Академический Документы
Профессиональный Документы
Культура Документы
To users
In order to correctly design the Integlex fire alarm system for your application, please read this manual carefully to
understand the system functionality.
The content of this manual is limited to system design only. For further details on system operation, installation, and
data programming, please refer to the following documents.
Document history
Notes
•Nohmi Bosai Limited reserves the copyright of this System Design Manual.
•Copying or reproduction of this manual wholly or in part without express permission of Nohmi Bosai Limited is
prohibited.
•These instructions do not purport to cover all the details or variations in the equipment described herein, nor
provide for every possible contingency in connection with installation, operation and maintenance.
•Nohmi Bosai Ltd. shall not be responsible or liable for any consequence resulting from the use of this manual.
•On designing Integlex fire alarm system that is connected to relative systems, especially fire suppression
systems, thorough discussions and confirmations on specifications, functionality, and actual performance with
relative systems suppliers are required.
•Actual performance is based on proper application of the product by a qualified professional.
•Specifications of products, parts, and components in this manual are subject to change without notice.
•Should further information be desired or should particular problems arise, which are not covered sufficiently
herein for the users' purposes, please contact Nohmi or your local distributor.
CONTENTS
1. Introduction .................................................................................................................................................1
3. Features .......................................................................................................................................................2
3.1. Ample display of information on LCD .....................................................................................................2
3.2. Network functionality .............................................................................................................................. 2
3.3. Easy system expansion .......................................................................................................................... 3
3.4. Versatile data settings ............................................................................................................................3
3.5. Integrated VESDA LaserCOMPACT LP ................................................................................................. 3
3.6. Multiple detection levels of detectors .....................................................................................................3
3.7. Event log ................................................................................................................................................3
3.8. Day/Night/Holiday monitoring level change-over ................................................................................... 3
3.9. Low temperature trouble function ........................................................................................................... 3
3.10. Auto program ........................................................................................................................................3
3.11. Dedicated control function for suppression system (Suppression Zone) ............................................. 3
5. Specifications ..............................................................................................................................................6
5.1. Fire alarm control panel .......................................................................................................................... 6
5.2. Analog detectors ....................................................................................................................................8
5.3. VESDA LaserCOMPACT LP .................................................................................................................. 8
5.4. Conventional detectors ........................................................................................................................... 9
5.5. Addressable modules .............................................................................................................................9
5.6. Short circuit isolator .............................................................................................................................. 11
5.7. Remote annunciators ........................................................................................................................... 11
5.8. Manual stations .................................................................................................................................... 13
6. Functionality ..............................................................................................................................................16
6.1. System administration numbers ........................................................................................................... 16
6.1.1. Node numbers ............................................................................................................................... 16
6.1.2. Group numbers .............................................................................................................................. 16
6.1.3. Loop numbers (Integlex loop numbers) ........................................................................................ 16
6.1.4. Address numbers .......................................................................................................................... 16
6.1.5. Conventional zone numbers (Z000 to Z500) ................................................................................. 16
6.1.6. Inter-Panel zone numbers (Z600 to Z699: IP00 to IP99) ............................................................... 16
6.2. Types of input signals ........................................................................................................................... 17
6.2.1. Alarm signals ................................................................................................................................. 17
6.2.2. Supervisory signals ....................................................................................................................... 17
6.2.3. Trouble signals .............................................................................................................................. 17
6.2.4. Other signals ................................................................................................................................. 17
6.3. Threshold setting ranges of analog detectors and VESDA LaserCOMPACT LP ................................. 18
6.4. System control switches on a fire alarm control panel ......................................................................... 18
6.4.1. ACKNOWLEDGE .......................................................................................................................... 18
6.4.2. SILENCE ....................................................................................................................................... 18
6.4.3. DRILL ............................................................................................................................................ 18
6.4.4. SYSTEM RESET ........................................................................................................................... 18
6.5. Status LEDs of FACP ........................................................................................................................... 18
6.5.1. AC POWER lamp (green) .............................................................................................................. 18
6.5.2. STANDBY POWER lamp (green) .................................................................................................. 18
6.5.3. ALARM lamp (red) ......................................................................................................................... 18
6.5.4. PRE-ALARM lamp (red) ................................................................................................................ 18
6.5.5. SUPERVISORY lamp (yellow) ...................................................................................................... 18
6.5.6. TROUBLE lamp (yellow) ............................................................................................................... 18
