Arc Flash and Shock Hazard Arc Flash and Shock Hazard Arc Flash and Shock Hazard
Appropriate PPE Required Appropriate PPE Required Appropriate PPE Required
Arc Flash Boundary 0.10 m Arc Flash Boundary 3.12 m Arc Flash Boundary 0.79 m
Incident Energy (cal/cm²) 0.1 Incident Energy (cal/cm²) 16.3 Incident Energy (cal/cm²) 1.8
Working Distance 45.7 cm Working Distance 61.0 cm Working Distance 61.0 cm
Level A Level D Level A
Non-melting or untreated natural fiber long-sleeve Multilayer FR flash jacket and FR bib overalls (m Non-melting or untreated natural fiber long-sleeve
shirt and long pants inimum arc rating of 4) or FR long-sleeve shirt shirt and long pants
and FR pants (minimum arc rating of 4) worn
over untreated natural fiber long-sleeve shirt and
pants, worn over an untreated cotton T-shirt
Shock Hazard Exposure 415 VAC Shock Hazard Exposure 415 VAC Shock Hazard Exposure 415 VAC
Shock Hazard when covers removed Shock Hazard when covers removed Shock Hazard when covers removed
Limited Approach 1.07 m Class 00 Limited Approach 1.07 m Class 00 Limited Approach 1.07 m Class 00
Restricted Approach 0.30 m Insulating Gloves Restricted Approach 0.30 m Insulating Gloves Restricted Approach 0.30 m Insulating Gloves
V-rating 500 VAC V-rating 500 VAC V-rating 500 VAC
Equipment Name: Equipment Name: Equipment Name:
Source Protective Device: Fuse677 Source Protective Device: Inc. EU2-PA-400A Source Protective Device: Inc. EU2-PA-403
EU2-200-PA-434-DB EU2-PA-400A EU2-PA-403
19-05-2020 19-05-2020 19-05-2020
Arc Flash and Shock Hazard Arc Flash and Shock Hazard Arc Flash and Shock Hazard
Appropriate PPE Required Appropriate PPE Required Appropriate PPE Required
Arc Flash Boundary 2.92 m Arc Flash Boundary 3.12 m Arc Flash Boundary 2.83 m
Incident Energy (cal/cm²) 14.6 Incident Energy (cal/cm²) 16.3 Incident Energy (cal/cm²) 22.1
Working Distance 61.0 cm Working Distance 61.0 cm Working Distance 45.7 cm
Level D Level D Level D
Multilayer FR flash jacket and FR bib overalls (m Multilayer FR flash jacket and FR bib overalls (m Multilayer FR flash jacket and FR bib overalls (m
inimum arc rating of 4) or FR long-sleeve shirt inimum arc rating of 4) or FR long-sleeve shirt inimum arc rating of 4) or FR long-sleeve shirt
and FR pants (minimum arc rating of 4) worn and FR pants (minimum arc rating of 4) worn and FR pants (minimum arc rating of 4) worn
over untreated natural fiber long-sleeve shirt and over untreated natural fiber long-sleeve shirt and over untreated natural fiber long-sleeve shirt and
pants, worn over an untreated cotton T-shirt pants, worn over an untreated cotton T-shirt pants, worn over an untreated cotton T-shirt
Shock Hazard Exposure 415 VAC Shock Hazard Exposure 415 VAC Shock Hazard Exposure 415 VAC
Shock Hazard when covers removed Shock Hazard when covers removed Shock Hazard when covers removed
Limited Approach 1.07 m Class 00 Limited Approach 1.07 m Class 00 Limited Approach 1.07 m Class 00
Restricted Approach 0.30 m Insulating Gloves Restricted Approach 0.30 m Insulating Gloves Restricted Approach 0.30 m Insulating Gloves
V-rating 500 VAC V-rating 500 VAC V-rating 500 VAC
Equipment Name: Equipment Name: Equipment Name:
Source Protective Device: Inc. EU2-PD-400 Source Protective Device: Inc. EU2-PD-401 PA400A Source Protective Device: Inc. EU2-PD-400
EU2-PD-400 EU2-PD-401 EU2-PD-420
19-05-2020 19-05-2020 19-05-2020
Arc Flash and Shock Hazard Arc Flash and Shock Hazard Arc Flash and Shock Hazard
Appropriate PPE Required Appropriate PPE Required Appropriate PPE Required
Arc Flash Boundary 0.32 m Arc Flash Boundary 5.67 m Arc Flash Boundary 2.40 m
Incident Energy (cal/cm²) 0.7 Incident Energy (cal/cm²) 21.0 Incident Energy (cal/cm²) 10.7
Working Distance 45.7 cm Working Distance 91.4 cm Working Distance 61.0 cm
Level A Level D Level D
Non-melting or untreated natural fiber long-sleeve Multilayer FR flash jacket and FR bib overalls (m Multilayer FR flash jacket and FR bib overalls (m
shirt and long pants inimum arc rating of 4) or FR long-sleeve shirt inimum arc rating of 4) or FR long-sleeve shirt
and FR pants (minimum arc rating of 4) worn and FR pants (minimum arc rating of 4) worn
over untreated natural fiber long-sleeve shirt and over untreated natural fiber long-sleeve shirt and
pants, worn over an untreated cotton T-shirt pants, worn over an untreated cotton T-shirt
Shock Hazard Exposure 415 VAC Shock Hazard Exposure 11000 VAC Shock Hazard Exposure 415 VAC
Shock Hazard when covers removed Shock Hazard when covers removed Shock Hazard when covers removed
Limited Approach 1.07 m Class 00 Limited Approach 1.52 m Class 2 Limited Approach 1.07 m Class 00
Restricted Approach 0.30 m Insulating Gloves Restricted Approach 0.66 m Insulating Gloves Restricted Approach 0.30 m Insulating Gloves
V-rating 500 VAC V-rating 17000 VAC V-rating 500 VAC
Equipment Name: Equipment Name: Equipment Name:
Source Protective Device: Fuse EU2-PM-401 Source Protective Device: CB-EU2-KM-2651 Source Protective Device: CB23
EU2-PM-401 EU2-PS-1102 EU2-PS-405
19-05-2020