/12/20 11:22:46.000 CPU Watchdog enabled
4/12/20 11:22:46.000 Alarm - Int AI1 Loss of Signal
4/12/20 11:22:47.000 User Alarm - Alarma Bajo Flujo Aire
4/12/20 11:22:47.000 User Alarm - Air Flow Low Alarm
4/12/20 11:22:47.000 User Alarm - Perdida Ref1 Analog Vel
4/12/20 11:22:47.000 User Alarm - Analog Speed Ref1 Lost
4/12/20 11:22:47.360 System started
4/12/20 11:22:47.360 Ver 6.8.1 09-25-19
4/12/20 11:22:47.360 FPGA version 1.5.0.25 2-16-18
4/12/20 11:22:47.360 Glue version 1.1.0.2 5-23-17
4/12/20 11:22:47.360 Network 1 module type: Anybus Ethernet
4/12/20 11:22:47.360 Network 2 module type: Siemens Modbus
4/12/20 11:22:47.772 User Alarm - VDF Apagado
4/12/20 11:22:47.772 User Alarm - VFD Off Switch Active
4/12/20 11:22:56.329 Alarm acknowledge
4/12/20 11:24:32.297 User Alarm Reset - VDF Apagado
4/12/20 11:24:32.297 User Alarm Reset - VFD Off Switch Active
4/12/20 11:24:39.277 User Alarm - VDF Apagado
4/12/20 11:24:39.277 User Alarm - VFD Off Switch Active
4/12/20 11:34:37.215 Tool - (2050)Control loop type - Was "OLVC" Now "OLTM"
4/12/20 11:34:37.317 Tool - Saved parameters
4/12/20 11:36:52.740 Tool - (2846)Analog variable - Was "Speed Demand" Now "Speed
Reference"
4/12/20 11:36:52.838 Tool - Saved parameters
4/12/20 11:37:02.102 Alarm acknowledge
4/12/20 11:38:40.721 Tool - (9146)Select system program - Was "8198029e.hex" Now
"NoWago.hex"
4/12/20 11:38:40.829 Tool - Saved parameters
4/12/20 11:38:41.298 User Alarm Reset - Perdida Ref1 Analog Vel
4/12/20 11:38:41.298 User Alarm Reset - Alarma Bajo Flujo Aire
4/12/20 11:38:41.298 User Alarm Reset - VDF Apagado
4/12/20 11:38:41.298 User Alarm Reset - Analog Speed Ref1 Lost
4/12/20 11:38:41.298 User Alarm Reset - VFD Off Switch Active
4/12/20 11:38:41.298 User Alarm Reset - Air Flow Low Alarm
4/12/20 11:39:49.312 Tool - (9146)Select system program - Was "NoWago.hex" Now
"8198029e.hex"
4/12/20 11:39:49.406 Tool - Saved parameters
4/12/20 11:39:50.729 User Fault - Perdida Ref1 Analog Vel
4/12/20 11:39:50.729 User Fault - Alarma Bajo Flujo Aire
4/12/20 11:39:50.729 User Fault - Analog Speed Ref1 Lost
4/12/20 11:39:50.729 User Fault - Air Flow Low Alarm
4/12/20 11:39:51.662 User Alarm - VDF Apagado
4/12/20 11:39:51.662 User Alarm - VFD Off Switch Active
4/12/20 11:43:43.000 Event Log started
4/12/20 11:40:22 Fault - Power Supply
4/12/20 11:43:45.000 CPU Watchdog enabled
4/12/20 11:43:45.000 Alarm - Int AI1 Loss of Signal
4/12/20 11:43:46.360 System started
4/12/20 11:43:46.360 Ver 6.8.1 09-25-19
4/12/20 11:43:46.360 FPGA version 1.5.0.25 2-16-18
4/12/20 11:43:46.360 Glue version 1.1.0.2 5-23-17
4/12/20 11:43:46.360 Network 1 module type: Anybus Ethernet
4/12/20 11:43:46.360 Network 2 module type: Siemens Modbus
4/12/20 11:43:46.472 User Alarm - Perdida Ref1 Analog Vel
4/12/20 11:43:46.472 User Alarm - Analog Speed Ref1 Lost
4/12/20 11:43:46.892 User Alarm - VDF Apagado
4/12/20 11:43:46.892 User Alarm - VFD Off Switch Active
4/12/20 11:44:34.309 User Alarm Reset - VDF Apagado
4/12/20 11:44:34.309 User Alarm Reset - VFD Off Switch Active
4/12/20 11:44:37.029 Alarm acknowledge
4/12/20 11:44:51.900 User Alarm - VDF Apagado
4/12/20 11:44:51.900 User Alarm - VFD Off Switch Active
4/12/20 11:44:53.060 User Alarm Reset - VDF Apagado