6.5.7. SILENCED lamp (yellow) .............................................................................................................. 19
6.6. Output control switches of Output Control Unit .................................................................................... 19
6.7. Status indication LEDs on Output Control Unit .................................................................................... 19
6.7.1. Output status LEDs (red) ............................................................................................................... 19
6.7.2. Trouble status LEDs (yellow): OCU-W only .................................................................................. 20
6.8. System control switches of LCD type remote annunciator ................................................................... 20
6.9. Status LEDs of LCD type remote annunciator ..................................................................................... 21
6.10. Status LEDs of LED type remote annunciator - Zone Indication Unit ................................................ 21
6.10.1. Zone alarm status LEDs .............................................................................................................. 21
6.10.2. POWER LED ............................................................................................................................... 21
6.11. Buzzer silence switch of LED type remote annunciator - Zone Indication Unit .................................. 21
6.12. Control switches of Zone Output Control Unit .................................................................................... 22
6.12.1. Zone output control switches ....................................................................................................... 22
6.12.2. Buzzer silence switch .................................................................................................................. 22
6.13. Status LEDs of Zone Output Control Unit .......................................................................................... 22
6.13.1. Zone output status LEDs ............................................................................................................. 22
6.13.2. Power LED ..................................................................................................................................22
6.14. Status LEDs of Zone Indication Unit, Open-Collector type
6.14.1. Signal transnission status LED .................................................................................................... 23
6.14.2. Power LED ..................................................................................................................................23
6.15. Buzzer silence switch of Optional Buzzer Unit for ZIU-O ................................................................... 23
6.16. System control switches of System Monitoring Program ................................................................... 23
6.17. Status indicators of System Monitoring Program ............................................................................... 24
6.18. Classifications configured for addressable devices ............................................................................ 24
6.19. Programmable outputs of MCU .......................................................................................................... 27
6.19.1. Wet outputs ................................................................................................................................. 27
6.19.2. Dry contact outputs ......................................................................................................................27
6.19.3. Status zones ................................................................................................................................ 28
6.20. Programmable outputs of OCU .......................................................................................................... 29
6.20.1. OCU-W wet outputs ..................................................................................................................... 29
6.20.2. OCU-D dry outputs ......................................................................................................................29
6.21. Definition and settings of zones ......................................................................................................... 29
6.21.1. Definition of a zone ......................................................................................................................29
6.21.2. Settings of zones ......................................................................................................................... 29
6.21.2.1. Zone setting for analog detectors and VESDA LaserCOMPACT LP .................................... 29
6.21.2.2. Zone setting for addressable module for initiating device, input type, and
addressable manual station ................................................................................................... 29
6.21.2.3. Zone setting for addressable modules wet and dry output type ............................................ 29
6.21.2.4. Zone setting for programmable wet and dry outputs of MCU ................................................ 29
6.21.2.5. Zone setting for wet outputs of OCU-W and dry outputs of OCU-D ...................................... 30
6.21.2.6. Zone setting for ZIU ............................................................................................................... 30
6.21.2.7. Zone setting for ZIU-O ........................................................................................................... 30
6.21.2.8. Zone setting for ZOCU .......................................................................................................... 30
6.22. Zone attributes ...................................................................................................................................30
6.22.1. System NAC Code Type ............................................................................................................. 30
6.22.2. Continuous ..................................................................................................................................30
6.22.3. 60 pulse ....................................................................................................................................... 30
6.22.4. 120 pulse ..................................................................................................................................... 31
6.22.5. Suppression ................................................................................................................................. 31
6.22.6. No Attribute ..................................................................................................................................31
6.23. Interlocking .........................................................................................................................................31
6.23.1. Interlocking by conventional zones .............................................................................................. 31
6.23.2. Interlocking by cross zone ........................................................................................................... 32
6.23.3. Interlocking by counting zone ...................................................................................................... 32
9. Wiring ......................................................................................................................................................... 90
9.1. Stipulations of the National Electric Code (NEC) ................................................................................. 90
9.2. Recommended cable specifications ..................................................................................................... 91
9.2.1. Recommended specifications of cable for FACP network ............................................................. 91
9.2.1.1. Metal/copper cable .................................................................................................................. 91
1. Introduction
The Integlex fire alarm system is a flexible analog addressable fire alarm system that meets the following US
standards. In addition to spot type analog and conventional detectors, the Integlex fire alarm system can be
equipped with a dedicated type of Very Early Smoke Detection Apparatus – VESDA LaserCOMPACT LP* on its
signal line circuit directly.
