Академический Документы
Профессиональный Документы
Культура Документы
Grasso SP1
Large Series
Operating Manual (Translation of the original text)
P_241511_6
Operating Manual | Large Series
Screw Compressor Packages
Grasso SP1
COPYRIGHT
this document may contain or for their consequen-
All Rights reserved. ces.
No part of this documentation may be copied or pub- The manufacturer reserves the right to make techni-
lished by means of printing, photocopying, microfilm cal modifications during the course of further devel-
or otherwise without prior written consent of opment of the equipment covered by these operating
• GEA Refrigeration Germany GmbH instructions.
herein after referred to as the manufacturer. This Illustrations and drawings in these operating instruc-
restriction also applies to the drawings and diagrams tions are simplified representations. As a result of the
contained in the documentation. improvements and changes, it is possible that the
illustrations do not exactly match the unit you are
LEGAL NOTICE operating. The technical data and dimensions are
subject to change. No claims can be made on the
These operating instructions are part of the technical basis of them.
documentation for the scope of delivery. They con-
The manufacturer cannot accept liability for damages
tain important instructions for ensuring safe and
proper transport, installation, start-up, economic • which occur during the warranty period as a
operation, maintenance and repair of the unit. Their result of
observance helps in avoiding dangers, reducing
– improper operating conditions and conditions
repair costs and down-times and increasing the relia-
of use,
bility and durability of the unit.
These operating instructions are intended for the – inadequate maintenance,
users of the equipment and are specifically intended – improper operation,
for the operating company and its operating and
maintenance personnel. – incorrect installation,
It is essential that the operating company and its – incorrect or improper connection of the main
operating and maintenance staff read these operat- electrical drive,
ing instructions prior to transport, installation, start- • or which result from or can be attributed to
up, use, maintenance, repair, disassembly and dis- improper modifications or failure to observe the
posal. This obligation to read also applies to person- instructions;
nel involved in activities in the life phases of the
machine. • through the use of accessories or spare parts
The operating company must supplement these which were not supplied or recommended by the
operating instructions with instructions regarding manufacturer.
health and safety at work and environmental protec-
tion on the basis of existing national regulations for
industrial safety.
In addition to these operating instructions and the
binding accident prevention regulations valid for the
respective country and area where the product is
used, the recognised technical regulations for safe
and professional work must also be observed.
These operating instructions are part of the unit. The
entire documentation comprises these operating
instructions and all additional operating instructions
supplied with the unit. It must be kept readily availa-
ble where the unit is installed. The entire documenta-
tion must also be forwarded if the unit is installed at
another location and if the unit is sold.
These operating instructions have been written in
good faith. However, GEA Refrigeration Germany
GmbH cannot be held responsible for any errors that
Warning!
Stands for a possibly dangerous situa-
tion which leads to heavy physical
injuries or to the death.
Caution!
Stands for a possibly dangerous situa-
tion which could lead to light physical
injuries or to damages to property.
Hint!
Stands for an important tip whose
attention is important for the designa-
ted use and function of the device.
LAYOUT INFORMATION
Handling instructions
Handling instructions require you to do something. Several consecutive steps result in a handling sequence that
should be run in the specified order. The handling sequence can be divided into separate steps.
Handling sequence
1. Handling sequence step 1
– step 1,
– step 2,
– step 3.
2. Handling sequence step 2
The subsequent handling sequence is the expected result:
® Result of the handling sequence.
Individual handling steps
Individual handling steps are marked thus:
– Individual work steps
TABLE OF CONTENTS
1 BASICS 11
1.1 Importance of the documentation 11
1.2 Requirements for personnel, obligation to exercise due care 11
1.3 Legal foundations (Germany) 12
1.4 Specified Use 14
1.5 Warning against foreseeable abusive use 14
1.6 CE mark 15
2 MANUFACTURER INFORMATION 16
3 CUSTOMER SERVICE 17
3.1 Technical customer service department 17
3.2 Spare parts 17
3.3 Training courses 17
3.4 Service contracts 17
4 SAFETY 18
4.1 General information for safety 18
4.2 Behaviour in the case of emergency 18
4.3 Installation in explosive atmospheres, installation zones 1 and 2 18
4.4 Possible residual hazards 19
5 TRANSPORT, STORAGE 21
5.1 General instructions 21
5.2 Delivery 21
5.3 Transport (crane transport) 21
5.4 Bearings 22
5.5 Storage (several years) 23
6 INSTALLATION 25
6.1 Basic information for installation 25
6.2 Rigid installation 25
6.3 Anti-vibration mounting 25
6.4 Electrical connection 25
6.5 Sound insulation, weather protection 25
6.6 Information about noise emissions 27
7 DESCRIPTION OF DESIGN AND FUNCTION 32
7.1 Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Series 32
7.2 Technical specifications 34
7.3 Location of the product identification (type plate) 35
7.4 Information and safety labels on the product 37
7.4.1 Labelling of the pressure and temperature sensors, heater 37
7.4.2 Label of the safety valve 37
7.4.3 Labels of the screwed connections with DiNova ring 37
7.4.4 Labels of the pipelines 38
7.4.5 Marking the direction of rotation of the compressor drive motor 38
7.4.6 Marking the direction of rotation of the oil pump motor 38
7.4.7 Labels of the pressure gauge 39
7.4.8 Labeling of the control / control cabinet 39
7.4.9 Designation of the earth connection 40
7.5 Process flow diagram 41
7.6 Main components 42
7.6.1 Screw compressors 43
7.6.2 Compressor drive motor 44
7.6.3 Coupling 44
7.6.4 Oil separator 44
7.6.5 OMC block with oil filter system 45
7.6.6 Oil cooler 46
7.6.7 Oil pump 46
7.6.8 Suction filter combination SFC 46
7.6.9 Control 47
7.6.10 Fittings 47
7.6.11 Safety devices 48
7.6.12 Monitoring devices 49
7.6.13 Components installed by the client 49
TABLE OF FIGURES
fig. 1 CE mark 15
fig. 2 Designation of the attaching points. 21
fig. 3 Limit stop 22
fig. 4 Location of the product identification (type plate) 35
fig. 5 Type plate 36
fig. 6 Safety labels of the pressure and temperature sensors, heater 37
fig. 7 Label of the safety valve 37
fig. 8 Labels of the screwed connections 37
fig. 9 Labels of the pipelines 38
fig. 10 Marking the direction of rotation of the compressor drive motor 38
fig. 11 Marking the direction of rotation of the oil pump motor 38
fig. 12 Labels of the pressure gauge 39
fig. 13 Test verification for the control system 39
fig. 14 Designation of the earth connection 40
fig. 15 Process flow diagram Grasso SP1, Large 41
fig. 16 Standard Screw Compressor Package of Grasso SP1 LARGE Series 43
fig. 17 Grasso SP1 Large, position of the screw compressor 43
fig. 18 Grasso SP1 Large, position of the compressor drive motor 44
fig. 19 Grasso SP1 Large, position of the coupling 44
fig. 20 Grasso SP1, position of the oil separator 44
fig. 21 Grasso SP1 Large, position of the OMC block with oil filter system 45
fig. 22 Grasso SP1 Large, position of the oil cooler 46
fig. 23 Grasso SP1 Large, position of the oil pump 46
fig. 24 Grasso SP1 Large, position of the suction filter combination SFC 46
fig. 25 Grasso SP1 Large, position of the control 47
fig. 26 Corrosion resistance in presence of chlorides 55
fig. 27 Vacuum required to remove moisture from refrigerating plants 59
fig. 28 Stop valve open 60
fig. 29 Stop valve closed 60
fig. 30 Check valve 60
fig. 31 Shuttable check valve 60
fig. 32 Control valve 61
fig. 33 Shuttable check valve 61
fig. 34 Solenoid valve 61
fig. 35 Change-over valve 61
fig. 36 Oil pressure control valve 61
fig. 37 Overflow valve, safety valve 62
fig. 38 Pressure controlled check valve 62
fig. 39 Quick acting valve, spring-loaded 62
fig. 40 Charging valve, drain valve 62
fig. 41 Service valve 62
fig. 42 Oil temperature limiter 63
fig. 43 Temperature controlled control valve 63
fig. 44 Motor direction of rotation 65
fig. 45 Fine oil separation cartridge 80
1 BASICS
– applicable international and national standards,
1.1 Importance of the documentation – applicable occupational safety regulations,
These operating instructions are part of the technical – applicable accident prevention regulations,
documentation for the Grasso scope of delivery. It – applicable environmental protection regulations,
contains advice for operating the package/chiller
safely, properly and economically. The observance – the construction and functioning of the unit,
of the operating manual helps in avoiding dangers, – recognised technical regulations for safe work
reducing repair costs and down-times and increasing according to good professional practice.
the reliability and durability of the package/chiller.
The technical personnel must:
This operating manual is directed at the users of the
package/chiller and is specifically intended for the – be able to assess the work assigned to them,
operating company and its operating and mainte- recognise and avoid possible dangers,
nance personnel. This operating manual must be – be authorised by those responsible for the safety
read prior to transport, installation, commissioning, of the system to carry out the requisite work and
maintenance, repair, disassembly/disposal. activities.
All work explained in this operating manual must only
be carried out by technical personnel. Caution!