4/12/20 11:44:53.060 User Alarm Reset - VFD Off Switch Active
4/12/20 11:51:57.565 Tool - (4105)Source - Was "Int AI1" Now "Off"
4/12/20 11:51:57.566 Alarm Reset - Int AI1 Loss of Signal
4/12/20 11:51:57.669 Tool - Saved parameters
4/12/20 11:51:58.073 User Alarm Reset - Perdida Ref1 Analog Vel
4/12/20 11:51:58.073 User Alarm Reset - Analog Speed Ref1 Lost
4/12/20 11:54:00.976 User Alarm - VDF Apagado
4/12/20 11:54:00.976 User Alarm - VFD Off Switch Active
4/12/20 11:54:04.459 Alarm acknowledge
4/12/20 11:54:07.696 User Alarm Reset - VDF Apagado
4/12/20 11:54:07.696 User Alarm Reset - VFD Off Switch Active
4/12/20 11:59:19.000 Event Log started
4/12/20 11:56:38 Fault - Power Supply
4/12/20 11:59:21.000 CPU Watchdog enabled
4/12/20 11:59:22.360 System started
4/12/20 11:59:22.360 Ver 6.8.1 09-25-19
4/12/20 11:59:22.360 FPGA version 1.5.0.25 2-16-18
4/12/20 11:59:22.360 Glue version 1.1.0.2 5-23-17
4/12/20 11:59:22.360 Network 1 module type: Anybus Ethernet
4/12/20 11:59:22.360 Network 2 module type: Siemens Modbus
4/12/20 11:59:37.359 User Alarm - VDF Apagado
4/12/20 11:59:37.359 User Alarm - VFD Off Switch Active
4/12/20 11:59:43.025 User Alarm Reset - VDF Apagado
4/12/20 11:59:43.025 User Alarm Reset - VFD Off Switch Active
4/12/20 12:01:20.000 Event Log started
4/12/20 12:00:00 Fault - Power Supply
4/12/20 12:01:22.000 CPU Watchdog enabled
4/12/20 12:01:23.360 System started
4/12/20 12:01:23.360 Ver 6.8.1 09-25-19
4/12/20 12:01:23.360 FPGA version 1.5.0.25 2-16-18
4/12/20 12:01:23.360 Glue version 1.1.0.2 5-23-17
4/12/20 12:01:23.360 Network 1 module type: Anybus Ethernet
4/12/20 12:01:23.360 Network 2 module type: Siemens Modbus
4/12/20 12:05:55.000 Event Log started
4/12/20 12:03:06 Fault - Power Supply
4/12/20 12:05:58.000 CPU Watchdog enabled
4/12/20 12:05:59.360 System started
4/12/20 12:05:59.360 Ver 6.8.1 09-25-19
4/12/20 12:05:59.360 FPGA version 1.5.0.25 2-16-18
4/12/20 12:05:59.360 Glue version 1.1.0.2 5-23-17
4/12/20 12:05:59.360 Network 1 module type: Anybus Ethernet
4/12/20 12:05:59.360 Network 2 module type: Siemens Modbus
4/12/20 12:08:02.677 Tool - (9146)Select system program - Was "8198029e.hex" Now
"NoWago.hex"
4/12/20 12:08:02.781 Tool - Saved parameters
4/12/20 12:08:58.000 Event Log started
4/12/20 12:08:40 Fault - Power Supply
4/12/20 12:09:00.000 CPU Watchdog enabled
4/12/20 12:09:01.360 System started
4/12/20 12:09:01.360 Ver 6.8.1 09-25-19
4/12/20 12:09:01.360 FPGA version 1.5.0.25 2-16-18
4/12/20 12:09:01.360 Glue version 1.1.0.2 5-23-17
4/12/20 12:09:01.360 Network 1 module type: Anybus Ethernet
4/12/20 12:09:01.360 Network 2 module type: Siemens Modbus
4/12/20 12:12:02.135 Tool - (9985)Enable Local HMI - Was "Disabled" Now
"ReadWrite"
4/12/20 12:12:02.237 Tool - Saved parameters
4/12/20 12:12:53.775 Tool - (9114)MenuTimer3 - Was 6048.0 Now 77760.0
4/12/20 12:12:53.870 Tool - Saved parameters
4/12/20 12:13:13.675 Tool - (9185)Multiple config files - Was "OFF" Now "ON"
4/12/20 12:13:13.773 Tool - Saved parameters
4/12/20 12:13:56.821 Tool - (9185)Multiple config files - Was "ON" Now "OFF"
4/12/20 12:13:56.919 Tool - Saved parameters
4/12/20 12:16:57.823 Tool - (4833)Comp 3 manual value - Was 200.000 Now 11.667
4/12/20 12:16:57.922 Tool - Saved parameters
4/12/20 12:17:47.240 Tool - (4841)Comp 4 A in variable - Was Manual value-0000 Now
Mtr Spd-0000
4/12/20 12:17:47.349 Tool - Saved parameters
4/12/20 12:18:05.217 Tool - (4842)Comp 4 B in variable - Was Input Freq-0000 Now
Manual value-0000
4/12/20 12:18:05.314 Tool - Saved parameters
4/12/20 12:18:23.307 Tool - (4843)Comp 4 manual value - Was 200.000 Now 67.700
4/12/20 12:18:23.407 Tool - Saved parameters
4/12/20 12:18:59.889 Tool - (4853)Comp 5 manual value - Was 200.000 Now 0.000
4/12/20 12:18:59.987 Tool - Saved parameters
4/12/20 12:19:33.671 Tool - (4863)Comp 6 manual value - Was 200.000 Now 0.000
4/12/20 12:19:33.771 Tool - Saved parameters
4/12/20 12:20:43.620 Tool - (4863)Comp 6 manual value - Was 0.000 Now 99.990
4/12/20 12:20:43.717 Tool - Saved parameters
4/12/20 12:21:04.666 Tool - (4863)Comp 6 manual value - Was 99.990 Now 0.000
4/12/20 12:21:04.776 Tool - Saved parameters
4/12/20 12:21:44.188 Tool - (4893)Comp 9 manual value - Was 0.000 Now 200.000
4/12/20 12:21:44.286 Tool - Saved parameters
4/12/20 12:22:09.774 Tool - (4913)Comp 11 manual value - Was 200.000 Now 0.000
4/12/20 12:22:09.871 Tool - Saved parameters
4/12/20 12:22:47.569 Tool - (4923)Comp 12 manual value - Was 200.000 Now 0.000
4/12/20 12:22:47.678 Tool - Saved parameters
4/12/20 12:48:22.983 Tool - Saved parameters
4/12/20 12:50:37.561 Tool - (9985)Enable Local HMI - Was "ReadWrite" Now
"Disabled"
4/12/20 12:50:37.661 Tool - Saved parameters
4/12/20 12:57:14.554 Tool - (9115)MenuTimer4 - Was 1800.0 Now 600.0
4/12/20 12:57:14.666 Tool - Saved parameters
4/12/20 13:02:57.764 Tool - (4935)Compare 13 type - Was "Off" Now "Mag"
4/12/20 13:02:57.868 Tool - Saved parameters
4/12/20 13:03:14.709 Tool - (4945)Compare 14 type - Was "Off" Now "Mag"
4/12/20 13:03:14.809 Tool - Saved parameters
4/12/20 13:03:36.335 Tool - (4952)Comp 15 B in variable - Was Input Freq-0000 Now
Manual value-0000
4/12/20 13:03:36.435 Tool - Saved parameters
4/12/20 13:04:00.645 Tool - (4955)Compare 15 type - Was "Mag" Now "Off"
4/12/20 13:04:00.756 Tool - Saved parameters
4/12/20 13:05:23.082 Tool - (4419)Comp 18 B in variable - Was Input Freq-2015 Now
Man Id-2015
4/12/20 13:05:23.181 Tool - Saved parameters
4/12/20 13:05:43.915 Tool - (4422)Compare 18 type - Was "Mag" Now "Off"
4/12/20 13:05:44.015 Tool - Saved parameters
4/12/20 13:06:00.638 Tool - (4424)Comp 19 A in variable - Was Man Id-2260 Now
Manual value-2260
4/12/20 13:06:00.741 Tool - Saved parameters
4/12/20 13:06:26.767 Tool - (4425)Comp 19 B in variable - Was Manual value-0000
Now Man Id-2260
4/12/20 13:06:26.869 Tool - Saved parameters
4/12/20 13:06:51.344 Tool - (4434)Compare 20 type - Was "Mag" Now "Off"
4/12/20 13:06:51.445 Tool - Saved parameters
4/12/20 13:07:27.214 Tool - (4440)Compare 21 type - Was "Mag" Now "Off"
4/12/20 13:07:27.314 Tool - Saved parameters
4/12/20 13:07:47.513 Tool - (4446)Compare 22 type - Was "Mag" Now "Off"
4/12/20 13:07:47.613 Tool - Saved parameters
4/12/20 13:13:45.138 Tool - (9115)MenuTimer4 - Was 600.0 Now 1800.0
4/12/20 13:13:45.237 Tool - Saved parameters
4/12/20 13:14:17.699 Tool - (9146)Select system program - Was "NoWago.hex" Now
"8198029e.hex"
4/12/20 13:14:17.945 Tool - Saved parameters
4/12/20 13:25:12.715 Tool - (2600)Fast bypass - Was "Enable" Now "Disable"
4/12/20 13:25:12.818 Tool - Saved parameters