Additional functionality such as network function has been integrated into this system to make it suitable for
various types of applications.
*Note: The VESDA LaserCOMPACT LP is a product of Vision Fire & Security.
2. Standards to be complied
The Integlex fire alarm system complies with following standards.
NFPA (NFC) 12: CO2 Extinguishing Systems (High Pressure Only)
12A: Halon 1301 Extinguishing Systems
12B: Halon 1211 Extinguishing Systems
13: Sprinkler Systems
15: Water Spray Systems
16: Foam/Water Deluge and Foam/Water Spray Systems
17: Dry Chemical Extinguishing Systems
17A: Wet Chemical Extinguishing Systems
72: National Fire Alarm Code
*Note: NFPA is the acronym for the National Fire Protection Association, and NFC is the
acronym for the National Fire Code, which is issued by NFPA.
3. Features
3.1. Ample display of information on LCD
Each fire alarm control panel and LCD type remote annunciator has a 30-letter 6 4-line large-size LCD. The LCD
displays, in addition to basic information such as address numbers and classifications of active devices, the total
number of active signals per signal type, identification of the first and the last fire alarm signals, and current
analog values (i.e. smoke density and temperature). (See Figure 2 in section 6.1.1. for display details.)
LAN (NohmiNET)
SIU
FACP
NIU installed
FACP
*Note: NIU is the Network Interface Unit for constructing the network.
Power
Analog photo. Analog fixed Analog comb. input
smoke detector temp. heat heat detector Short circuit
Integlex fire alarm system
detector isolator
Relay module for AMMS*
analog detector AMWO* AMDO* AMI* AMI-b*
VESDA LaserCOMPACT
24VDC
24VDC
MCU Conventional
RA- Bus (RS-485) heat detector
Conventional Conventional Conventional Conventional
AMID* photoelectric ionization
Fire Alarm Control Panel heat & smoke air-duct use
smoke detector smoke detector detector smoke detector
4
Eight programmable dry
contacts (typical form C)
30VDC/2.0A each
FIM FIM
SIU AC
120/240VAC, 50/60Hz
PSM
Two 24VDC outputs
1.5A each
FACP
RS-232C (M size)
EPSM FACP
Four 24VDC outputs
1.5A each FACP (L size)
(XL size)
SMP
12V Battery 12V Battery
4.2.1. Fire alarm control panel (the following are components of the FACP)
•Main Control Unit (MCU)
•Power Supply Module (PSM)
•Extended Power Supply Module (EPSM): option
•Sub Control Unit (SCU): option
•Network Interface Unit (NIU): option
•Fiber-optic Interface Module (FIM): option
•City Tie Module (CTM): option
•Host Tie Module (HTM): option
•Output Control Unit Wet Type (OCU-W): option
•Output Control Unit Dry Type (OCU-D): option
•Enclosure
4.2.2. Analog detectors
•Photoelectric smoke detector
•Fixed temperature heat detector
•Combination type heat detector (i.e. fixed heat and rate-of-rise)
4.2.3. Very Early Smoke Detection Apparatus
•VESDA LaserCOMPACT LP
4.2.4. Conventional detectors
•Photoelectric smoke detector
•Ionization smoke detector
•Heat/Smoke detector
•Fixed temperature heat detector
•Combination type heat detector (i.e. fixed heat and rate-or-rise)
4.2.5. Manual stations
•Addressable manual station (i.e. Addressable module w/conventional manual station)
•Conventional manual station
4.2.6. Addressable modules
•Addressable module for initiating device
•Addressable module input type (normally-open contact)
•Addressable module input type, normally-closed contact
•Addressable module wet output type
•Addressable module dry output type
•Addressable module for manual station
4.2.7. Short circuit isolator
4.2.8. Remote annunciators
•LCD type remote annunciator
•LED type remote annunciator (i.e. Zone Indication Unit – ZIU)
•Open-collector type remote annunciator (i.e. Zone Indication Unit Open-collector output type - ZIU-O)
•Zone Output Control Unit (ZOCU)
•Optional buzzer unit for ZIU-O (OPT-BS)
4.2.9. Dry contact relay modules
•Dry contact relay module for analog detector
•Dry contact relay module for conventional detector