This operating manual must be supplemented with No arbitrary changes may be made to
instructions based on prevailing national regulations the control or other components
regarding industrial safety, health protection and belonging to the unit. Maintenance
environmental protection. work may only be done by authorised
In addition to this operating manual and the manda- service staff.
tory accident prevention regulations applicable for
the respective place of installation, the accepted Special requirements for the electrical techni-
technical regulations for safe work according to good cians
professional practices must also be observed. Work on electrical components and modules may
The operating manual is a part of the total product. only be carried out by an electrical technician
The entire documentation, consisting of this operat- according to the rules relevant to electrical engineer-
ing manual as well as all supplied additional instruc- ing. Furthermore the operator has to take care that
tions, is to be always kept easily accessible at the the electrical systems, tools and fixtures are oper-
place of installation of the package/chiller. The com- ated according to the rules relevant to electrical engi-
plete set of documentation must also accompany the neering and applicable standards and serviced prop-
package/chiller if it is sold. erly.
– In principle it is prohibited to carry out work on
parts under voltage.
1.2 Requirements for personnel, obliga- – Fuses may only be replaced and not repaired or
tion to exercise due care bypassed.
the package/chiller must not be operated in the – Accident Prevention Regulation including
defective condition. implementation regulations (BGR 500, chapter
2.35) on refrigeration plants, heat pumps and
Minimum age cooling equipment (BGV B3) regarding noise
The minimum age for the operation of the package/
– EN 12284 Refrigerant fittings, safety related
chiller and installation is 18 years. All persons
technical definitions, testing and marking
involved in the assembly and installation of the pack-
age/chiller and the system must get themselves – DIN 2405 Pipes in refrigeration plants, marking
trained at regular intervals and/or familiarise them-
– VDMA specifications,in particular VDMA 24
selves with the current technical data of the device.
243 and 24 020
The training and instructions is to be conducted at
least once a year, unless some other interval has – VDI Guidelines
been agreed upon with the manufacturer.
– Instruction sheets for handling ammonia,
Obligation to exercise due care Instruction sheet for halogenated hydrocar-
bons containing fluorine BGI 648
The statutory regulations for meeting the obligation
to exercise due care are to be observed. – Safety data sheet for ammonia and other refrig-
Meeting the obligation to exercise due care accord- erants and refrigeration oils
ing to the current level of technology requires that The list of rules and standards has been taken from
everything that is Status Report No. 5 of the German Refrigeration and
Air Conditioning Engineering Association "Safety and
– technically possible (use of accepted technologi-
environmental protection in ammonia refrigeration
cal rules) and
plants" and also fully applies to other refrigerants.
– economically reasonable
Danger!
be done to prevent damage in a protectively safe
manner.
– Federal Pollution Control Act (BImSchG), 4th – guidelines and recognised engineering practice,
BimSchV listed in these operating instructions must be
observed at least!
– Water Resources Act (WHG), VawS
Hint!
– Hazardous Substances Ordinance (GefStoffV)
If the package/chiller is used in a
– Recycling and Waste Management Act (KrW-
country other than Germany, the rules
AbfG)
and regulations applicable at the place
– DIN EN 378, Part 1 to Part 4 Safety-related of installation must be observed and
technical requirements and environmental complied with!
requirements
The mandatory accident prevention regulations
applicable for the respective country and area where
the product is used must also be observed.
The pressure equipment described here must not be – electrical components are wrongly connected.
used for any purpose other than the purpose speci-
fied here. The units must only be installed by the Hint!
supplier/installer and not by the end user. If the pres-
Watch voltage and frequency!
sure equipment is not used according to the regula-
tions, the safe use of the equipment is not guaran-
– mechanical components are wrongly connected.
teed. The supplier/installer or the operator – and not
1.6 CE mark
Hint!
Watch pressure and temperature! By affixing the CE mark, the manufacturer confirms
the conformity of the product with the applicable EC
– the supporting, hanging and storage facilities are Directives and compliance with the principle require-
misused. ments stipulated within them.
2 MANUFACTURER INFORMATION
GEA Refrigeration Germany GmbH is a company
within GEA Refrigeration Technologies, the Refriger-
ation Technology Segment of the GEA Group and
provides its customers around the world with high-
quality components and services for refrigeration and
process technology applications.
Locations:
3 CUSTOMER SERVICE
GEA Refrigeration Germany GmbH supplies prod- In most cases, you will receive your spare parts
ucts of high quality and reliability. In addition, the within 24 hours after placing the order.
manufacturer ensures continuous operation of the You can contact us using the following hotlines:
refrigeration and process technology system and
provides exceptional service for the components • Wireless, out of hours
supplied. +49 (0) 172 30 14 579
• Landline, weekdays from 8 to 17 hour
+49 (30) 43 59 27 50
3.1 Technical customer service depart-
ment • Fax
+49 (30) 43 59 27 58
Do you require support from the technical customer
service department? Specially trained, experienced • Email
service technicians are available on call for you in Grasso-parts@geagroup.com
order to provide assistance in case of technical prob-
lems and to offer support in the framework of our • Order spare parts from our G-Pos. online
after-sales service. shop
24/7 Hotline: (Grasso Parts online shop)
the hotlines can reached around the clock on every gea-refrigeration.de.spareparts@gea.com
day of the week:
• Wireless 3.3 Training courses
+49 (0) 172 39 12 050
Warning!
• Landline, weekdays from 7 to 17 hours
+49 (30) 43 59 27 61 All work on our systems must only be
carried out by technical personnel!
+49 (30) 43 59 27 62 Acquire the technical know-how
• Email: required for this in good time!
Grasso-service@geagroup.com Comprehensive training courses are held regularly
outside of Germany, Austria and Switzerland please for service technicians and mechanics, thus ensuring
contact: the safe and proper use and maintenance of our sys-
• local sales office tems.
www.gearefrigeration.de • Email
technical support for liquid chillers with reciprocating Grasso-service@geagroup.com
compressors in Germany, Austria and Switzerland
• 24/7 Hotline
3.4 Service contracts
+49 (345) 78236 20
The specialists of our Technical Customer Service It is possible to sign a long-term service agreement
department support you in installations, acceptan- (service contract). For further information regarding
ces, maintenance, operating questions, on-site the content, scope and conditions of the possible
inspections and repairs of our products. service options, please contact the Technical Cus-
tomer Service department.
• Email:
3.2 Spare parts Grasso-service@geagroup.com
GEA Refrigeration Germany GmbH has its own prac-
tical and rapidly working spare parts department to
supply the necessary spare parts worldwide. Neces-
sary spare parts are shipped as quickly as possible.
4 SAFETY
4.3 Installation in explosive atmos-
pheres, installation zones 1 and 2
4.1 General information for safety
Danger!
The safety aspects to be observed for operating the
equipment are shown in the chapter on "Safety". The additional instructions for using
The equipment has been developed and manufac- screw compressor packages in explo-
tured according to the currently applicable state of sive atmospheres, installation zones 1
the art and is reliable in operation. It has been tested and 2, must be complied with!
and left the factory in a technically faultless safe con-
dition. Function and Design
In order to maintain this condition for the operation The same functional and design characteristics apply
time, the details of the project documentation and to the maintenance instructions for the use of screw
certificates must be observed and complied with. compressor packages in potentially explosive atmos-
When operating the equipment, at least the general pheres as described in the respective applicable
safety regulations and the provisions and guidelines operating manual.
referred to in this documentation must be observed. In addition to this, the following extensions
Only compliance with all provisions and guidelines apply:
will enable optimum protection of the personnel as – All components relevant for the use of screw
well as dangers to the environment and the safe and compressor packages in relation to their use in
smooth operation of the equipment. potentially explosive atmospheres (concerns
both electrical and non-electrical components)
are separately designed and documented! The
4.2 Behaviour in the case of emergency extended documentation scope (component
descriptions, certificates, calculations) is part of
Hint! the product documentation.
Familiarise yourselves with the local – Extension to the method of working
evacuation plan before beginning the
The use of screw compressor packages is exten-
work.
ded to use in potentially explosive atmospheres,
Should an emergency situation arise despite adher- including the compression of process gases
ing to the safety regulations, the package/chiller (only compression for the purposes of pressure
must be shut down immediately and isolated from increase). The screw compressor packages are
the electrical mains. not suitable for pumping potentially explosive
mixtures. This means that, when the compressor
The mains cable must be blocked in such a way it is
is in intake condition, the pumped liquid must not
not possible to restart the unit accidentally and
contain any oxygen. The intake condition always
marked as such.
refers to pressure layers in the overpressure
The operator of the complete system has to take range.
care that an isolation device, e.g. a mains switch with
The owner operator and the system builder must
appropriate contact rating and an integrated indica-
use monitoring devices reflecting the respective
tor, is pre-installed in the mains cabling on site.
state of the art standards to positively monitor
A separate mains cable/feed cable must be laid for and ensure this effect.
the operation of the package/chiller.
– Safety equipment extension
The mains cable/feed cable is to be specially protec-
ted and provided with an emergency stop switch. If oil heaters are used in potentially explosive
atmospheres (see component specification),
additional, separate oil level monitoring is abso-
lutely necessary to ensure a minimum oil level
above the heating elements. To this end, a sepa-
rate oil level switch is used in each use case
according to the necessary explosion protection – Appropriate special tools approved for the poten-
specification. tially explosive atmosphere must be used.
