Date : 08 SEP 09
REF : OS/OPN/OO/HOD/019
DATE : 01.09.2009
The existing scheme and proposed scheme for implementation in stage-I and
stage-II in line with the CERC order on FGMO are as follows for your review.
In stage-III the scheme can be implemented using MaxDNA.
1 of 5
Ramagundam
correction
<0
&
Frequency
< 50
+ + Load LOAD
+ + Controller Programmer +
Summer Turbine
-
+
EHC /
Load Set Frequency
Point Pressure Influence
Controller
Actual Load
2 of 5
Ramagundam
You are requested to kindly advise us for further action at our end
please.
(B.B.TRIPATHY)
3 of 5
Ramagundam
Annexure
Ansaldo units of stage-I (200MW) equipped with inbuilt governor with a droop
of 5%. Load command gets generated from sum of ‘Frequency Influence’ and
‘Load programmer set point’.
Frequency Influence:
47.5 48.0 48.5 49.0 49.5 50.0 50.5 51.0 51.5 52.0 52.5
(+)100%(+)80 % (+)60% (+)40% (+ )20% 0 (-) 20% (- )40% (-)60% (-)80% (-)100%
Load programmer set point is from 0 – 140% which varies as per the
“Load set point in CMC” or manual.
4 of 5
Ramagundam
Limitations:
5 of 5