4.2.10. Enclosure for large capacity battery
4.2.11. End-of-line device and End-of-line resistor
4.2.12. Alarm bell
4.2.13. Software Program for CRT system (System Monitoring Program)
4.2.14. Interface for CRT system (System Interface Unit)
5. Specifications
5.1. Fire alarm control panel
Item Details
7MCU printed circuit assembly: part no. PCA-2700X MCU
7PSM printed circuit assembly: part no. PCA-2701X PSM
7EPSM printed circuit assembly: part no. PCA-2714X EPSM
7SCU printed circuit assembly (option): part no. PCA-2704X SCU
7NIU printed circuit assembly (option): part no. PCA-2706X NIU
7FIM printed circuit assembly (option): part no. PCA-2707X FIM
7CTM printed circuit assembly (option): part no. PCA-2703X CTM
Part number
7HTM printed circuit assembly: part no. PCA-2705X HTM
7OCU-W printed circuit assembly: part no. PCA-2712X OCU-W
7OCU-D printed circuit assembly: part no. PCA-2713X OCU-D
7Enclosure Small size: part no. ECL-4942NY/R
7Enclosure Medium size: part no. ECL-8967 NY/R
7Enclosure Large size: part no. ECL-4968 NY/R
7Enclosure Extra Large size: part no. ECL-4969 NY/R
7255 addresses consisting of 1 loop (standard)
No. of addresses 7510 addresses consisting of 2 loops (with optional 1 PCA SCU)
and loops 7765 addresses consisting of 3 loops (with optional 2 PCA SCUs)
71020 addresses consisting of 4 loops (with optional 3 PCA SCUs)
7R-22 protocol expanded type
System signal
7Less than 25m, 0.4nF
transmission
7NFPA Style 4, 6, and 7 complied
7240 6 64 dot graphic LCD (30 letters 6 4 lines)
7LEDs (AC POWER, STANDBY POWER, ALARM, PRE-ALARM,
Display & operation SUPERVISORY, TROUBLE, SILENCED)
7Switches (ACKNOWLEDGE, SILENCE, DRILL, SYSTEM RESET,
10-key, Up-Down-Left-Right arrow keys)
Audible device Buzzer (installed in MCU)
7Serial port: RS232C 6 2
7Serial port for remote annunciator: RS485 6 1
7Dry output (programmable for various purposes) 6 3, 2A at 30VDC, 0.5A
at 125VAC
7Wet output (programmable for various purposes) 6 2, 24VDC 1.5A
Outputs and ports of *Note: The total of MCU's 2 wet outputs and PSM’ 2 wet outputs shall
MCU adhere to the following limitations.
•S size FACP enclosure: The total shall be 4.0A maximum.
•M size FACP enclosure: The total shall be 3.5A maximum.
•L size FACP enclosure: The total shall be 3.0A maximum.
•XL size FACP enclosure: The total shall be 2.0A maximum.
CTM output Reverse Polarity output and Local Energy output with optional CTM
HTM output RS-485 serial signal
AC power input 120/240VAC auto-change: 85V to 132VAC, or 170V to 264VAC, 50/60Hz
Lead sealed battery 7 to 38AH
•S size FACP enclosure: Up to 12AH batteries can be housed.
•M size FACP enclosure: Up to 17AH batteries can be housed.
Standby power •L size FACP enclosure: Up to 17AH batteries can be housed.
•XL size FACP enclosure: Up to 17AH batteries can be housed.
Enclosure for large capacity battery is required when larger batteries are
needed.
Enclosure color Yellow/beige and red
Item Details
24VDC 1.5A 6 2
*Note: The total of MCU's 2 wet outputs and PSM' 2 wet outputs shall
adhere to the following limitations.
Wet outputs of PSM •S size FACP enclosure: The total shall be 4.0A maximum.
for various purposes
•M size FACP enclosure: The total shall be 3.5A maximum.
•L size FACP enclosure: The total shall be 3.0A maximum.
•XL size FACP enclosure: The total shall be 2.0A maximum
Wet outputs of
EPSM for various 24VDC 1.5A max. 6 4 (*Note: 5A max. for total of 4 outputs)
purposes
7Dry output (programmable for various purposes) 6 8 per OCU-D, 2A at
30VDC, 0.5A at 125VAC
7Wet output (programmable for various purposes) 68 outputs per OCU-W,
Outputs of OCU for 2A at 24VDC, 50W at 25VAC, 50W at 70VAC
various purposes
*Note: The total of outputs 1 through 4 shall be 4.0A at 24VDC, 100W at
25VAC, and 100W at 70VAC. The total of outputs 5 through 8 shall
also be 4.0A at 24VDC, 100W at 25VAC, and 100W at 70VAC.