Operation – Only original spare parts may be used. If original
The same regulations apply in regard to the operat- spares are not used, the guarantee is invalidated
ing instructions for screw compressor packages in or the owner is liable in the event of damage.
potentially explosive atmospheres as described in – Each maintenance inspection (see maintenance
the applicable operating manual. book) must also include checking the secure fit
In addition to this, the following extensions of the threaded connections for the coupling
apply: safety hood.
– In addition, the legal safety regulations apply to
the people responsible for operating the screw
compressor package, and must be complied with 4.4 Possible residual hazards
respect to the transport, assembly, operation and
Warning!
maintenance and if necessary the replacement
of subassemblies, etc. in potentially explosive Despite careful design of the machine
atmospheres. and implementation of all the safety-
The owner operators regulations must also relevant regulations, further risks for
always be observed – see also section: Safety persons and machine during all life
information for compressor, Appendix E, and for phases of the package/chiller cannot
package, Appendix E. be fully ruled out. The additional safety
instructions in the individual chapters
– The electrical engineering regulations for instal- of this manual must therefore be care-
lations in potentially explosive atmospheres , fully observed!
especially EN 60079-10, apply to the installation
and connection of electrical components. The Residual risks that were ascertained during the risk
relevant prescribed cabling material must be assessment carried out for the product according to
used. safety standard EN ISO 14121 - Safety of Machines
- are:
– The whole screw compressor package must be
earthed by the owner operator. – mechanical hazards due to sharp sheet metal
edges and projecting parts,
Maintenance
The same regulations apply to the maintenance of – electrical hazards as a result of inadvertently
screw compressor packages in potentially explosive coming in contact with terminals and cables,
atmospheres as described in the respective applica- – thermal hazards as a result of inadvertently com-
ble operating manual. ing in contact with heat exchangers and pipes,
In addition to this, the following extensions – exposure to noise,
apply:
– hazards caused by vibration due to improper
– In addition, the legal safety regulations for the installation,
installation of the screw compressor packages
apply to the people responsible for the mainte- – hazards due to working materials and other
nance of the screw compressor package with materials in case of allergies orthe like,
respect to the maintenance of individual compo- – neglect of ergonomic principles,
nents or assemblies or their complete replace-
ment in potentially explosive atmospheres. – combinations of various hazards,
– The maintenance may only be carried out in – unexpected start-up, unexpected rotation in case
agreement/with the knowledge and release of of incorrect electrical connections or defects,
the owner operator. – shut-down, emergency stop when defects are
– The maintenance and replacement regulations detected,
resulting from the operating manual for the com- – changes to the rotational speed,
ponents must be conformed with.
– power failure,
Hint!
There are no radiation hazards
5 TRANSPORT, STORAGE
5.2 Delivery
5.1 General instructions Shipment is made in the type of packing stipulated in
the order. The screw compressor package is gener-
Caution! ally supplied without packing.
Adequate lighting must be ensured The screw compressor package has an inert gas
during loading and unloading as well filler in the refrigerant circuit.
as for storage in order to avoid injuries
Warning!
and damage to property.
There is a danger of impacts and The compressor(s) of the screw com-
stumbling due to protruding parts on pressor package is/are not filled with
the equipment (e.g. valve caps). There oil. The screw compressor package
is also the danger of being cut on must not be started, therefore, before
sharp edges and surfaces. There is a proper assembly and start-up.
danger of crushing parts of the body
during the transport work. Personal
protective equipment (work clothing, 5.3 Transport (crane transport)
work books, gloves) must be worn
during all activities on the equipment. Warning!
Warning!
Screw compressor packages must be
adequately protected from external
influences (humidity, frost, extreme
heat) during storage. This usually con-
cerns lengthy standing times outdoors
before installation and start-up of the
refrigeration plant. The manufacturer
recommends the use of plastic sheet-
ing to cover the whole product.
The venting slits of the electric motors
must always be covered!
fig.3: Limit stop
Storage temperature: 5°C ... 40°C
The composition of the paint on the screw compres-
Danger! sor package is designed for installation in the
Make certain there is no one under the machine room (inside installation). Contact with
suspended load during transport with water (including water spray) must be avoided.
the crane!
Hint!
Does not apply to sliding bearing com-
pressor drive motors.
Caution!
After completion of the storage period
and prior to re-delivery, a general
review in the factory or a general
examination at the storage location,
performed by the technical customer
service technician of GEA Refrigera-
tion Germany GmbH, is recommended.
Please pay attention to the information
in the "Start-up" chapter.
The general check includes changing
the O-ring on the compressor shaft
seal as well as replacing the shaft seal
of the oil pump.
6 INSTALLATION
misalignment ≤ 0.25 mm) at the coupling is attained
again. Then tighten the foundation bolts.
6.1 Basic information for installation
Caution!
6.3 Anti-vibration mounting
During the installation, make sure that
substances escaping from leaks do The frame of the screw compressor unit must be
not reach into the soil, groundwater or aligned with the levelling bolts until the coarse align-
surface water. The applicable legal ment (radial and angular misalignment (radial and
regulations must be heeded at the angle offset ≤ 0.25 mm) at the coupling is attained
place of installation (e.g.for Germany: again.
German Federal Water Act WHG). Before tightening the foundation bolts of the isola-
tors, check that the isolators over the spring (pre-
All foundation calculations, the selection of materials dominantly made of rubber) are free and do not lie
and the soil analysis are the designer's or owner’s on the foundation.
responsibility.
A plan must be produced for proper and professional
assembly prior to the installation. The electrical and 6.4 Electrical connection
operating media connections must be established. It
must be borne in mind that, in addition to the installa- Danger!
tion area of the screw compressor package, there
Contact with live components is pro-
must be sufficient space available for the pipes as
hibited.
well as for operating during maintenance activities.
Produce the earth connection accord-
Install the screw compressor package on a level sur-
ing to the designation in the general
face. The difference from the horizontal must not be
assembly drawing. See chapter "Des-
more than 0.3 %. Provide enough space for mainte-
ignation of the earth connection".
nance work.
Under normal conditions, the screw compressor Before starting work, make sure that all parts to be
package stands solidly on the installation surface connected are de-energised, e.g. by removing the
due to its own dead weight. We recommend that you main fuse in all phases or installing a jumper wire.
provide ribbed rubber plates for shock absorption The insulation resistance of the electrical tools and
between the support surface and screw compressor fixtures and wiring is to be checked. The connection
package feet or machine base frame. may only be undertaken if this value lies in the allow-
If greater damping is required (installation on a floor able range.
ceiling or on the roof), vibration dampers must be All electrical connections must be established and all
provided. The appropriate type of vibration damper electrical consumers/sensors must be connected
must be determined and realised for this case. Also according to the circuit diagram.
decouple the secondary refrigerant lines using com-
pensators when vibration absorbers are used.
The welding seams must be inspected in accordance 6.5 Sound insulation, weather protec-
with the Pressure Equipment Directive after welding tion
work by the customer or operator on pipe line con-
nections and flanges. If the screw compressor package is intended for out-
door installation, it must be provided with a suitable
housing for sound insulation and weather protection
6.2 Rigid installation by the customer. The weather protection must pro-
vide the machine with adequate protection against
The frame of the screw compressor unit/ liquid chiller the climatic conditions at the installation location.
is placed on foundation bolts on a prepared founda-
tion. The frame must be levelled with suitable shims
such that the coarse alignment (radial and angular
Hint!
The screw compressor package is not
intended for unprotected outdoor
installation. Protection against exter-
nal influences, especially dirt, dust
and moisture (wetness), is essential.
Caution!
According to EU Directive 2003/10/EC, the allowable exposure limit value regarding the daily
noise exposure level is 80 db(A). In the event of noise levels above this limit value the system
operator must provide the operator with information on exposure to noise and personal hear-
ing protection and ensure that this is also worn (2003/10/EC Article 6).
Max 91 91 91
22
Min 84 84 84
Max 92 92 92 92
30
Min 85 85 85 85
Max 93 93 93 93 93
37
Min 86 86 86 86 86
Max 94 94 94 94 94 94
45
Min 87 87 87 87 87 87
Max 95 95 95 95 95 95 95
55
Min 88 88 88 88 88 88 88
Max 96 96 96 96 96 96 96
75
Min 89 89 89 89 89 89 89
Max 97 97 97 97 97 97 97
90
Min 90 90 90 90 90 90 90
Max 98 98 98 98 98 98
110
Min 91 91 91 91 91 91
Max 98 99 99 99 99
132
Min 92 92 92 92 92
Max 101
200
Min 94
Max 95 95
55
Min 88 88
Max 96 96 96
75
Min 89 89 89
Max 97 97 97 97
90
Min 90 90 90 90
Max 98 98 98 98 98 98
110
Min 91 91 91 91 91 91
Max 99 99 99 99 99 99 99
132
Min 92 92 92 92 92 92 92
Max 105
630
Min 99
Max 99
132
Min 92
Min 94 94 94
Hint!
The individual emission data for the motor-compressor combinations can be found in the
tables and added using logarithms for screw compressor packages and chillers (DuoPack ver-
sion) as well as two-stage screw compressor packages.
