Академический Документы
Профессиональный Документы
Культура Документы
Simulator
6.1 Objectives:
To perform the symmetrical fault analysis and determine for circuit breaker rating.
To calculate the current supplied by each generator and bus voltage magnitudes during fault
6.2 Introduction:
Fault in a circuit is any failure which interferes with the normal flow of current. Most faults
on transmission lines of 115 kV and higher are caused by lightning, which results in the flashover
of insulators. The high voltage between a conductor and the grounded supporting tower causes
ionization, which provides a path to ground for the charge induced by the lightning stroke. Once
the ionized path to ground is established, the resultant low impedance to ground allows the flow
of current from the conductor to ground and through the ground to the grounded neutral of a
transformer or generator, thus completing the circuit. Line-to-line faults not involving ground are
less common.
Most of the faults on the power system lead to a short-circuit condition. When such a
condition occurs, a heavy current (called short-circuit current) flows through the equipment,
causing considerable damage to the equipment and interruption of service to the consumers.
ZTH ZFAULT
VTH
The software, ‘Power World Simulator’ is used in this experiment to study the symmetrical
fault and determine CB ratings.
1.5 Experimental Procedure:
Make the transmission system as shown in Figure 6.2.
Bus 2
Load 1 (40MW, 10MVAR)
Bus 1(1+j0 p.u) j0.04
G1
Load 2 (40MW, 10MVAR)
100MW j0.05 j0.05 Bus 4
100 MW G2 Bus 3
G1
Load 2 (50 MW, 10 MVAR)
100 MW 0.3 j0.05 0.2+j0.05 Bus 4(0.98+j0 p.u)
Bus 1
Bus 2
Table 6.3
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
Bus 4
Bus 1
Bus 2
Bus 3
Bus 4
Table 6.5
Phase Phase Phase Phase Ang Phase Ang Phase Ang
Current A Current B Current C A B C
Bus 1
Bus 2
Table 6.6
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
Bus 4
Table 6.8
Phase Phase Phase Phase Ang Phase Ang Phase Ang
Current A Current B Current C A B C
Bus 1
Bus 2
Table 6.9
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
Bus 4
6.6.2 Lab Task 2
Study the fault at Bus 1 for the following fault impedances:
Zf 0.35 + j0.99 p.u
Zf 0.44 + j0.86 p.u
Zf 0.42 + j0.55 p.u
G1
Load 2 (50 MW, 10 MVAR)
100 MW 0.3 j0.05 0.2+j0.05 Bus 4(0.98+j0 p.u)
Bus 1
Bus 2
Table 6.11
Phase Phase Phase Phase Ang Phase Ang Phase Ang
Current A Current B Current C A B C
Bus 1
Bus 2
Table 6.12
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
Bus 4
Bus 5
Bus 1
Bus 2
Bus 3
Bus 4
Bus 5
Table 6.14
Phase Phase Phase Phase Ang Phase Ang Phase Ang
Current A Current B Current C A B C
Bus 1
Bus 2
Table 6.15
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
Bus 4
Bus 5
Bus 1
Bus 2
Bus 3
Bus 4
Bus 5
Table 6.17
Phase Phase Phase Phase Ang Phase Ang Phase Ang
Current A Current B Current C A B C
Bus 1
Bus 2
Table 6.18
Phase Current A Phase Current B Phase Current C
Bus 2
Bus 3
PE-351L Power System Analysis Lab
Lab Rubric
Some
Specifications, • No
Specifications, specifications,
parameters and specifications,
parameters and parameters and parameters and
constraints of design
constraints of design constraints of constraints of
are present.
are present. design are present design are
present
Design PLO-3 Sufficient
Detailed calculations Insufficient • No calculations
calculations and/or and/or
and/or procedures calculations and/or
procedures to obtain procedures to
to obtain the design procedures to
the design are obtain the
are provided. obtain the design
provided design are
are provided. provided.
Demonstrates
Demonstrates Demonstrates Demonstrates some incomplete
extensive knowledge knowledge of the topic knowledge of the knowledge of the
Viva PLO-9 of the topic by by responding topic by responding topic by
responding precisely to precisely to all accurately to all responding
all questions questions questions inaccurately to all
questions
Student arrives on
Student arrives on
time in less than or
Punctuality PLO-8 N/A N/A time in more than
equal to 60% of
60% of labs
the labs