Protection and Control IED

General catalog

©Copyright 2019 Toshiba Energy Systems & Solutions Corporation. All rights reserved.

- The information provided in this catalog is subject to change without


notice.
- The information provided in this catalog is accurate as of 30 March
2019.
- The information provided in this catalog is presented only as a guide
for the application of TOSHIBA products. No responsibility is
assumed by TOSHIBA for any infringements of patents or other
rights of third parties which may result from its use. No license is
granted by implication or otherwise under any patent or patent rights
of TOSHIBA or others.
- TOSHIBA products should not be embedded within downstream
Toshiba Energy Systems & Solutions Corporation products production and sale of which are prohibited, under any law
and regulation.
72-34, Horikawa-cho, Saiwai-ku, Kawasaki 212-8585, Japan - Toshiba does not take any responsibility for incidental damage
(including loss of business profit, business interruption, loss of
Tel +81-44-331-1462 Fax +81-44-548-9540 business information and other pecuniary damage) arising out of the
http://www.toshiba-relays.com use or misuse of TOSHIBA products.

Printed in Japan 6661 1903A0


Product Range
GR-200 Series is the next generation of protection and control devices from Features
Toshiba, designed to support a comprehensive range of functions for
transmission and distribution networks. This powerful and flexible platform
Intelligent Platform for Future Grid Applications
- Protection & Control for Transmission & Distribution Networks
will support all of your network protection and control requirements, while
- Basis for future systems and application development
its user-friendly HMI and the software support package, GR-TIEMS, will
facilitate your engineering experience. A range of I/O configurations, Universal platform with flexibility to meet future requirements
together with various communication ports and standard protocols ensure
Extensive Hardware Options & Flexible Adaptation
easy integration into both new and existing systems. GR-200 Series consists
- Comprehensive Range of Hardware Components
of the following model types for transmission and distribution network
- Main Processing/Computing Board with Enhanced Processor
protection and control: - Wide variety of Binary Input & Output combinations
- Standard LCD and touch type screens together with mimic option
- Plug-in Communication module
- Flexible hardware combinations to meet specific applications

IED configuration achieved using flexible/multiple hardware options

GBU200 Bay Control


Function-wise Implementation
GRZ200 Distance Protection - Library of Function blocks enables wide application for protection, control,
measurement and other functions
- Protection elements and schemes
GRL200 Line Differential Protection
- Control schemes
- Metering and Recording functions
GRT200 Transformer Protection
- Individual function blocks work independently
- Easy IED customisation to add/delete particular function blocks
GRB200 Busbar Protection
- Flexible implementation of new functions or to modify a specific function

GRD200 Multi-Function Protection & Control IED fully adaptable to user functional requirements

1 2
Example Application Function List

Bay control IED


Generator Function / device no. Description GBU200
Control Select-control with synchro-check ●
Interlock Interlock ●
AutoSEQ Automatic sequential control ●
Monitoring Monitoring ●
DCB Double command blocking ●
TAP TAP control ●
DCAI DC analog input measurement ○
DCAO DC analog output control ○
Synchrocheck between different network
SYNDIF ●
(e.g. between transmission line and generator plant)
GRT200 (*) MNOVR Manual override ○
GRT200
PWRQTY Power quality measurement (harmonics, sag and swell) ○
50/67,51/67 Non-directional / directional phase overcurrent protection ○
(*)
50N/67N,51N/67N Non-directional / directional earth fault protection ○
50N/67N,51N/67N (SEF) Non-directional / directional sensitive earth fault protection ○
GRB200 46/67 Non-Directional / directional negative phase sequence over-current protection ○
50BF Circuit breaker failure protection ○
37 Phase under-current protection ○
46BC Broken conductor protection ○
EHV/HV
49 Thermal overload protection ○
(*) GRT200
(*) (*) 59 Phase-Over-voltage protection ○
59N Earth fault over-voltage protection ○
GRZ200 GRZ200 GRT200 47 Negative phase sequence over-voltage protection ○
GBU200 27 Phase under-voltage protection ○
81 Frequency protection ○
GRL200 GRL200
ROCOF Rate of change of frequency (df/dt) ○
MV
51V Voltage controlled/restraint overcurrent ○
50SOTF Switch on to fault protection ○
GRL200 GRL200
21FL Fault locator ○
GBU200 ICD Inrush current detection function ○
GRZ200 GRZ200 To other networks 79 Auto-reclosing function ○
25 Sync check for auto-reclosing ○
TCS Trip circuit supervision ●
VTF VT Fail detection function ●
CTF CT Fail detection function ●