7.1 Product code of screw compressor packages - Grasso SP1, SP2, SPduo and M Ser-
ies
A Oil cooling
Code letter Theoretical volume flow Code letter Theoretical volume flow
at 2940 min-1 in m³/h at 2940 min-1 in m³/h
C 231 T 1460
D 265 V 1740
E 321 W 1940
Code letter Theoretical volume flow Code letter Theoretical volume flow
at 2940 min-1 in m³/h at 2940 min-1 in m³/h
G 372 Y 2390
H 471 Z 2748
L 544 XA 3250
P 805 XD 5800
R 1040 XE 7170
S 1290 XF 8560
* Grasso M Series
Y Screw compressor package version
6 Booster Vi = fixed
8 -- --
A Oil cooling
C Refrigerant injection
Examples of designation
XA B - 6 A Singe stage screw compressor package Grasso SP1 with screw compressor 3250 m³/h
(XA), refrigerant NH3 and vertically installed oil separator (B), booster with fixed internal vol-
ume ratio (6)with oil fine separation and water-cooled oil cooler (A)
TA-2A Singe stage screw compressor package Grasso SP1 or SSP1 with screw compressor 1460
m³/h (T), refrigerant NH3 and horizontally installed oil separator (A), fixed internal volume
ratio Vi = 3.6 (2) with oil fine separation and water-cooled oil cooler (A)
NA-3B Screw compressor package Grasso M with screw compressor 873 m³/h (N), refrigerant NH3
and horizontally installed oil separator (A), fixed internal volume ratio Vi = 4.8 (3)with oil fine
separation and refrigerant-cooled oil cooler (A)
LD - 2 A Screw compressor package Grasso SPduo with 2 of screw compressors 544 m³/h (L),
refrigerant NH3 and DuoPack version or multiple configuration (D), fixed internal volume
ratio Vi = 3.6 (2) with oil fine separation and water-cooled oil cooler (A)
W E - 6 A (L) Two-stage screw compressor package with LP screw compressor 1940 m³/h (W), refriger-
ant NH3 two-stage package (E), LP-compressor as booster (6), with oil fine separation and
water-cooled oil cooler (A), HP-compressor 544 m³/h (L)
– order specification,
7.2 Technical specifications – list of parameters,
Packages / chillers are designed and manufactured – general assembly drawing,
for special fields of application. For technical specifi- – P+I diagram.
cations see the following.
Type plate
Weight without filling: Weight of the screw compressor package without filling
7.4 Information and safety labels on the 7.4.2 Label of the safety valve
product
(safety labels)
Danger!
The safety-related labels on the pack-
age/chiller must be followed!
7.4.7 Labels of the pressure gauge 7.4.8 Labeling of the control / control
cabinet
(information plate)
(information plate)
• Label on the rear side of the control unit of the
control system (visible after opening the switch-
ing cabinet):
– Project name
– Make number of the package/chiller
– MPI address
• Label on the inside of the switching cabinet:
– Test verification for the control system
7.4.9 Designation of the earth connec- See general assembly drawing for the position of the
tion earth connections.
10 Screw compressors
15 Compressor drive motor
20 Oil separator
25 Oil filter
30/200 Oil cooler (water cooled/ refrigerant cooled)
40 Oil pump
45 Suction filter
55 Check valve – suction side
60 Check valve – pressure side
260 Stop valve – pressure side
280 Stop valve – suction side
010 Screw compressors See installation instructions for the screw compressor
015 Compressor drive motor See operating manual of the compressor drive motor
025 OMC block (can be arranged as separate oil filter for greater See component documentation
amounts of oil)
030 Oil cooler (not shown in the picture) See component documentation
040 Oil pump (can be arranged as an external oil pump for See component documentation
greater amounts of oil)
Safety devices
The documentation of the main components are integral parts of the product documentation (see product
description or operating manual from the supplier, e.g. for the compressor drive motor).
The screw compressors are characterised by a com-
pact design, high reliability, high-quality components
7.6.1 Screw compressors and ease of maintenance.
Screw compressors are oil-injected dual-rotor posi-
tive displacement machines.
The screw compressors are operated with refrigerant
(standard: ammonia NH3, other refrigerants on
request). The refrigerating machine oil for the refrig-
erant must be selected in accordance with the infor-
mation about lubricating oils for screw compressors.
Various series and sizes of screw compressors are
available for different fields of application.
The screw compressors are driven directly by the
compressor drive motor via a flexible coupling.
7.6.3 Coupling
Hint!
The documentation of the screw com-
pressor (installation instructions, part
lists, drawings) is part of the product
documentation.
Hint!
Standard: The compressors are driven via a cou-
pling by means of an air-cooled 2-pole IP23 electric The documentation of the coupling
motor with an operating voltage of 400 V; 50 Hz. (operating manual) is part of the prod-
Optional: Other protection classes, operating vol- uct documentation.
tages and frequencies as well as speed-controlled
motors are available on request.
The oil separator is installed vertically. 7.6.5 OMC block with oil filter system
Hint!
The documentation of the oil separator
(operating and maintenance instruc-
tions, acceptance certificate) is part of
the product documentation.
Oil heater
Electric oil heaters are installed in the oil separator in
order to heat the oil-refrigerant mixture in the oil sep-
arator while the screw compressor package is at a
standstill. Oil heating prevents condensation of the
refrigerant in the oil and hence any foaming of the oil
during start-up.
Oil heaters are equipped with: fig.21: Grasso SP1 Large, position of the OMC block with oil fil-
ter system
– Temperature controller to maintain a constant
oil temperature in the oil separator
The OMC block includes the oil distribution system of
(adjustable from 20°C to 150°C, preset to 60°C) the oil circuit. Necessary control and shut-off fittings
– Temperature limiter in case of faults, e.g.dry- are integrated in the OMC block. Connections for
running protection temperature and pressure sensors as well as service
(permanently set to 150°C) ports are present. The OMC block is combined with
a standardised filter system and oil pump units and
The oil heating is switched on when the screw com- forms the central control and operating unit in the oil
pressor package is at a standstill and switched off circuit.
automatically when starting up. Manual disconnec-
tion is recommended for prolonged standstill periods. Optionally, the OMC block can be equipped with a 3-
way valve element (for ensuring a minimum oil tem-
Hint! perature when starting the compressor).
The documentation of the oil heater Hint!
(operating and maintenance instruc-
tions, acceptance certificate) is part of The documentation of the OMC block
the product documentation. (operating manual, acceptance certifi-
cate) is part of the product documenta-
tion.
The oil cooler is used for cooling the oil heated in the
compressor in order to ensure sufficient oil viscosity
for supplying to the compressor.
Hint!
The documentation of the oil cooler
(operating manual, acceptance certifi- fig.24: Grasso SP1 Large, position of the suction filter combi-
cate) is part of the product documenta- nation SFC
tion.
The suction filter combination SFC contributes sub-
stantially to the high working reliability of the compo-
7.6.7 Oil pump nents and the overall product.
The suction filter combination prevents dirt particles
carried by the suction flow from entering the com-
pressor. The flow through the suction filter element is
from the inside to the outside. It is designed so that
monitoring is not required. The filter element can be
cleaned.
Hint!
The documentation of the suction filter
combination SFC (operating manual,
acceptance certificate) is part of the
product documentation.
Hint!
The documentation of the controller
(operating manual, circuit diagram,
parameter list, communication guide-
line, Quick Reference Card) is part of
the product documentation.
7.6.10 Fittings
fig.25: Grasso SP1 Large, position of the control The term fitting generally designates a control ele-
ment of the machine. Among other things, the term
The screw compressor package is equipped with a fitting is also used for valves if these are used for the
GSC TP type control as standard. control and regulation of fluid flows in the piping.
The GSC TP consists of the control unit with opera- Furthermore, all kinds of installations in piping, such
tor keypad and display unit, indicator lights for "Run- as sight glasses, measurement apertures, filters and
ning", "Warning" and "Alarm", the emergency stop similar are also designated as fittings. Therefore, fit-
button, the output relays and the housing. tings also include all kinds of valves, such as:
The GSC TP will be mounted directly on the com- – Stop valves
pressor package unit (standard). As an option, the
– Check valves
GSC TP can be arranged in a control centre.
– Safety valves
The GSC TP performs the following functions as
standard: – Throttle valves
• Display of all important physical and technical Each fitting has its own field of use, according to the
parameters, e.g.pressure, temperature, motor pressure or temperature in the pipe, the size of the
current, capacity, number of operating hours, pipe, the sealing requirements for the fitting, the
operating mode and status signals reduction and direction of the flow of liquid as well as
the medium itself.
• Automatic start-up and shut-down of the screw
The safety fittings are used to limit the pressure in
compressor package and capacity control
systems which are under pressure.
depending on the suction pressure or an external
temperature Each fitting is designed for the specific application.
The fittings can be operated manually or by motor,by
• Monitoring of all operating parameters gear motors, or pneumatic or hydraulic cylinders, for
• Compressor capacity limitation, in case the example. In reset fittings, the flow of fluid in the pipe
measured discharge pressure, suction pressure, causes automatic closing of the valve.
secondary refrigerant temperature or motor cur- Depending on the model, different closing elements
rent indicate overload (e.g.valve discs, flaps, pushers) close the pipe con-
nected to the fitting.
• Fault memory with date and time
• Wire failure detection for all analogue input sig- Hint!
nals The documentation of the fittings
• Password protection for preventing unauthorised (acceptance certificates) forms part of
access to important parameters the product documentation.
motor off if the discharge pressure rises above the – Differential pressure of oil pressure after oil filter
set point. and discharge pressure (oil filter monitoring) -
Switch-off pressure 1 = See parameter list optional -
Switch-off pressure 2 = See parameter list
If the liquid refrigerant can reach more than 90% of
the oil separator’s volume, the client has to install an 7.6.13 Components installed by the cli-
additional safety valve against liquid expansion in the ent
oil separator. Design in accordance with EN 13136,
position in accordance with EN 378-2 Appendix F. Warning!