Ambient humidity 7Temperature: 0 to 49 degrees C (i.e. 32 to 120 degrees F)
and temperature 7Humidity: Less than 93% (non-condensing)
Printer Keltron's VS4095/5 can be connected to either of two RS232C serial ports.
7Up to 30 units can be connected to the RS485 port for remote
annunciator
Remote annunciator 7Connection style: NFPA Style 4 complied
connection
7Connectable unit: LCD type remote annunciator, LED type annunciator,
open-collector type annunciator, and zone output control unit
7Constructed with optional printed circuit assembly NIU
7Fiber optic system available w/optional printed circuit assembly FIM
7Connection system: Daisy chain system
Network
7Max. 64 nodes
7Connection style: NFPA Style 4 (copper cable) and Style 7 (copper cable
or optical fiber) complied
Configuration data 7Dedicated software application used on Windows95/98/Me/NT/2000
creation 7Upload/download from/to the flash memory in MCU
Addressable module wet output type Addressable module dry output type
Item Specification Item Specification
Model number FRR01U-SL Model number FRR01U-SS
Signal line 2 wires (S+ & S-) Signal line 2 wires (S+ & S-)
71 Dry from C contact
2 wires (M+ & M-), consisting of NO, COM, & NC
Power line Output
24VDC, or 70VAC (audio power) 7Contact rating: 30VDC, 2A
125VAC, 0.5A
72 wires (C(RC) & D(RD)) for 1 7Monitoring: Less than 250nA
output (signal line)
7Output rating: 24VDC, 2A Current consumption
Output 7Operating: Less than 250nA
70VAC, 0.5A
(RC and RD are return in loop
(signal line)
wiring) Address setting Set by dedicated unit
7Monitoring: Less than 290nA
(signal line) Wiring supervision in
Current consumption Nil
7Operating: Less than 250nA secondary line
(signal line)
Address setting Set by dedicated unit 7Monitoring: Green flashes,
Available by reverse polarity system LED operation and red turns off
Wiring supervision 7Style Y: With 56Km end-of-line 7Operating: Red flashes, and
resistor or 56Km end-of line device green turns off
(open & short circuits) with diode
7Style Z: No end-of-line resistor Applicable wire AWG24 to 14 (i.e. 1.5m2)
7Normal: Green flashes, and red Ambient humidity & 0 to 49˚ C (32 to 120˚ F)
turns off. temperature 0 to 93% (non-condensing)
LED operation 7Active: Red flashes, and green
turns off. Installed in North American
Installation
single gang box
Applicable wire AWG24 to 14 (i.e. 1.5m2)
Ambient humidity & 0 to 49˚ C (32 to 120˚ F)
temperature 0 to 93% (non-condensing)
Installed in North American 4"
Installation
square box and double gang box
Open-collector type zone indication unit (ZIU-O) Zone output control unit (ZOCU)
Item Specification Item Specification
Part number PCA-2711X ZIU-O Model number FIR22U
Main line 2 wires (RS485+-) Main line 2 wires (RS485+-)
Power line 2 wires Power line 2 wires
Current 24VDC, 47mA Current consumption 24VDC, 32mA
consumption
78 LEDs for zone output
Open collector
35VDC, 100mA LEDs activation status indication
output ratings
71 LED for POWER
Number of open- 78 zone output activation switch
32 per unit Operation part
collector output 7Buzzer silence switch
71 LED for POWER
LE D s Audible device Buzzer
71 LED for signal transmission
Nil (optional buzzer unit
Audible device Enclosure color Yellow/beige and red
OPT-BS connectable)
Annunciator no. Annunciator no.
Rotary switches Rotary switches
setting setting
Applicable wire AWG24 to 14 (i.e. 1.5m2) Applicable wire AWG24 to 14 (i.e. 1.5m2)
Ambient humidity 0 to 49˚ C(32 to 120˚ F) Ambient humidity 0 to 49˚ C (32 to 120˚ F)
and temperature 0 to 85% (non-condensing) and temperrature 0 to 85% (non-condensing)
Relay modules for conventional detectors Relay module for analog detector
*Note:The following relay modules are typically Item Specification
combined with detector bases when shipped.