GBU200 / ● : Standard, ○ : Dependent upon hardware configuration and model configuration

GRD200

GBU200 /
To other networks GRD200

3 4
Function List Function List

Line protection and control Multi-Function Protection & Control


Function / device no. Description GRZ200 GRL200 Function / device no. Description GRD200
21/21N Distance protection (for phase and ground faults) ● ○ 50/67,51/67 Non-directional / directional phase overcurrent protection ●
85-21 Command protection for distance schemes ● ○ 50N/67N,51N/67N Non-directional / directional earth fault protection ●
85-67N Command protection for EF and DEF schemes ○ ○ 50N/67N,51N/67N (SEF) Non-directional / directional sensitive earth fault protection ○
87L Phase-segregated current differential protection ● 46/67 Non-Directional / directional negative phase sequence over-current protection ●
87N Zero phase current differential protection ● 50BF Circuit breaker failure protection ●
87R Remote differential trip ● 37 Phase under-current protection ●
DTT Direct transfer trip function ● 46BC Broken conductor protection ●
50/67,51/67 Non-directional / directional Phase over-current protection ● ● 49 Thermal overload protection ●
50N/67N,51N/67N Non-directional / directional Earth fault protection ● ● 59 Phase over-voltage protection ●
Non-Directional / directional 59N Earth fault over-voltage protection ●
46/67 ○ ○
Negative phase sequence over-current protection 27 Phase under-voltage protection ●
49 Thermal overload protection ● ● 81 Frequency protection ●
46BC Broken conductor protection ● ● ROCOF Rate of change of frequency (df/dt) ●
50BF Circuit breaker failure protection ● ● 51V Voltage controlled/restraint overcurrent ●
50SOTF Switch on to fault protection ● ● 21FL Fault locator ●
50STUB Stub protection ○ ○ ICD Inrush current detection function ●
59 Phase over-voltage protection ● ● CLP Cold load protection function ●
59N Earth fault over-voltage protection ○ ○ 79 Auto-reclosing function ●
27 Phase under-voltage protection ● ● 25 Sync check for auto-reclosing ●
81 Frequency protection ● ○ Control Control function ○
68 Power swing blocking ● ○ TCS Trip circuit supervision ●
56Z Out-of-step tripping by distance relay ● ○ VTF VT Fail detection function ○
56V Out-of-step tripping by voltage ● CTF CT Fail detection function ○
ICD Inrush current detection function ● ●
● : Standard, ○ : Dependent upon hardware configuration and model configuration
CLP Cold load protection function ○ ○
FL Fault locator ● ●
79 Auto-reclosing function ● ●
25 Sync check for auto-reclosing ● ●
Control Control function ○ ○
TCS Trip circuit supervision ● ●
VTF VT Fail detection function ● ●
CTF CT Fail detection function ● ●
● : Standard, ○ : Dependent upon hardware configuration and model configuration

5 6
Function List Function List

Transformer protection and control Busbar protection


Function / device no. Description GRT200 Function / device no. Description GRB200
87T Transformer biased differential protection ● 87B Biased differential relay ●
87H High-set differential overcurrent ● 50/51 Non-directional phase overcurrent protection ○
64/87N Restricted Earth Fault Protection (REF) ○ 50N/51N Non-directional earth fault protection ○
50/51 Non-directional phase overcurrent protection ○ 50BF Circuit breaker failure protection (2 stage) ●
50N/51N Non-directional earth fault protection ○ EFP End fault protection ○
67/67N Directional phase overcurrent and earth fault protection ○ FS(27) Fail-safe function (Voltage check function) ○
46 Negative phase sequence overcurrent protection ● CTF CT Fail detection function ●
50BF Circuit breaker failure protection ● ● : Standard, ○ : Dependent upon hardware configuration and model configuration
49 Thermal overload protection ●
27 Phase under-voltage protection ○
59 Phase overvoltage protection ○
64 Ground detection protection ○
81 Frequency protection ○
24 Overexcitation ○
ICD Inrush current detection function (2f/3f/5f) ●
Control Control function ○
TCS Trip circuit supervision ●
VTF VT Fail detection function ○
● : Standard, ○ : Dependent upon hardware configuration and model configuration