The components and parts the cus-
Thermostat (361) oil heater
tomer installs in particular the secon-
Setting value = See parameter list dary refrigerant and cooling medium
Temperature limiter (362) oil heater circuits as well as the oil circuit need
The temperature limiter shuts down the oil heating if to made from materials suitable for the
a specific surface temperature of the oil heater is fluids flowing through them. Further-
exceeded. more, in the event of modifications to
the product by the customer, the
effects on the safety devices are to be
checked.
7.6.12 Monitoring devices
GEA Refrigeration Germany GmbH
The following operating values will be continually does not assume any liability for dam-
monitored in a standard screw compressor package: age arising and the violation of the
– safety regulations which result from
Suction pressure
the use of unsuitable materials or
– Discharge pressure through modification to the product
– Oil pressure oil circuit monitoring which is not considered in the original
safety concept.
– Suction temperature
– Discharge temperature
– Oil temperature 7.7 General functional description
– absolute primary slide position Screw compressor packages are refrigeration sys-
tem components and serve to compress refrigerants
– Motor current
such as ammonia (or other operating media on
– Suction pressure saturation temperature request).
– Saturation temperature Operation as a heat pump is also possible.
of condensing pressure
– Number of running hours
7.8 Refrigerant circuit
– Difference between oil and discharge pressures
(oil circuit monitoring) The screw compressor draws in refrigerant vapour
through the suction filter combination and suction fil-
– Set point of controled value in °C ter and then discharges the compressed vapour into
– Real point of controled value in °C the plant via the oil separator and discharge check
valve.
– Internal volume ratio
The check valve function of the suction filter combi-
– Used refrigerant nation SFC prevents pressure equalisation with the
LP side of the plant and simultaneously prevents
– Controled value
reverse rotation of the screw compressor.
– Used options The discharge check valve prevents refrigerant from
– Oil pressure after oil filter - optional - re-condensing in the oil separator.
7.9.7 Oil circuit, OMC block Secondary Fluids that can absorb the heat of
refrigerant a system and dissipate it to a
An OMC-block (oil management block) is flanged on refrigerant (reversible process)
to the oil filter as an oil distributor system. The oil and are used for the cooling of a
flow is distributed via the bore-holes and channels to system (industrial process)
functional ranges of the screw compressor. All regu-
lating valves and shut-off valves necessary for the Heating Media (liquid or air), which trans-
regulation of the oil circuit are integrated into the agents port and emit the heat absorbed in
block. As a result, a centralised control unit is availa- the secondary refrigerant. If water
ble for the screw compressor package. is used as the heat carrier, the
The oil filter with OMC-block (oil management block) terms warm water or cooling water
is fitted with an oil drain and refilling stop valve which are also used.
may be connected to a separate oil pump or
receiver.
Vent valves are fitted to oil filters for maintenance
and repair purposes. 7.11.2 Operating media
The oil in oil filter may be drained for changing oil fil-
ter via a separate stop valve.
7.11.2.1 Refrigerant
7.10 Capacity control The technical order specification defines the refriger-
ant used. All components of the screw compressor
The screw compressors are fitted with a continuous package are designed for use with the defined refrig-
capacity control with a range of 10 -100%. erant.
The capacity is adjusted by shortening the screw
Hint!
compressor stroke. The defining factor for the com-
pression process is the effective rotor length; this is The safety data sheet for the refriger-
altered by a hydraulically operated control slide. ant used must be observed. The safety
The position of the control slide is recorded by the data sheet is part of the product docu-
position sensor. The control device signals the mentation.
attainment of the MIN or MAX end position and the
relative control slide position can be displayed on the
Touch Panel in percent.
The hydraulic adjustment of the control slide is done
using four solenoid valves which are integrated into a
single block.
The control slide travel speeds in the MIN and MAX
directions should be the same as much as possible
during operation to ensure better compressor con-
trol.
Compressor type P R, S, T V, W, Y
Danger! Hint!
When operating the screw compressor If you fail to adhere to the limiting val-
package in explosive atmospheres, the ues stated in VDI 3803, the manufac-
special safety instructions for use in turer cannot provide any warranty for
explosive atmospheres that are men- water carrying parts within its supplied
tioned in this operating manual must components.
be heeded. Clarification as to whether or not it is
possible to adhere to these limiting
Hint! values with the respective water condi-
The screw compressor packages can tions should be agreed on with a spe-
basically be used in explosive atmos- cialist company during the planning
pheres. and design phase.
Some specifics must be heeded when using the The limiting values as per VDI 3803, as required for
screw compressor packages in explosive atmos- the use of carbon steel components in non corrosive
pheres of installation zones 1 and 2. water systems, are listed below.
The basis for use in explosive atmospheres is the
following data of the operator: Water quality requirements, parameters
Hint!
Water quality requirements, parameters
Manufacturer's recommendation: Use
Criterion Value Unit uncontaminated secondary refriger-
ants and cooling media, in particular in
Active biological chillers and when using of plate heat
KBE < 10,000 per ml exchangers.
components
The media quality must be assured by
Thickness factor EZ 2-4 means of an appropriate filter on the
inlet to the heat exchanger. The mesh
The use of carbon steel and cast iron is required in for such a filter must be ≤ 0.9 mm!
the most of applications water conditioning with cor- Should the chiller be required to
rosion inhibitors. remain in operation during filter clean-
The use of stainless steel requires very special moni- ing, double filters must be used. Pres-
toring of water in apply to Chloride contents (risk of sure loss through the filter must be
stress crack and pitting corrosion). taken into consideration on the build-
ing side when configuring the pump.
Hint!
The manufacturer recommends enlisting the services
Recommend when using plate heat of a reputable water conditioning company.
exchangers in the refrigerant circuit
< 100 ppm Cl while using steel 1.4301
and
maximum 40°C wall temperature in the
plate heat exchanger
< 200 ppm Cl while using steel 1.4401
and
maximum 100 °C wall temperature in
the plate heat exchanger
8 START-UP
The following points must be observed before
commencing with the start-up:
8.1 Important information for start-up
– Check of the external condition of the screw
Warning! compressor package (check of insulation, trans-
port damage... ).
Contact with live components is pro-
hibited. – The area around the machine in which the start-
up is carried out must be marked and secured
Hint! against the access of unauthorised persons. Suf-
The Customer Service department of ficient lighting of the working area must be
GEA Refrigeration Germany GmbH ensured to prevent personal injury and material
offer comprehensive support for start- damage.
ing up the screw compressor package. – Personal protection gear (work clothing, work
For contact details, please refer to the boots, gloves) must be worn during all work on
chapter entitled "Technical customer the screw compressor package. There is a dan-
service". ger of impact and stumblingfrom protruding parts
on the screw compressor package (e.g. valve
Warning! caps). There is also the danger of cut wounds on
The screw compressor package must sharp edges and rough surfaces. All activities
only be operated by suitably skilled must therefore be carried out with particular
personnel who are familiar with the attention.
contents of the operating manual for – Suitable hearing protection must be worn in
screw compressor packages. order to protect against damage to hearing or
The safety regulations for refrigeration deafness.
plants must always be observed in
– Thermal hazards resulting in injuries due to
order to prevent damage to the screw
compressor package and injury to the burns or freezing may occur on contact with
operating staff. parts of the system which are at a very high or
very low temperature. Personal protective equip-
The screw compressor packages are tested and ment must be worn.
accepted at the works. By the time these screw – Suitable tools or special tools must be used.
compressor packages are delivered to the cus-
tomer, the following work will have been carried – Check that all electrical work has been carried
out: out in accordance with the standards (e.g.protec-
tive earth, insulation, shielding, covers). If neces-
• Complete installation of the cooling system and sary, an earth connection must be provided.
in particular:
– Pipes and pipe sections must be secured to
– cleaning and drying the refrigerant and oil ensure sufficient mechanical strength. The pipes
circuits and equipment of the screw compressor pack-
– Leak test with air age must not be entered.
– Evacuation of the refrigerant circuit and filling – Operating media (nitrogen, oil, refrigerant) can
with protective gas (nitrogen) to a pressure escape. Preventive measures must be taken to
of 0.3 to 0.5 bar (above atmospheric) collect and dispose of them in an environmen-
tally responsible manner (e.g.using an oil pan).
• Electrical wiring and testing of the wiring
Personal breathing protection must be kept
• Factory setting for the parameters on the control ready in the event of a refrigerant leak. The
safety data sheets of the oil and refrigerant used
• Factory setting of the safety and monitoring devi-
must be read prior to commencing start-up work.
ces
Familiarise yourself with the evacuation plan of
• Works trial runs (at the request of the client) the installation location.
The screw compressor package has been designed 8.5 Start-up procedure
for plug-in and reliable automatic operation.
All connections must be carried out according to the The following procedures should be completed in the
current installation regulations. sequence in which they are described:
Connections to the screw compressor package must
be flexible and free of loads.
8.5.1 Checking the electrical connec-
Hint! tion
Dimensioning of the inlet pipe cross-
Danger!
sections must be according to DIN
VDE 100 Part 520. Contact with live components is pro-
hibited.
