Академический Документы
Профессиональный Документы
Культура Документы
H 22
DRIESCHER
Indoor -
H 22
Switch-Disconnector and
switch-fuse combination H 22
• Three-pole
• Rated voltage
12 kV, 24 kV, 36 kV and 38,5 kV
• Rated current
630 A and 1250 A
H 22
H 22
ELEKTROTECHNISCHE WERKE
FRITZ DRIESCHER & SÖHNE GMBH
D-85366 MOOSBURG • TEL. +49 87 61 6 81-0 • FAX +49 87 61 68 11 37
http://www.driescher.com infoservice@driescher.de
722
DRIESCHER - Indoor Switch-Disconnector and
Switch-fuse combination H 22
acc. to EN 60265-1and EN 62271-105
content:
Types of Switch-disconnectors
For many years DRIESCHER - indoor load-break • Type H 22 EK - without trip-free release
switches have guaranteed an excellent position in
• Type H 22 EA - with trip-free release*
switchgear engineering. These switch-disconnectors
master the daily loads exerted under normal swit- • Type H 22 SEA - with trip-free release*, as well as
ching duty - for interrupting ring feeders, disconnec- cross rails attached below, mounted insulators and HV
ting network transformers and such - with very high HBC fuse holders, for all-pole disconnection of the
operating frequencies and a minimum amount of switch when a fuse operates.
maintance. The devices are fitted with an energy storage
These load-break switches are distiguished by sim- mechanism for quick-make and quick-break
ple design, absolute reliability in operation and easy operation.
actuation. In switch-fuse combination (Type SEA) only
HV HBC fuses with pin release and a tripping
impact force of min. 80 N are to be used (refer
* see to page 3, energy storage mechanism also to 791).
Operating conditions
The use of switchgears under normal operating con-
ditions is specified in the EN 62271-1 as follows:
• The maximum ambient temperature is 40 °C, the • The following conditions apply with regard to humidity:
average value over a period of 24 h is max. 35 °C. - average value of relative air moisture measured
The minimum ambient temperature is –5 °C. For our over 24 h is max. 95 %,
indoor switches the class "Minus 5 indoors” is speci- - average value of water vapour pressure over 24 h
fied. is max. 2.2 kPa;
• Solar radiation has no significant impact. - average value of the relative air moisture over a
• The altitude at the place of installation is max. 1000 m period of one month is max. 90%
above sea level. - average value of the water vapour pressure over
• The ambient air is to have no significant contamina- one month is max. 1.8 kPa;
tion through dust, smoke, corrosive and/or flamma-
ble gasses, fumes or salts.
To each switchgear an instruction for transportation, mounting and putting into service is inclosed.
This instruction which we certainly would send you in advance, has to be absolutely obeyed.
2
722
DRIESCHER - Indoor Switch-Disconnector H 22
Main advantages
• Absolute operational reliability • Easy operation
• Isolating distance visible after load disconnection • High operating frequency with minimum amount of
• Convenient dimensions maintenance
Arc extinction
Upon breaking the main contacts 1 open first and the the arc by lateral spring pressure.
current is briefly taken over by the parallel connected At low currents the arc is extinguished by deionising
lagging pins 2 . During this breaking motion opening action due to the cooling effect of the walls.
springs 3 acting on the lagging pin are tensioned. On Arc extinction is achieved in the higher current range
reaching a stop the lagging pin leaves the holding by the arc extinguishing gasses produced in the
contact 4 . The arc occurring between the arcing tip pressure chamber flowing out of the pressure cham-
of the holding contact and the tungsten tip of the lag- ber into the expansion chamber. Due to this rational
ging pin is extinguished in the arcing chamber 5 . combination of several extinguishing principles the
The arcing chamber itself is closed. entire current range of the load-break switch is effec-
It is a device with four sections and has a pressure tively covered in all cases.
chamber 6 and an expansion chamber 7 . Since neither an arc extinguishing liquid nor com-
Arranged in the pressure chamber are two extin- pressed air are required, the arcing chambers are
guishing plates 8 which are forced into the path of maintenance free.
5 2
Upper connection 7
6
Lower connection
8
4
ON OFF
3
722
DRIESCHER - Indoor Switch-Disconnector H 22
Technical Data
EN 60265-1
Rated voltage Ur kV 12 24 36 38,5
Rated frequency fr Hz 50 50 50 50
Rated-current Ir A 630 1250 630 1250 630 1250 630
Rated-peak withstand current Ip kA 501) 751) 501) 751) 321) 751) 321)
Rated-short-time current Ik kA 201) 301) 201) 301) 12,51) 301) 12,51)
Rated-making current Ima kA 50 40 35 30 20 20 20
Rated-breaking current I1 A 630 1250 630 1250 630 1250 630
Rated-loop breaking current I2a A 630 1250 630 1250 630 1250 630
Rated-transformer off-load breaking current I3 A 120 120 50 40 40
Rated-cable charging breaking current I4a A 90 90 35 20 20
Rated-earth fault off-load breaking current I6a A 300 300 200 100 100
Rated-cable charging breaking current
below earth fault conditions I6b A 90 90 35 20 20
EN 60694
Rated voltage Ur kV 12 24 36 38,5
Rated-impulse withstand voltage 1,2/50 µs Uw
Phase - Earth kV 75 125 170 180
Phase - Phase kV 75 125 170 180
Open Gap kV 85 145 195 210
4
722
DRIESCHER - Indoor Switch-Disconnector H 22
x y
65
p p
ø30
1
t1
f
b
a
ø15
w
ø30
77 M12
u
M12x401) M12x401)
2
c
65 d
1) hexagonal screw with two span washers and nut
5
722
DRIESCHER - Indoor Switch-Disconnector H 22
x1 y
p p
140
f
ø30
b
a
w
15
t
77 M12
u
M12x401)
2
c
1) hexagonal screw with two span washers and nut
d
6
722
DRIESCHER - Indoor Switch-Disconnector H 22
Version
24 kV, p = 275
(f=993)
7
DRIESCHER - Indoor Switch-Disconnector H 22
Dimensions, weights , diagrams and descriptions in the list are non-binding. Subject to change without notice.
ELEKTROTECHNISCHE WERKE
FRITZ DRIESCHER & SÖHNE GMBH
D-85366 MOOSBURG • TEL. +49 87 61 6 81-0 • FAX +49 87 61 68 11 37
http://www.driescher.com infoservice@driescher.de