7 8
GR-200 Series-Platform Hardware Communication Engineering Tool

GR-200 has been designed to meet the wide variation in ▶ Case size ▶ Data communication for IEC 61850 station bus, IEC 60870-5- The PC interface tool, GR-TIEMS enables users to access GR-
functionality demanded by the global P&C market whilst The GR-200 series IEDs are 6U in height and can be configured 103, DNP3 and Modbus® RTU 200 series IEDs from a local personal computer (PC) in order to
avoiding the need for end-users having to undertake complex from a selection of unit sizes in terms of width from 1/3 x 19”, ▶ Ethernet redundancy scheme protocols: RSTP, PRP and HSR view on-line data i.e. real-time status monitoring as well as to
configurations of functions not required in a particular application. 1/2 x 19”, 3/4 x 19” or 1/1 x 19”. ▶ Line differential and teleprotection communications interfaces view stored data, make settings changes, edit the LCD screen
Toshiba has introduced the following four design measures to include direct optical fiber, X.21, CCITT G703, IEEE Std. and configure sequential logic. The tool can also be used for
▶ CT/VT module
overcome the common problem of the user having to configure C37.94 logical node and signal mapping for substation automation
Various CT/VT modules can be selected in accordance with the
multiple unused functions: ▶ Local setting and testing facility using a front fascia mounted integration. The user can configure and parameterize the
requirements of the user application. A maximum of two modules
- Fully modularized hardware architecture USB port with software engineering tool GR-TIEMS IED to provide a customized solution to meet their specific
can be mounted in a case of 1/1 x 19” width.
- Flexible firmware platform enabling easy addition of functions requirements.
- Introduction of a new software management system ▶ Input and output modules
- New high performance Programmable Logic Controller Binary input and output modules, DC analog input and output General function
Hardware requirements vary depending upon operating modules are provided to enable flexible configuration based upon
conditions, application etc. and in particular with respect to binary user requirements. In addition to the typical protection and control applications found
inputs and outputs, analog inputs and communication ports. The ▶ Communication module within an IED the following additional functions have been provided
realization of an optimal hardware structure providing increased A maximum number of 5 communication modules can be in the GR-200 Series of IEDs.
modularization enables the provision of optimal hardware accommodated in a case. Typically, the ports can be used for ▶ Recording
configurations to support a particular functional requirement. communication within a Substation Automation System or for - Alarms and events (each with 1,024 records) can be recorded
GR-200 Series IEDs have a multiple microprocessor design. communication with a remote end protection IED. with 1ms resolution
The microprocessors perform software functions such as signal
▶ HMI function - The 8 most recent time-tagged fault records including pre-fault
processing, protection algorithms, scheme logic, output control
- Standard LCD or large touch type screen. and fault values for currents and voltages in text format
and management of the human machine interface. The GR-200
- 24 configurable tri-state LEDs selectable red/green/yellow - Disturbance record acquired using sampled data from all
Series IEDs comprise a number of printed circuit boards, typically
provided at the local human-machine interface analog inputs and binary signals selected
a CT/VT module, input/output modules, a communication module
as well as the microprocessor board. The printed circuit boards - 7 programmable function keys and direct control buttons for ▶ Time synchronization
have been standardized and can be utilized within any of the GR- open/close (O/I) and control authority (43R/L) Time synchronization can be achieved over the IEC 61850 station
200 Series IEDs thus providing a common platform. In addition to bus with SNTP (Simple Network Time Protocol) or by using the
the hardware platforms, software modules such as applications, GPS signal available via an IRIG-B port.
protection elements, and communication protocol packages have
▶ Setting groups
been standardized and are managed as functional blocks. The
8 settings groups are provided, allowing the user to set one
function blocks are available in a library such that modules that
group for normal conditions, while other groups may be set to
are required for a particular user application can be adopted using
cover alternative operating conditions.
the TOSHIBA IED Engineering & Monitoring Software. (GR-TIEMS)
▶ Simulation and test
Function Block Library Implemented Function The GR-200 series IED provides simulation and test functions to
ID.A80
Function Block ID.A80 79 Common
enable a check to be made of control functions without the need to
Function Block ID.A60 ID.A60
25 Binary Input
make hardwired connections. This facility is provided by the provision
Function Block ID.A10
Binary Output of a ‘virtual’ dummy circuit breaker in the IED. It is also possible to
Autoreclose [79] Recording test communication signals by forced signal status change. The
ID.530 Setting
50BF simulation and test facility is available in Test mode only.
Function Block ID.530 Signaling
ID.310 PLC
21N ▶ Test terminal
Function Block ID.300
ID.300
Function Block ID.100 21S GR-200 series IEDs are equipped with three signal monitoring
DIF_L Protection [87L] terminals on the front fascia panel for testing protection and
control characteristics. Using these ports, the user can conduct
Feature separation of fixed/common elements from variable testing from the front panel by assigning signals or logic without
application functions supports customization to meet specific the need to make hardwired connections at the rear of the IED or
user requests throughout the lifetime of the product. A within the protection and control panel.
standardized interface between common parts and application
functions assures the highest quality.