Before starting work, make sure that all parts to be
connected are de-energised, e.g. by removing the Check that all electrical work has been carried out in
main fuse in all phases or installing a jumper wire. accordance with the standards (e.g.protective earth,
The insulation resistance of the electrical tools and insulation, shielding, covers). If necessary, an earth
fixtures and wiring is to be checked. The connection connection must be provided.
may only be undertaken if this value lies in the allow-
able range.
Connections and almost all external connections are 8.5.2 Leak test
pre-wired at the factory.
Hint!
Warning!
See type plate for permissible operat-
Produce the earth connection accord- ing pressure.
ing to the designation in the general
assembly drawing. See chapter "Des- The necessary safety precautions should be taken
ignation of the earth connection". before performing the leak test.
An approx. 3-hour pressure drop test with dry nitro-
The electrical consumers and sensor must be con- gen is used for the test. Test pressure: 7 bar
nected according to the circuit diagram. All electrical
A pressure drop of 2% is allowed during the 3 hours.
connections must be made according to the circuit
Fluctuations in the ambient temperature must be
diagram, e.g.
taken into account.
– Compressor drive motor
Caution!
Checking devices which could be
damaged by the specified test pres-
sure must be removed or blocked
before the leak test is performed.
Caution!
The valves must be in operating position prior to the start-up of the package / chiller. Trouble-
free operation is only possible in this manner!
Caution!
An oil pressure being set too high or too low may result in serious compressor damage or
even the total breakdown of the compressor after just a short period of operation!
controlled self-sufficient
– ½” connections
– with cap
– Connection Rp ¼”
– For pressure gauge and pressure transmitter
When charging with oil for the first time, oil must also
be charged via the service valve (135) too. To this
8.5.5 Oil charge end, the stop valve (065) must then be closed.
Caution! Caution!
Check the oil grade to be charged! See Due to the use of selected compo-
contract/project or recommendation of nents, the refrigerating machine oils
GEA Refrigeration Germany GmbH. A tend to absorb more moisture. There-
comprehensive overview of the allowa- fore, when charging a compressor the
ble oil types is provided in "Technical oil should be allowed to come into
information on lubricating oils". This contact with air for a short time only.
technical information is part of the The contents of an opened drum have
product documentation. to be used up within one working day,
For severely hygroscopic oils, the oil provided the drum is properly closed
container must be placed under a pro- between charging.
tective atmosphere.
While the compressor is not running and the oil has 12. Set the motor current limitation acc. to nominal
not yet reached the operating temperature, the differ- motor data. See parameter list!
ential pressure can be slightly higher than the indica-
ted value.
The differential pressure can be changed by rotating 8.5.7 Adjustment of oil pressure
the spindle on the oil pressure control valve. (The dif-
Danger!
ferential pressure is increased by turning it inwards
and vice versa). The oil pressure being set too high or
too low may result in serious compres-
sor damage or even total breakdown
8.5.6 Checking the fault monitoring of the compressor after even a short
period of operation!
1. Disconnect the incoming feeder of the compres-
sor drive motor from the mains supply when Before the compressor drive motor and therefore the
checking the safety device (e.g. remove LV/HBC unit can be started, the oil pressure must be set cor-
fuse links). rectly by adjusting the oil pressure regulating valve
(075).
2. Apply voltage to the control device.
For adjustment solely the oil pump must be started.
3. Check the built-in pressure transducer and For units with the control GEA Omni, digital output
resistance thermometer for correct wiring. must be forced for this.
To do so, loosen the relevant contacts. The mes- The set value of the oil differential pressure should
sage "Broken wire <sensor XXX>" appears on be taken from the P+I flow chart of the specific
the display of the control. Check that the display project.
is correct after the contact has been re-estab-
Oil differential pressure = oil pressure item (110)
lished.
- discharge pressure item (105)
Further information can be found in the con-
The differential pressure can be changed by rotating
troller manual.
the spindle on the oil pressure regulating valve (the
4. Check limit values. differential pressure is increased by turning it
Limit value = see parameter list inwards and vice versa). To do so, the seal on the oil
pressure control valve (075) must be removed.
5. Switch on the screw compressor package/chiller
In comparison to normal operation conditions, the oil
from the controller.
differential pressure can be slightly higher if only the
6. "Oil circuit monitoring failure” must be indicated oil pump is operated or if the operating temperature
after a starting delay time of 20 sec. is not reached yet (with the valve open to the same
degree).
7. Reconnect the oil pump motor to the mains sup-
ply. In this case, the oil differential pressure should be
readjusted (according to the value in the P+I flow
8. Check the excitation of the solenoid valves of the chart) after start of the unit and reaching of the oper-
adjusting device for capacity control in the Mini- ation temperature.
mum direction.
8.5.8 Checking the direction of rotation – After checking the direction of rotation of the
of the drive motor drive motor, the coupling may be connected with
the motor.
Warning!
The coupling must not yet connect the
motor and compressor! 8.5.9 Mounting the coupling
– Secure the electric switchgear so as to prevent 1. The electric switchgear is secured to prevent it
the compressor drive motor from being switched from being switched on accidentally.
on accidentally.
2. Mount the coupling while observing the instruc-
– With the control slide in the MIN or MAX position, tions of the separate documentation.
it should be possible to rotate the compressor
3. The values for radial and angular deviations
shaft easily and smoothly by hand. When check-
given in the coupling documentation must be
ing the direction of rotation of the compressor
checked and corrected if necessary. The axis
driving motor pay attention to the conditions for
distance between the compressor drive motor
switching the compressor on.
and the compressor must be checked.
4. The real values have to record at data sheet of
coupling documentation. Please send back a
copy of the filled data sheet to:
GEA Refrigeration Germany GmbH
Holzhauser Straße 165
13509 Berlin
Fax: +49 (0)30 - 43 592 759
Caution!
Observe the maintenance instruction!
fig.44: Motor direction of rotation
Regrease the coupling at the prescri-
A Compressor bed intervals if scheduled in the main-
B Motor tenance instruction for the coupling!
3. Select manual operating mode. The water volume must be regulated so that the
cooling water volume corresponds to the project
4. Turn on SCP. value. The inlet and outlet temperatures must be
checked. The oil temperature adjusts automatically
via the 3-way valve.
8.5.12 Checking the adjustment of the
control slide Checking the oil cooling with refrigerant-cooled
oil cooler
1. SCP is running. No regulating or checking required.
2. Select manual operating mode.
3. The maximum end position (100%) must be
8.5.15 Adjusting the amount of injection
reached and signalled when the "Increase
power" button is pressed. oil and the oil temperature
4. The minimum end position (0%) must be
reached and signalled when the "Decrease
power" button is pressed. 8.5.15.1 Screw compressor packages
without refrigerant injection
5. Vent the adjusting device by moving the control
slide backwards and forwards about ten times. The amount of injection oil and the oil temperature
directly influence the discharge temperature of the
compressor. The amount of injection oil is adjusted
8.5.13 Checking the control slide adjust- under operating conditions through the injection oil
ment times control valve.
The throttle valves of the solenoid valves are adjus- NH3/HP t ≥ toil + 20K 30K 95°C
ted in the factory in such a manner that they ensure
an optimal adjustment time of the control slide of
NH3/LP t ≥ toil approx. 45 ... 60°C 80°C
between 30 and 60 seconds.
While running at operating temperature and pressure
Freon/HD t ≥ toil + 15K 80°C
conditions, determine the adjustment times needed
when the control slide is continually moved from the
maximum end position to the minimum end position R22/LP t ≥ 45 ... 60°C 80°C
and back. For the automatic system to run smoothly,
the adjustment times in either direction must be
approximately the same.
8.5.15.2 Compressor units with refriger-
The adjustment time can be adjusted with the help of
throttle valves DS5 and DS6. ant injection
2 Manual + Auto Manual Start/Stop via TP and full automatic local Manual Auto
capacity control
3 Auto + Auto Full automatic start/stop and local capacity control Auto Auto
4 Remote Start/stop and capacity demand via digital contacts External External
+ HW (cont) (hardware) from a remote master controller. The GSC continuous
TP derives from the continuous +/- signals the pulses
for capacity (indirect).
5 Remote Start/stop and capacity demand via digital contacts External External
+ HW (pulse) (hardware) from a remote master controller. The mas- pulses
ter also generates the +/- signals as pulses for control-
ling the slide capacity directly.
6 Remote Start/Stop from a remote master controller via digital External Local
+ HW (loc. contacts (hardware). The GSC TP controls the output + setpoint Setpoint
SW) depending on a local setpoint (TP) and from this set- deviation
point also automatically switches the product ON/OFF.
7 Remote Start/Stop from a remote master controller via digital External Remote
+ HW (ext. contacts (hardware). The GSC TP controls the output + setpoint Setpoint
SW) depending on an external setpoint (analog input) and deviation
from this setpoint also automatically switches the
product ON/OFF.
8 Remote Start/stop and capacity demand via network from a Network Network
+ Net (cont) remote master controller. The GSC TP derives from continuous
the continuous +/- signals the pulses for controlling the
capacity (indirect).
9 Remote Start/stop and capacity demand via network from a Network Network
+ Net (pulse) remote master controller. The master also generates pulses
the +/- signals as pulses for controlling the capacity
directly.