Model number FRL02U
Item Specification
Contact style Dry form C contact
FRL01U
Model number FRL01U-4 30VDC, 2A
Contact rating
125VAC, 0.5A
7FRL01U: Dry form C contact
Contact style 7FRL01U-4:Dry form C contact Applicable base FZB01U-N
and form A contact Applicable detector FDK38U, FDL25U,
7FRL01U :30VDC, 1A FDPL25U
125VAC, 0.5A Installation Mounted into detector base
Contact rating
7FRL01U-4:30VDC, 2A
125VAC, 1A
FZB01U-SX (FRL01U combined)
Applicable base FZB01U-4SX (FRL01U-4
combined)
Applicable detector FDK01U, FDS01U,
FDKL01U
Installation Mounted into detector base
6. Functionality
6.1. System administration numbers
The Integlex fire alarm system has the following system administration numbers.
6.1.1. Node numbers
A maximum of 64 nodes (i.e. FACPs and SMPs) can be networked. Node numbers are the numbers by which
each node on the network can be identified. Therefore, each node must be assigned a unique node number
from 1 to 64.
Node numbers are displayed on the FACP, LCD-RA, and SMP as [N00] (e.g. [N21] means node number 21.)
(Refer to Figure 2 below.)
When there is only 1 FACP (i.e. no network), the node number of the FACP is 1 (i.e. it is displayed as [N01]).
*Note: 1) When the Alarm of an analog smoke detector, the AlarmF1 and the AlarmF2 of VESDA
LaserCOMPACT LP are configured as Supervisory signals (see section 6.2.2. below), these signals
are operated as Supervisory signals, not as Alarm signals.
2) The Active signal of an input type addressable module is operated as an Alarm signal only when
“Alarm” classification type is configured for the module. (See Table 3 of section 6.18. for details.)
6.4.1. ACKNOWLEDGE
This is to acknowledge the event that is displayed on the LCD, and thereby to silence the audible device of the
FACP being activated by the event. If the event has already been acknowledged by this switch, re-pressing this
switch scrolls the LCD displays.
6.4.2. SILENCE
This is to deactivate notification appliances.
6.4.3. DRILL
This is to activate all pre-programmed notification appliances together.
output.)
4) An input signal to activate an OCU-W output was initiated. However, a short circuit has been detected in the
wiring of the output. Therefore, the output is not activated and its activation is reserved. (i.e. Removing the
short circuit activates the OCU output.)
Switch
Red LED
Yellow LED
Switch
Red LED
6.10. Status LEDs of LED type remote annunciator - Zone Indication Unit
The Zone Indication Unit (ZIU) is equipped with the following status LEDs. (See Figure 7.)
6.11. Buzzer silence switch of LED type remote annunciator - Zone Indication Unit
The ZIU is equipped with a buzzer and a buzzer silence switch. The buzzer activates when any alarm signal is
received from the configured zones. The buzzer is deactivated by operating either the ACKNOWLEDGE switch
on the FACP or the LCD-RA and / or the buzzer silence switch on the ZIU. (See Figure 7 below.)
Switch
Red LED
Signal transmission
status LED
0
Power LED
0
0
0
0
Figure 9: Zone Indication Unit, Open-collector type
causes a “Silence On” command to be sent from the SMP to the FACPs. (See Figure 11 below.)
FACP FACP
No.1 No.2
SMP
Always sends
"Silence On" FACP FACP
in this case No.3 No.4
Same Group
Figure 11: “Silence On” command transmission from SMP in a rare case
Status Indicators
Classification type
SUPERVISORY
SUPPRESSION
Classification
Addressable device
PRE ALARM
(Displayed on FACP LCD)
TROUBLE
OTHER
ALARM
NAC
Analog photoelectric smoke detector Analog Smk Detector √
Analog photoelectric smoke detector (supervisory) Analog Smk Detector √
Analog fixed temperature heat detector F/T Heat Detector √
Analog combination type heat detector Comb. Heat Detector √
VESDA LaserCOMPACT LP LaserCOMPACT LP √
VESDA LaserCOMPACT LP (supervisory) LaserCOMPACT LP √
Addressable manual station (i.e addressable module √
Pull Station
with conventional manual station)
Photo Smk Detector √
Ion Smoke Detector √
Heat Detector √
Smoke/Heat Detector √
Addressable module for initiating device
Leak Detector √
Pull Station √
Monitor Module √
Supervisory √
Monitor Module √
(Trouble)
