Mirpur Cantonment, Dhaka-'l 2 l 6


Centre for Advisory and Testing Services (CATS-MI5T)
Military lnstitute of Science and Technology

Compressive Strength of Concrete Drilled Cores


CATS Reference :2376/Conl20400-20401,/9/L9 Date : 09.09.2019
Client : Sheema Fashion
Project Name & Address :Sheema Fashion atC-L78, L79 & tSO {.22817)sarkar Market) Digir
Chala, Eata Hata, Word: 16, Joydebpur, Gazipur.
Sample Brought By : Md. Emarat Hossain Date of Receiving : 01.09.2019
Test Method ASTM C 42lC 42-M Date of Test 08.09.20L9
Type of Sample Drilled Core Sample Condition Sealed
Location of Sample Footing F4, Grid: H7 &H7
Construction Year Not Mentioned Quantity of Sample 02 nos
No of Story Not Mentioned Type of Aggregate Stone chips

Sample Oriiinal Sawed tiameterl CrushinBl Crushine failure FracturrE Type


il$,|.
[t
iN= ldentification
Ma,r.k mm *T
tength Length,l
I Load I Stiength TYpe

1 Core-L 200.0 138.0 67.O 1,L2.6 31.9 4630 Combined Cone and Shear

2 Core-2 200.0 138.0 67.O 131.0 37.1 5380 Combined Cone and Shear

REMARKS:
1-. All information displayed obove was provided by the client. CATS -M|ST did not verify ony of those.
2. Pleose compore the results with your corresponding design values ond consult with your design engineer.

lslam,PhD,Engrs
Countersigned

U
Bv: (

NUR HossArN
G(.
ug5*y*oD
fli:;i,,*,'fi;,if:i;,,-, Senior Instructor
EnSineering Deparrmenf
frivil

Note: Samples as supplied to us have been tested in our laboratory. CATS-MIST does not have any responsibility
as to the representative character of the samples required to be tested. lt is recommended that samples to be
sent in secure and sealed cover/packet/container under signature of the competent authority in order to
fraudulent fabrication of test results. lt is recommended to collect all test reports by duly authorized person and
not by the contractor/supplier himself.