10 Remote Start/stop from a central master controller via a bus Network Local
+ Bus (loc. signal. The GSC TP controls the output depending on + setpoint Setpoint
SW) a local setpoint (TP) and from this setpoint also auto- deviation
matically switches the product ON/OFF.
11 Remote Start/stop from a central master controller via a bus Network Network
+ Bus (net. signal. The GSC TP controls the output depending on + setpoint Setpoint
SW) an external setpoint sent externally via the network deviation
and from this setpoint also automatically switches the
product ON/OFF.
9.2.2 Setting of setpoint and limiting GEA Omni performs the following functions as
values as well as safety devices standard:
Table of malfunctions
The suction pressure is too low, Slow loss of refrigerant through Check the entire system for leaks.
performance is reduced and the leaks in the refrigerant circuit. Eliminate leakage, replenish refrig-
system overheats. erant if necessary.
The suction pressure increases, the The compressor/s are sucking in Check the filling of the system,
compressor(s) frost up to impermis- wet steam or liquid when started drain any refrigerant, repair safety
sibly high level or make noises that up. The safety device to prevent a device. Check for superheating.
suggests fluid (refrigerant) in the too-high liquid level is not respond-
compressor. ing.
The condensation pressure is too There is air or other non-condensa- Vent the refrigerant circuit.
high. ble gases in the refrigerant circuit.
The compressor(s) will not start-up The electrical circuit is interrupted Turn on the power, check safety
after switching on or it shuts down by a unit in the safety chain. devices and replace or correctly
immediately after starting again. adjust if necessary.
The compressors do not adapt to The capacity control device is mal- Check the oil circuit. The compres-
the required capacity. functioning due to disturbances in sors should only be repaired by
the oil circuit or mechanical influen- experts. Check the position detec-
ces. tor of the compressor control slide.
The compressors are shut off very The condensation pressure is too See above.
often by the maximum pressure high.
governor.
The maximum pressure governor is Remove the maximum pressure
defective or set wrongly. governor, repair it, set it correctly or
replace it.
The compressors are shut off very The suction pressure is too low. Open all valves on the suction side
often by the minimum pressure of the compressors.
governor.
Table of malfunctions
The heat transfer capacity of the Check the evaporator for elevated
evaporator decreases. oil concentration, drain oil if neces-
sary.
When operting, the package/chiller The compressor(s) or the drive Inform the GEA Refrigeration Ger-
is louder than permitted. motor(s) is/are defective. many GmbH customer service
10.3 Maintenance
10.3.2 Repair work New inspection and approval is required after pres-
sure vessels that are subject to approval have been
Modifications and repair work may only be carried
repaired or changed. Welding may only be carried
out by qualified persons or persons with suitable
out by approved welders with a valid welder’s card.
training with the manufacturer's consent and must
strictly comply with the rules set out in the mainte-
nance instruction for the components concerned.
10.3.3 Maintenance intervals
Hint!
Caution!
The following maintenance notes must
be observed: The maintenance intervals in accord-
ance with maintenance checklist must
Only spare parts made by the original component be observed.
manufacturer may be used for repairs and for replac-
ing wearing parts. These are available from the The maintenance checklist is part of the product doc-
spare parts department. umentation. The attached maintenance checklist
contains all the maintenance instructions and certifi-
cations for the first 10 years of performance of the
10.3.2.1 Repair information screw compressor package. The maintenance certifi-
cates are completed and signed as part of the
Important features of the technology and production inspection and maintenance by authorized fitters as
process must be taken into account when repairing evidence of the work done.
the plant: During the warranty period, these validated mainte-
– complete sealing of all devices and pipes. nance certificates also serve as a precondition for
any warranty claim put to GEA Refrigeration Ger-
– Dryness and cleanliness of the entire plant. many GmbH.
– Use of welding methods causing only a minimum
amount of dirt to collect in the plant.
10.3.4 Maintenance work
– Pipes bent on a pipe-bending machine only
using refrigerating oil. Hint!
– If repairing the piping system from your own The documentation for the main com-
stocks, we recommend that you use a pipe with ponents is a part of the product docu-
NBK surface quality (annealed and descaled, mentation. This contains important
mechanically or chemically descaled after information to be considered before
annealing). beginning the maintenance work.
– When carrying out repairs to piping systems,
care should be taken to maintain the original pip-
ing routes. 10.3.4.1 Maintenance of the screw
– Only pipes of sufficient material quality, which compressor
are certified according to DIN 10216-2 should be
used. The following maintenance work must be performed
on the screw compressor at regular intervals (see
maintenance checklist):
10.3.2.2 Repairs of pressure vessels – Measure axial play of bearings,
subject to approval inspection – Check shaft seal,
Hint! – Check primary slide movement,
The responsible monitoring body – Check the adjustment of the position sensor.
(e.g.TÜV) must be notified in advance. After 50,000running hours or in the 10th running
year, a general check of the screw compressor is
provided by the manufacturer. Contact Customer
Service in this regard.
10.3.4.3.2 Cleaning the filter element – if the oil becomes unacceptably contaminated-
The metal-gauze element used in the filter can be due to a major accident (e.g. water penetration
cleaned and reused several times before it has to be into the refrigerant circuit).
changed. The degree to which oil in refrigeration plants has
aged must be checked by analysis and in compari-
Manual cleaning son of the data with those of fresh oil. Oil ageing can
Immerse the soiled metal-gauze element in a clean, also be judged from the darkening of the oil colour
grease-dissolving liquid, then blow it through with and the deposits found in the oil filters. If the degree
compressed air from the outside inwards. Here it is of ageing cannot be assessed reliably by laboratory
important to place a cylindrical part – possibly wrap- analysis and the results of visual examination, it is
ped in corrugated cardboard – inside the element to advisable to change the oil at the following intervals
catch the dirt particles. (see maintenance checklist).
The assessment of the condition of the refrigerating
Caution!
machine oil by means of a general visual inspection
Never use wire brushes for cleaning. (contamination) or laboratory analysis must be car-
ried out:
Hint! – after 5000 operating hours:
To avoid fatigue failures of the metal or
gauze, strainer elements should be
replaced with new, original filter ele- – at the end of one year's operation
ments after being cleaned 4 – 5 times. or
– after remedying major damage.
or
10.3.4.4 Oil draining, oil filling, oil – if the oil is dark coloured or very cloudy.
change
Warning!
Oil change intervals 10.3.4.4.3 Changing the oil
Oil change with ammonia as the refrig- 1. The screw compressor package/chiller must be
erant after every 5,000operating hours run for at least half an hour to reach its operating
or after 1 year at the latest. temperature before the oil can be changed.
Oil change with freon as the refrig-
2. First shut down the screw compressor package/
erant after 10,000operating hours or
chiller as described in the operating instructions.
after 2 years at the latest.
3. Open the stop valve in the bypass line around 10.3.4.4.4 Used oil
the check valve on the suction side and the stop Refrigeration machine oil drained from the circuit is
valve on the suction side to equalise the pres- no longer suitable for use in refrigeration plants. It
sure between the screw compressor package/ has to be stored or transported in appropriately label-
chiller and suction line. If screw compressor led containers in accordance with the legal provi-
packages operated in parallel or other separate sions. The operator is responsible for its proper dis-
chillers are present, the refrigerant should pref- posal.
erably be drawn off at a pressure which is
approx. 1 to3 bar above atmospheric pressure.
Then re-close the stop valves bypass and the
10.3.4.4.5 Draining the oil
suction-side stop valve. Otherwise the pressure
can be reduced by opening the vent valve on the It may be necessary to drain the oil:
suction filter and then disposing of the refrigerant
– to inspect or repair the compressor
as specified by law.
and
4. Then drain the used oil through the oil
draining/oil charging valves and dispose of it – if there is too much oil in the circuit.
(Caution! hazardous waste!). Once this has The oil must be drained in accordance with points 1
been done, re-close the valve and if possible to 6 of the chapter entitled "Carrying out oil change".
continue to draw off the refrigerant with a com- The oil must be drained through the filling hose and
pressor connected in parallel or a disposal into a container suitable for waste oil.
device until atmospheric pressure is almost
reached.
5. Otherwise depressurise the screw compressor 10.3.4.4.6 Checking the oil level
package/chiller by opening the vent valve on the The oil level is checked visually in the sight glass of
suction filter, taking into account the safety rules the oil separator.
for refrigeration systems.
The filling level should be 1/2 to 3/4 of the height of
6. Open the drain plugs and valves on the oil the sight glass.
cooler, oil separator and OMC block to drain any If the filling level is too low, replenish the oil. The fill-
residual oil. Then re-close the drain plugs and ing amount must be documented in an appropriate
valves. log.
7. Replace the filter element of the oil filter; replace
and/or clean the filter element of the suction filter
combination. 10.3.4.4.7 Charging with oil, topping
8. Evacuate the screw compressor package/chiller up with oil
using a vacuum pump. See chapter entitled "Start-up, charging with oil".
Warning! Hint!
Shut off the oil pump! For permissible types of oil, please
refer to the technical information enti-
9. Pressurise the screw compressor package/chiller tled "Lubricating oils".
with a slight overpressure via the stop valve
Oil removed from the compressor
bypass check valve on the pressure side.
must not be re-used. Always use fresh
10. Then check all components for leakages. On oil from sealed containers! Do not mix
successful completion, perform a complete pres- with other types of oil.
sure compensation with the discharge line fol-
lowed by a repeated leakage test of the screw
compressor package/chiller. The oil charge oil
and start-up of the screw compressor package/
chiller must be accomplished in accordance with
the operating instructions.