9 10
Remote Setting and Monitoring Technical Data

GR-TIEMS supports functions that allow the user to upload/download settings and to view and analyze fault and disturbance records HARDWARE
captured and stored in GR-200 series IEDs. Waveform data contained within the disturbance records can be displayed, edited, measured Analog Inputs
and analyzed in detail. Rated current In 1A or 5A (selectable)
Rated voltage Vn 100V to 120V
Rated Frequency 50Hz or 60Hz (specified on order)
4 times rated current continuous, 5 times rated current for 3 minutes,
6 times rated current for 2 minutes, 30 times rated current for 10 seconds,
Current inputs
100 times rated current for 1 second,
Overload Rating 250 times rated current for one power cycle (20 or 16.6ms)
2 times rated voltage continuous
Voltage inputs
2.5 times rated voltage for 1 second
Phase current inputs ≤ 0.1VA at In = 1A, ≤ 0.2VA at In = 5A
Earth current inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Burden
Sensitive earth fault inputs ≤ 0.3VA at In = 1A, ≤ 0.4VA at In = 5A
Voltage inputs ≤ 0.1VA at Vn
PC Display of GR-TIEMS Power Supply
24/48/60Vdc (Operative range: 19.2 – 72Vdc), 48/110Vdc (Operative range: 38.4 –
Rated auxiliary voltage
132Vdc), 110/250Vdc or 115/220Vac (Operative range: 88 – 300Vdc or 80 – 230Vac)
Superimposed AC ripple on DC supply ≤ 15%
LCD Configuration Programmable Logic Editor
Supply interruption ≤ 20ms at 110Vdc
The user can configure and customize the MIMIC data displayed The programmable logic controller is compliant with IEC 61131- Power consumption ≤ 15W (quiescent), ≤ 25W (maximum)
on the LCD of GR-200 series IEDs using the GR-TIEMS. 3. The PLC Editor enables the user to configure flexible logic Binary Inputs
allowing customized application and operation. Logic can be 24/48/60Vdc (Operating range: 19.2 – 72Vdc), 48/110Vdc (Operative range: 38.4 –
prepared using a graphical PC tool to allow special applications 132Vdc), 110/125/220/250Vdc (Operating range: 88 – 300Vdc)
Input circuit DC voltage
such as automatic disconnection of a feeder from a busbar, Note: Variable threshold settings are available for BI2 and BIO4 (Setting range: 14V to
automatic busbar changeover and automatic Close/Open of a bus 154V)
coupler/section. In addition mathematical calculation logic using 10μF charged to maximum supply voltage and discharged into the input terminals,
Capacitive discharge immunity
according to ENA TS 48-4 with an external resistor
analog values can be included. The status of configured logic can
be monitored using the tool software and the logic calculation Maximum permitted voltage 72Vdc for 24/48/60Vdc rating, 300Vdc for 110/250Vdc rating
cycle can be executed in 1ms steps. Power consumption ≤ 0.5W per input at 220Vdc
Binary Outputs
Make and carry 5A continuously, 30A, 290Vdc for 0.2s (L/R=5ms)
Fast operating contacts Break 0.15A, 290Vdc (L/R=40ms)
Operating time Typical 3 ms
PC Display of SLD configuration
Make and carry 8A continuously, 30A, 240Vdc for 1s (L/R=5ms)
Semi-fast operating 0.1A, 250Vdc (L/R=40ms)
Break
contacts 0.2A, 125Vdc (L/R=40ms)
Operating time Typically 6 ms
Make and carry 8A continuously, 30A, 240Vdc for 1s (L/R=5ms)
0.1A, 250Vdc (L/R=40ms)
Auxiliary contacts Break
0.2A, 250Vdc (L/R=40ms)
PC display of PLC editor
Operating time Typically 8 ms
Make and carry 8A continuously, 10A, 220Vdc for 0.5s (L/R=5ms)
Hybrid contacts
Break 10A, 220Vdc (L/R=20ms), 10A, 110Vdc (L/R=40ms)
(10 A breaking)
Operating time 1 ms
Durability ≥ 10,000 operations (loaded contact), ≥ 100,000 operations (unloaded contact)