Waterflow Monitor √
Supervisory √
Tamper √
Abort Switch(*) √
Manual Release(*) √
Trouble Input √
Fault Input √
Leak Detector Fault √
Silence √
Addressable module input type (normally-open contact) Drill √
Addressable module input type, normally-closed contact (*) System Reset √
PAS Inhibit(*) √
Hazard Alert √
Second Shot(*) √
Sprinkler System (A) √
Sprinkler System (S) √
Silent Input(*) √
Monitor Module √
Alarm Input √
Action Input √
Alert Input √
Pull Station √
[Continued on the next page]
SUPERVISORY
SUPPRESSION
Classification
Addressable device
PRE ALARM
(Displayed on FACP LCD)
TROUBLE
OTHER
ALARM
NAC
Control Output √
Bell Circuit(*) √
Horn Circuit(*) √
Strobe Circuit(*) √
Audible Circuit √
Speaker Circuit √
Release End Bell(*) √
Addressable module wet output type
Release Circuit(*) √
Addressable module dry output type
Release Audible √
Telephone √
Relay √
Power Shutdown(*) √
HVAC Shutdown(*) √
FAN Shutdown(*) √
Release Form C √
Blank Classification 1(*) 8 8 8 8 8 8 8
Blank Classification 2(*) 8 8 8 8 8 8 8
Addressable module input type (normally-open contact) Blank Classification 3(*) 8 8 8 8 8 8 8
Addressable module input type, normally-closed contact(*) Blank Classification 4(*) 8 8 8 8 8 8 8
Addressable module wet output type Blank Classification 5(*) 8 8 8 8 8 8 8
Addressable module dry output type Blank Classification 6(*) 8 8 8 8 8 8 8
Blank Classification 7(*) 8 8 8 8 8 8 8
Blank Classification 8(*) 8 8 8 8 8 8 8
Table 3: Classifications for configuring the addressable devices
*Note: (1) A checkmark (√) indicates the fixed classification type for a particular classification.
(2) Blank classifications 1 through 8 are commonly used for input type addressable modules, wet output
type addressable modules, dry output type addressable modules, MCU wet outputs, MCU dry outputs,
OCU-W wet outputs, and OCU-D dry outputs. (Refer to section 6.19. for MCU wet and dry outputs,
and section 6.20. for OCU-W wet outputs and OCU-D dry outputs.)
(3) Any one classification type may be selected for each blank classification.
(4) (A) indicates Alarm, and (S) indicates Supervisory for some classifications.
(5) Classifications with an asterisk (*) are described in later sections.
(6) The address number of the addressable module input type shall be one of 33 through 255 when the
classification “System Reset” is configred for the module.
(7) According to NFPA72 1999 edition, any “Alarm” type classifications (i.e. Waterflow Monitor, Manual
Release, Second Shot, Sprinkler System (A), Monitor Module, Alarm Input and Blank Classifications
with “Alarm” classification type) shall not be configured for the addressable module input type,
normally-closed contact.
Classification
PRE ALARM
(Displayed on FACP LCD)
TROUBLE
OTHER
ALARM
NAC
Control Output √
Bell Circuit(*) √
Horn Circuit(*) √
Strobe Circuit(*) √
Audible Circuit √
Speaker Circuit √
Release End Bell(*) √
Release Circuit(*) √
Release Audible √
Telephone √
Relay √
Power Shutdown(*) √
HVAC Shutdown(*) √
FAN Shutdown(*) √
Release Form C √
Fire Alarm Status √
Trouble Status √
Supervisory Status √
Status zone
Disable Status √
System Reset Status √
Silence Status √
Drill Status √
Main Power Fault √
Standby Power Fault √
[Continued on the next page]
SUPERVISORY
SUPPRESSION
Classification
PRE ALARM
(Displayed on FACP LCD)
TROUBLE
OTHER
ALARM
NAC
Blank Classification 1(*) 8 8 8 8 8 8 8
Blank Classification 2(*) 8 8 8 8 8 8 8
Blank Classification 3(*) 8 8 8 8 8 8 8
Blank Classification 4(*) 8 8 8 8 8 8 8
Blank Classification 5(*) 8 8 8 8 8 8 8
Blank Classification 6(*) 8 8 8 8 8 8 8
Blank Classification 7(*) 8 8 8 8 8 8 8
Blank Classification 8(*) 8 8 8 8 8 8 8
*Note: (1) A checkmark (√) indicates the fixed classification type for a particular classification.
(2) Blank classifications 1 to 8 are commonly used for input type addressable modules, wet output type
addressable modules, dry output type addressable modules, MCU wet outputs, MCU dry outputs,
OCU-W wet outputs, and OCU-D dry outputs.
(3) Any one classification type may be selected for each blank classification.
(4) Refer to section 6.19.3. for Status Zones.
