CAUSE:
EFFECT:
CAUSE:
EFFECT:
DCS Hand Switch added in the logic to enable operator to open propylene valves during start-up (no
flow) and after switching of seal flush to nitrogen. In case if seal flush switched from propylene to
nitrogen during normal operation the operator will have possibility to open propylene valves and after
the C3 flow is established and becomes more than low HP nitrogen valve can be closed by operator.
IZ – 39016 REACTOR SHUTDOWN (RSD)
CAUSE:
1) RSD Logic for Reactor Agitator speed low low trip SSLL-3904A/B/C (2,5 rpm) was modified so, that
the interlock becomes active 2 minutes after speed low (2.8 rpm) is reached in order to enable
reactor start-up when speed is less than 2.5 rpm.
2) Configuration of analog inputs of TT-3901-05 was changed: transmitter faults will cause PV to be
100% (which would cause RSD). Also transmitter faults (2oo5) will additionally cause RSD.
3) RSD Logic for reactor trip on pressure Low Low PSLL-3901 was modified so, that the interlock
becomes active 2 minutes after Low Low Pressure is reached (12 kg/cm2 g) in order to enable
reactor start-up when the pressure is below LL. After RSD interlock remains 2 min (adjustable)
active, after which Reset 1,2,3 can be pressed.
EFFECT:
CAUSE:
EFFECT:
CAUSE: