Product data sheet 17951

17867
Characteristics C65N MCB, D
C curve, 14A, 230
400V, 13P, 6kA

Main
Range of product Multi 9
Range Multi 9
Product name C65
Product or component Miniature circuit-breaker
type
Device short name C65N
Device application Distribution
Poles description 3P
1P
Number of protected 13
poles
[In] rated current 4
1 A at 30 °C
Network type AC

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Trip unit technology Thermal-magnetic
Curve code D
C
Breaking capacity 6 kA Icn conforming to IEC 60898-1 - 230
400 V AC
Suitability for isolation Yes conforming to IEC 60898-1

Complementary

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Network frequency 50...60 Hz

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
[Ue] rated operational voltage 400
230 V AC
Magnetic tripping limit 10...14 x In
[Ics] rated service breaking capacity 6 kA at 100 % of breaking cap. conforming to IEC 60898-1 - 400 V AC
Limitation class 3 conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60898-1
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting mode Clip-on
Mounting support DIN rail
9 mm pitches 6
Height 81 mm
Width 54 mm
Depth 66 mm
22
Product weight 340 g
Mechanical durability 20000 cycles
Connections - terminals Tunnel type terminals, top or bottom
Tightening torque 2.5 N.m top or bottom power circuit
Earth-leakage protection Without

Environment
Standards IEC 60898-1
GB 10963.1
Product certifications CCC
CCS
IP degree of protection IP20
Pollution degree 3
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1

Feb 26, 2019


1
Relative humidity 95 % 55 °C
Ambient air temperature for operation -30...70 °C

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0627  -  Schneider Electric declaration of conformi-
ty Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Need no specific recycling operations