11 12
Technical Data Environmental Performance
HARDWARE
DC-AI (analog inputs) Atmospheric Environment
DC 0±1mA, 0±20mA, 4–20mA , 0–10mA, 0–20mA, ±10mA
Measurement range Operating range: -10°C to +55°C.
DC –1 – 0 – +1V, –5 – 0 – +5V, –10 – 0 – +10V IEC 60068-2-1/2
Temperature Storage / Transit: -25°C to +70°C.
Accuracy ±0.5% of full scale IEC 60068-2-14
Cyclic temperature test as per IEC 60068-2-14
Maximum permitted continuous current 2 times for maximum measurement range
Input resistance 250Ω (0±20mA), 3,000Ω (0±1mA ) IEC 60068-2-30 56 days at 40°C and 93% relative humidity.
Humidity
IEC 60068-2-78 Cyclic temperature with humidity test as per IEC 60068-2-30
DC-AO (analog outputs)
DC 0 – ±20mA IP52 - Dust and Dripping Water Proof
Measurement range Enclosure Protection IEC 60529
DC 0 – ±10V IP20 for rear panel
Accuracy ±1% of full scale
Mechanical Environment
Measuring input capability
Standard current input ≥ 60A (1A rating) or 300A (5A rating) Response - Class 1
Vibration IEC 60255-21-1
Endurance - Class 1
Full scale Sensitive current input ≥ 3A (1A rating) or 15 A (5A rating)
Voltage input ≥ 200V Shock Response Class 1
Sampling rate 48 samples / cycle Shock and Bump IEC 60255-21-2 Shock Withstand Class 1
Frequency response < 5% deviation over range 16.7Hz to 600Hz Bump Class 1
Mechanical Design Seismic IEC 60255-21-3 Class 1
Installation Flush mounting or rack mounting
Electrical Environment
Weight Approx. 10kg (1/3 size), 12kg (1/2 size), 15kg (3/4 size), 25kg (1/1 size)
Case colour 2.5Y7.5/1 (approximation to Munsell value) 2kVrms for 1 minute between all terminals and earth.
Dielectric Withstand IEC 60255-27 2kVrms for 1 minute between independent circuits.
LED
1kVrms for 1 minute across normally open contacts.
Number 26 (Fixed for “In service” and “ERROR”)
Color Red / Yellow / Green (configurable) except In service (green) and Error (red) IEC 60255-5 Three positive and three negative impulses of 5kV(peak), 1.2/50μs, 0.5J between all
High Voltage Impulse
Function keys IEEE C37.90 terminals and between all terminals and earth.
Number 7
1. Voltage dips:
Local Interface 0 % residual voltage for 20 ms
USB Type B 40 % residual voltage for 200 ms
 Maximum cable length 2m (max.) 70 % residual voltage for 500 ms
System Interface (rear port) Voltage Dips, IEC 60255-11,
2. Voltage interruptions:
Interruptions, IEC 61000-4-29,
CAT5e STP cable 0 % residual voltage for 5 s
100BASE-TX/ Cable type Variations and Ripple IEC 61000-4-17
- enhanced category 5 with Shielded Twisted Pair cable
1000BASE-T on DC supply IEC 60255-26 Ed 3 3. Ripple:
Connector type RJ-45
15 % of rated d.c. value, 100 / 120 Hz
Cable type Multimode fibre, 50/125μm or 62.5/125μm
100BASE-FX Connector type SC duplex 4. Gradual shut-down / start-up: 60 s shut-down ramp, 5 min power off, 60 s start-up ramp
Wave length 1300nm 5. Reversal of d.c. power supply polarity: 1 min
Cable type Single-mode fibre
1000BASE-LX Connector type LC duplex 10μF charged to maximum supply voltage and discharged into the input terminals with an
Capacitive Discharge ENA TS 48-4
external resistance
Wave length 1310nm
Cable type Shielded twisted pair cable
RS485
Connector type Push-in spring terminal
Cable type Multimode fibre, 50/120μm or 62.5/125μm
Fiber optical
Connector type ST
(for serial communication)
Wave length 820nm
Terminal Block
CT/VT input M3.5 Ring terminal
Binary input, Binary output Compression plug type terminal