4/12/20 13:31:38.030 Tool - (9985)Enable Local HMI - Was "Disabled" Now
"ReadWrite"
4/12/20 13:31:38.133 Tool - Saved parameters
4/12/20 13:34:39.000 Event Log started
4/12/20 13:31:58 Fault - Power Supply
4/12/20 13:34:41.000 CPU Watchdog enabled
4/12/20 13:34:42.361 System started
4/12/20 13:34:42.361 Ver 6.8.1 09-25-19
4/12/20 13:34:42.361 FPGA version 1.5.0.25 2-16-18
4/12/20 13:34:42.361 Glue version 1.1.0.2 5-23-17
4/12/20 13:34:42.361 Network 1 module type: Anybus Ethernet
4/12/20 13:34:42.361 Network 2 module type: Siemens Modbus
4/12/20 13:36:49.395 User Alarm - VDF Apagado
4/12/20 13:36:56.055 User Alarm Reset - VDF Apagado
4/12/20 13:37:21.966 Tool - (9985)Enable Local HMI - Was "ReadWrite" Now "Read-
Only"
4/12/20 13:37:22.069 Tool - Saved parameters
4/12/20 13:37:29.118 Alarm acknowledge
4/12/20 13:39:12.469 Tool - (9146)Select system program - Was "8198029e.hex" Now
"NoWago.hex"
4/12/20 13:39:12.574 Tool - Saved parameters
4/12/20 13:44:20.000 Event Log started
4/12/20 13:40:21 Fault - Power Supply
4/12/20 13:44:23.000 CPU Watchdog enabled
4/12/20 13:44:24.360 System started
4/12/20 13:44:24.360 Ver 6.8.1 09-25-19
4/12/20 13:44:24.360 FPGA version 1.5.0.25 2-16-18
4/12/20 13:44:24.360 Glue version 1.1.0.2 5-23-17
4/12/20 13:44:24.360 Network 1 module type: Anybus Ethernet
4/12/20 13:44:24.360 Network 2 module type: Siemens Modbus
4/12/20 13:56:10.000 Event Log started
4/12/20 13:45:31 Fault - Power Supply
4/12/20 13:56:12.000 CPU Watchdog enabled
4/12/20 13:56:13.360 System started
4/12/20 13:56:13.360 Ver 6.8.1 09-25-19
4/12/20 13:56:13.360 FPGA version 1.5.0.25 2-16-18
4/12/20 13:56:13.360 Glue version 1.1.0.2 5-23-17
4/12/20 13:56:13.360 Network 1 module type: Anybus Ethernet
4/12/20 13:56:13.360 Network 2 module type: Siemens Modbus
4/12/20 13:58:59.837 Tool - (9985)Enable Local HMI - Was "Read-Only" Now
"Disabled"
4/12/20 13:58:59.941 Tool - Saved parameters
4/12/20 13:59:51.381 Tool - (9114)MenuTimer3 - Was 77760.0 Now 0.0
4/12/20 13:59:51.485 Tool - Saved parameters
4/12/20 14:00:01.415 Tool - (9115)MenuTimer4 - Was 1800.0 Now 0.0
4/12/20 14:00:01.518 Tool - Saved parameters
4/12/20 14:00:08.987 Tool - (9112)MenuTimer1 - Was 180.0 Now 0.0
4/12/20 14:00:09.079 Tool - Saved parameters
4/12/20 14:00:32.245 Tool - (9112)MenuTimer1 - Was 0.0 Now 180.0
4/12/20 14:00:32.349 Tool - Saved parameters
4/12/20 14:01:02.487 Tool - (9114)MenuTimer3 - Was 0.0 Now 77760.0
4/12/20 14:01:02.580 Tool - Saved parameters
4/12/20 14:01:06.506 Tool - (9115)MenuTimer4 - Was 0.0 Now 1800.0
4/12/20 14:01:06.598 Tool - Saved parameters
4/12/20 14:05:48.653 Tool - (2020)Rated input current - Was 135.7 Now 152.7
4/12/20 14:05:48.746 Tool - Saved parameters
4/12/20 14:07:45.158 Tool - (2430)Spinning load mode - Was "Forward" Now "Off"
4/12/20 14:07:45.261 Tool - Saved parameters
4/12/20 14:09:21.000 Event Log started
4/12/20 14:08:22 Fault - Power Supply
4/12/20 14:09:24.000 CPU Watchdog enabled
4/12/20 14:09:25.360 System started
4/12/20 14:09:25.360 Ver 6.8.1 09-25-19
4/12/20 14:09:25.360 FPGA version 1.5.0.25 2-16-18
4/12/20 14:09:25.360 Glue version 1.1.0.2 5-23-17
4/12/20 14:09:25.360 Network 1 module type: Anybus Ethernet
4/12/20 14:09:25.360 Network 2 module type: Siemens Modbus