How to initialize the I/P Positioner for FDF damper controller

Written by : M.G.Park

Change control mode to manual by


pressing the hand symbol key
briefly.

Press the “ - “ or “ + ” symbol in


order to closed the damper
manually, mainly the “ - “ symbol
is used for close the damper but in
case the parameter of No.7, No.38
are set for “FALL” then “ +
“ symbol is used for close.

When damper is fully closed, then


carefully turn the “Adjusting wheel
slip clutch” left or right side in order
to set the zero position and position
on LCD to “0”,
Aalborg Industries A/S Tel. +45 99 30 44 00 E-mail: aalm@aalborg-industries.dk
24 A Gasvaerksvej Fax +45 98 16 83 16 http://www.aalborg-industries.com
P O Box 844 Telex 69705 albor dk Bankers: Den Danske Bank A/S, Aalborg
9100 Aalborg Giro No. 746-1232 Account No. 3201-66914-6
Denmark PBS No. 02176815 Unibank A/S, Copenhagen
Reg. No A/S 158349 VAT No. 17831577 Account No. 2149-0270344283

Press the “ - “ or “ + ” symbol in


order to open the damper, mainly
the “ + “ symbol is used for open the
damper but in case the parameter of
No.7, No.38 are set for “FALL”
then “ - “ symbol is used for open.

When damper is fully open, then


carefully turn the “Adjusting wheel
slip clutch” left or right side in order
to set the span position and position
on LCD to “100”

Call the configuration mode by


pressing the hand symbol key about
5sec from normal operation mode.

5Sec
Aalborg Industries A/S Tel. +45 99 30 44 00 E-mail: aalm@aalborg-industries.dk
24 A Gasvaerksvej Fax +45 98 16 83 16 http://www.aalborg-industries.com
P O Box 844 Telex 69705 albor dk Bankers: Den Danske Bank A/S, Aalborg
9100 Aalborg Giro No. 746-1232 Account No. 3201-66914-6
Denmark PBS No. 02176815 Unibank A/S, Copenhagen
Reg. No A/S 158349 VAT No. 17831577 Account No. 2149-0270344283

Now configuration mode is appear on


the display, and it shown parameter
list
Switch to the parameter for
initialization (4 INITA) by pressing
the hand symbol briefly three times.

Start the initialisation (“4.INITA”) by


pressing the “ + ” key for longer than
5 seconds

5Sec

During initialization phase “RUN1”


to “RUN5” appear one after another
in the bottom of the display, and
during initialization the micro
controller will automatically
determines the zero, full-scale and
positioning speed and so on.
Aalborg Industries A/S Tel. +45 99 30 44 00 E-mail: aalm@aalborg-industries.dk
24 A Gasvaerksvej Fax +45 98 16 83 16 http://www.aalborg-industries.com
P O Box 844 Telex 69705 albor dk Bankers: Den Danske Bank A/S, Aalborg
9100 Aalborg Giro No. 746-1232 Account No. 3201-66914-6
Denmark PBS No. 02176815 Unibank A/S, Copenhagen
Reg. No A/S 158349 VAT No. 17831577 Account No. 2149-0270344283

If problems occur, carry out the


described in the table ”Possible
messages” shown in instruction
manual.
The initialization is completed when
“FINSH” appears
For exit initialization mode press
hand symbol briefly.

Now unit is back to configuration


mode.
To exit the configuration mode, press
the hand symbol key for longer than
5sec, and the software version is
displayed after 5sec.

5Sec

Now unit is back to operation mode,


but it will remain in the manual
mode, and this mode operator can
open and close the damper by
pressing the “-“ or “+”key.
The positioner can be changed to
auto mode by pressing hand symbol
key briefly
Aalborg Industries A/S Tel. +45 99 30 44 00 E-mail: aalm@aalborg-industries.dk
24 A Gasvaerksvej Fax +45 98 16 83 16 http://www.aalborg-industries.com
P O Box 844 Telex 69705 albor dk Bankers: Den Danske Bank A/S, Aalborg
9100 Aalborg Giro No. 746-1232 Account No. 3201-66914-6
Denmark PBS No. 02176815 Unibank A/S, Copenhagen
Reg. No A/S 158349 VAT No. 17831577 Account No. 2149-0270344283

Now unit is in auto mode and this


mode is the normal operation mode,
and the positioner compares the set
point with the current position and
moves the actuator unit the control
deviation reaches the dead zone.