13 14
Environmental Performance Environmental Performance

Electromagnetic Environment Performance and Functional Standards


High Frequency Category Standards
IEC 60255-22-1 Class 3, 1 MHz burst in common / differential modes
Disturbance / General
IEC 61000-4-18 Auxiliary supply and I/O ports: 2.5 kV / 1 kV
Damped Oscillatory Common requirements IEC 60255-1
IEC 60255-26 Ed 3 Communications ports: 1 kV / 0 kV
Wave
Data Exchange IEC 60255-24 / IEEE C37.111 (COMTRADE) / IEEE C37-239 (COMFEDE)
IEC 60255-22-2 Class 4, Product Safety IEC 60255-27
IEC 61000-4-2 Contact: 2, 4, 6, 8kV Functional
Electrostatic Discharge
IEEE C37.90.3-2001 Air: 2, 4, 8, 15kV
Distance IEC 60255-121
IEC 60255-26 Ed 3
Under/Over Voltage Protection IEC 60255-127
IEC 60255-22-3, Sweep test ranges: 80 MHz to 1 GHz and 1.4 GHz to 2.7 GHz. Thermal Protection IEC 60255-149
Radiated RF IEC 61000-4-3 Level 3 Spot tests at 80, 160, 380, 450, 900, 1850 and 2150 MHz.
Over/Under Current Protection IEC 60255-151
Electromagnetic IEC 60255-26 Ed 3 Field strength: 10 V/m
Disturbance
IEEE C37.90.2-1995 Field strength 35V/m for frequency sweep of 25MHz to 1GHz. European Commission Directives
IEC 60255-22-4 5 kHz, 5/50ns disturbance Compliance with the European Commission Electromagnetic
Fast Transient 2014/30/EU
IEC 61000-4-4 Auxiliary supply and input / output ports: 4 kV Compatibility Directive is demonstrated according to EN 60255-26:2013.
Disturbance
IEC 60255-26 Ed 3 Communications ports: 2 kV Compliance with the European Commission Low Voltage Directive for
2014/35/EU
electrical safety is demonstrated according EN 60255-27:2014.
IEC 60255-22-5 1.2/50µms surge in common/differential modes:
Surge Immunity IEC 61000-4-5 Auxiliary supply and input / output ports: 4, 2, 1, 0.5 kV / 1, 0.5 kV
IEC 60255-26 Ed 3 Communications ports: up to 1, 0.5 kV / 0 kV

3kV, 1MHz damped oscillatory wave


Surge Withstand IEEE C37.90.1-2002
4kV, 5/50ns fast transient

Conducted RF IEC 60255-22-6 Sweep test range: 150 kHz to 80MHz


Electromagnetic IEC 61000-4-6 Spot tests at 27 and 68 MHz.
Disturbance IEC 60255-26 Ed 3 Voltage level: 10 V r.m.s

IEC 60255-22-7
Power Frequency 50/60 Hz disturbance for 10 s in common / differential modes
IEC 61000-4-16
Disturbance Binary input ports: 300 V / 150 V
IEC 60255-26 Ed 3

Field applied at 50/60Hz with strengths of:


Power Frequency IEC 61000-4-8 Class 4
30A/m continuously,
Magnetic Field IEC 60255-26 Ed 3
300A/m for 1 second.

Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
IEC 60255-25
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Conducted and EN 55022 Class A,
Radiated emissions
Radiated Emissions EN 61000-6-4
30 to 230 MHz: < 40 dB(uV/m)
IEC 60255-26 Ed 3
230 to 1000 MHz: < 47 dB(uV/m)
Measured at a distance of 10 m

15 16
Dimension (1/3 size) Dimension (3/4 size)

265.9

260.7

265.9

260.7
186 209 33
366 209 33

Front view Side view Front view Side view

Dimension (1/2 size) Dimensions (1/1 size)

265.9

260.7
265.9

260.7

260 209 33 483 209 33

Front view Side view Front view Side view