10.3.4.5 Oil pump maintenance 5. Dismantle the check valve installed in the oil
Assuming correct installation in accordance with the separator. This step is omitted if a check valve
conditions of use and correct fitting, gear pumps which can be shut off is used on the pressure
have the design prerequisites for long and fault-free side.
operation. 6. Remove the securing wire [3].
The gear pumps require a minimum of maintenance 7. Loosen the hexagon head screws/tie rod [2]
which is, however, indispensable for fault-free opera-
used to attach the oil fine separation cartridges.
tion since experience has shown that a high percent-
age of the faults and damage which occur are attrib- 8. Remove the fine oil separation cartridge [1].
utable to the ingress of dirt and inadequate mainte- 9. Install the new fine oil separation cartridge in
nance. reverse order.
The maintenance intervals have been defined in the
maintenance checklist (part of the product documen- Warning!
tation). Securing wire [3] must be re-attached!
An oil leakage of up to one drop/minute is required Max. tightening torque = 15 Nm
for the lubrication of the shaft seal and is permissi-
ble.
The shaft seal is maintenance-free. If the oil leakage
is too great, replace it according to the oil pump doc-
umentation.
Hint!
The regular examination of all operat-
ing data, such as pressure, tempera-
ture, power consumption, degree of fil-
ter fouling, etc., helps in the early
detection of potential failure!
Unless otherwise stated by warning signs, the tight- Lower refrigerant levels in the containers are due to
ening torque is dependent on the size and strength loss of refrigerant as a result of leaks. For this rea-
of the screw fastening. son, all pipes, connections and valve glands should
be checked regularly, especially in the initial period
of assembly.
10.3.4.8 Coupling maintenance The most striking feature if there is a leak in the filled
refrigerant circuit is the smell of refrigerant. The
1. Switch the screw compressor package/ chiller
odour threshold of ammonia in the air is approx. 5
off.
ppm and thus well below the permitted MAK values.
2. Secure the electric motor against accidentally Methods of leak detection:
being switched on.
– Regular visual inspections.
3. Visually inspect the disk packs.
– Smudges/dirt stains indicate leaking
4. Check the tightening torques of the fit screws. refrigerant/oil mixture.
5. Check the alignment of the electric motor and – Leak tests with nitrogen with a max. of 0.5%
correct it according to the steel lamination cou- ammonia by volume, an elapsed time of more
pling documentation, if required. than 3 hours and application of a foaming agent
6. Re-grease the coupling (if provided for in the to all the joints with a brush. Oil-filled compres-
maintenance instructions for the coupling). sors or circuit sections must only be charged
with nitrogen – not air – to generate pressure.
– Use of an NH3 leak detector.
10.3.4.9 Checking the function of check
– Ammonia produces the following colours when
valves
leak tests are performed:
In order for a check valve to be effective, it is impor- – Red litmus paper turns blue,
tant to perform function checks at regular intervals.
– Blotting paper impregnated with phenolph-
An inspection is carried out by checking the noise
thalein turns red (moisten).
behaviour of the valves during operation. After
switching off the screw compressor package, mal- Caution!
function on the suction side is indicated by prolonged
turning back of the compressor. Malfunction on the Due to the danger of explosion, oxy-
pressure side leads to an increase of the standstill gen must never be used to build up
pressure in the package to the pressure level of the the pressure!
system pressure side. Generate a test pressure in the refrigerant circuit that
meets the intended operating pressure for the leak
tightness test to determine leaks on the refrigerant
10.3.4.10 Searching for leaks on the side, e.g. in the case of escaped inert gas or refriger-
refrigerant side / leak test ant. When system parts are individually tested, the
maximum operating pressure indicated on the
The absence of leaks is a precondition for perfect
respective system part for the corresponding pres-
functioning of the compressor unit/chiller unit. Leak-
sure chamber must not be exceeded. The use of
ing parts or connecting elements will lead to the loss
foaming agents gives the best results at test pres-
of refrigerant and oil as well as the penetration of air
sures < 5 bar.
and moisture into the low pressure side. The site of
the leak must therefore be located and remedied if If leaks are determined, these must be sealed imme-
there is: diately. Release the test pressure before beginning
repair! Evacuate the system after repairs are com-
– Loss of the inert gas charge (delivery state), plete and after rechecking for leaks.
– Loss of the entire refrigerant charge
or
– underfilling.
10.3.4.11 Venting the refrigerant circuit 10.3.4.14 Checking the solenoid valves
for capacity control
When air penetrates the refrigerant circuit, this
makes itself felt in a fall-off in performance and the See the following sections in the start-up chapter:
manometer on the discharge side of the compressor
indicates a higher pressure compared to the conden- • "Checking the control slide adjustment"
sation temperature. Any leaks must be remedied. In • "Checking the control slide adjustment times"
extreme cases, air in the circuit may interrupt the
flow of refrigerant and cause the oil cooling to fail.
There are several ways of venting the system. The 10.3.4.15 Checking the oil heater
air or the NH3-air mixture is vented via the vent
Check the electrical function using a clamp-on
valves of the condenser or the suction filter in water
ammeter.
filled vessels when the package is at a standstill.
Check the outer temperature of the oil separator and
If air is in the mixture, the venting ammonia is absor-
compare with the temperature of the machine room
bed from water.
(while the screw compressor package is at a stand-
Hint! still).
Continuous venting using a Grasso
purger is recommended.
10.3.4.16 Maintenance of the compres-
sor drive motor
10.3.4.12 Refrigerant evacuation Hint!
The compressor drive motor must be
Hint!
maintained in accordance with the
Shut the oil pump during evacuation! "Motor documentation".
The purpose of evacuating the system is to remove Maintenance of the compressor drive motor includes
air and moisture from the refrigerant circuit. the following activities:
Evacuation is required: – Lubrication of the motor
– after intervention in the refrigerant circuit and Lubrication intervals and quantities according to
elimination of leaks, the "Motor documentation" or "Type plate".
Parameter to be Every 24
Weekly Monthly Remark
checked to 72 hrs
Parameter to be Every 24
Weekly Monthly Remark
checked to 72 hrs
10.3.4.22 Insulation
Check the insulation (if present) on components,
containers and piping for damage.
Damaged insulation must be replaced. The insula-
tion strength must be selected according to the tem-
perature and humidity at the place of installation.
Details on the insulation can be found in the P+I dia-
gram.
Caution!
No screw connections must be used
under the insulation if the piping is
insulated. The pipes must be welded.
11 DECOMMISSIONING
3. Switch off the main switch of the three-phase
electric system.
11.1 Shut-down in the event of danger-
ous situations 4. If necessary, shut off the secondary refrigerant,
heating agent or the cooling water supply.
The safety equipment of the screw compressor pack-
age complies with EN 378. 5. Ensure that the venting slots of the electric
motors are covered under all circumstances!
By means of automatic monitoring of the individual
operating parameters, the control unit detects haz- ® Shut-down has been carried out
ardous situations in good time and automatically
switches off the screw compressor package.
The cause of the fault is displayed on the control unit 11.3 Standstill for a period >48 hours
and can then be corrected.
Hint!
Among other things, the concept of the screw com-
pressor packages is based onlow maintenance The obligation to label the plant as
refrigerant circuits that are as well sealed as possi- "Plant not in operation" must be
ble. However, residual risks remain, especially due observed!
to possible leaks or escaping refrigerant or rotating
drive parts. If the screw compressor package is shut down for a
period >48 hours, the following activities must be
Hint! performed:
The EMERGENCY STOP switch in the 1. Switch off the compressor in accordance with the
switching cabinet is used to quickly operating instructions for the electrical switch-
switch off the chiller whenever neces- gear.
sary.
2. Switch off all ancillary drives.
Leaking refrigerant can be detected with a gas 3. Switch off the main switch of the three-phase
detector (not included in the scope of delivery). This electric system.
detector can be integrated in the automatic safety
4. Close the stop valve (or combined stop/check
chain.
valves) on the suction side and the pressure
Please consult the safety regulations in this docu- side.
mentation for information about what to do in the
case of leaking refrigerant. 5. Close the stop valves (or shuttable check valves)
in the suction line of the economiser.
6. Shut off the secondary refrigerant, heating agent
11.2 Standstill for a period <48 hours or cooling water.
12 DECOMMISSIONING, DISPOSAL
Preparatory measures – National regulations (e.g. EN 378-4, Appendix A)
Hint! must be observed for the reclamation and dis-
posal of operating media (oil).
The information in the chapter
"Decommissioning" must be – No unauthorised persons must be within the
observed. installation area of the plant during decommis-
sioning, as they could come into contact with
refrigerant.
Hint!
– All components of the plant which are not to be
Care must be taken during disposal re-used, as well as refrigerant and operating
and devaluation that the various mate- media, must be stored in suitable separate con-
rials are separated and taken for recy- tainers. They must be treated as waste and dis-
cling. Disposal of component remains posed of safely.
and components in the domestic ref-
uge or on refuse tips is not permitted. Hint!
The legal regulations applicable to the Re-use of operating media is not pos-
place of installation regarding the dis- sible!
posal of electrical equipment must be
taken into account.
Dismantled components must be dis-
posed of correctly and according to
legal requirements.