(5) Classifications with an asterisk (*) are described in later sections.
6.21.2.2. Zone setting for addressable module for initiating device, input type, and addressable manual
station
A maximum of 7 conventional zones and/or IP zones are programmable for each of the addressable mod-
ule for initiating device, the input type addressable module, and the addressable module for manual station.
However, only 1 conventional zone is configured if any of following classifications is configured for an input
type addressable module.
PAS Inhibit, Second Shot, Silence, Drill, System Reset
6.21.2.3. Zone setting for addressable modules wet and dry output type
A maximum of 7 conventional zones and/or IP zones are programmable for the wet output type addressable
module and the dry output type addressable module.
6.21.2.4. Zone setting for programmable wet and dry outputs of MCU
A maximum of 7 zones are configurable for each MCU wet output and MCU dry output. However, only 1
zone is configured if any status zone is configured.
6.21.2.5. Zone setting for wet outputs of OCU-W and dry outputs of OCU-D
A maximum of 7 zones are configurable for each of OCU-W wet output and OCU-D dry output. However,
only 1 zone is configurable if any status zone is configured.
*Note: The Trouble Status of Status Zone cannot be configured for any output of OCU-W and OCU-D.
*Note: When multiple zones are configured for addressable modules, MCU outputs, and OCU outputs, the zone
configured in the 1st position is displayed on the LCD.
In the case of analog detectors and VLC, the zones configured in the 1st position of Alarm and AlarmF1
are displayed not only for Alarm and AlarmF1 events but also for other thresholds’ events.
•Example: If zone no. 268 is configured in the 1st position, no. 281 is in the 2nd, and no. 283 is in the 3rd
for the VLC’s AlarmF1, zone no. 268 is displayed on the LCD.
Figure 13: Zone display on LCD when multiple zones are configured
6.22.2. Continuous
All outputs belonging to the zones for which this attribute is programmed activate as “Continuously ON”.
All outputs with NAC type classifications belonging to these zones CANNOT be deactivated/silenced by press-
ing the SILENCE switches of FACP and LCD-RA.
6.22.3. 60 pulse
All outputs with NAC type classifications belonging to the zones for which this attribute is programmed activate
at “60 pulses per minute”. Outputs with any other type classifications belonging to these zones activate as
“Continuously ON”.
This attribute is used for suppression zone interlocking. (See section 6.15.4. for suppression zone interlocking.)
All outputs with NAC type classifications belonging to these zones CANNOT be deactivated/silenced by press-
ing the SILENCE switches of FACP and LCD-RA.
*Note: Outputs of addressable modules are activated as “Continuously ON” regardless of the 60 pulse attribute
setting.
6.22.5. Suppression
This attribute is used only for establishing a suppression zone. See section 6.23.4. for details of suppression
zones.
All outputs with NAC type classifications belonging to these zones CANNOT be deactivated/silenced by press-
ing the SILENCE switches of FACP and LCD-RA.
6.22.6. No Attribute
All the outputs belonging to the zones for which this attribute is programmed activate as “Continuously ON”.
All outputs with NAC type classifications belonging to these zones CAN be deactivated/silenced by pressing the
SILENCE switches of FACP and LCD-RA.
When multiple zones have been configured for a threshold, module, or output, their operation shall be based on
following ranking of priorities.
Suppression > 120 pulse > 60 pulse > Continuous > System NAC Code Type > No Attribute
*Note: •The zone attribute of IP zones is fixed as “System NAC Code Type”.
•The zone attribute of Z000 is fixed as “System NAC Code Type”.
6.23. Interlocking
6.23.1. Interlocking by conventional zones
As mentioned in the above section, a conventional zone is an area consisting of one or more addressable
devices connected to a FACP. Up to 501 conventional zones (i.e. Z000 to Z500) are configurable per system/
FACP.
In a conventional zone, activation of any addressable input device interlocks/activates all addressable output
devices within the same zone.
In this case, the wet and dry outputs of the MCU are included as addressable output devices.
Interlocked
Active (Alarm)
OD
ID
ID: Addressable input device
ID OD: Addressable output device
Interlocked OD
OD
ID
ID
Interlocked
Same zone
As multiple zones can be configured for the Alarm level of analog detectors and the AlarmF1 level & the AlarmF2
level of the VESDA LaserCOMPACT LP, interlocking is available as shown in Figure 15 below.
*Note: The addressable module input type does not make any zone-interlocking when any of classifications
Silence, Drill, and System Reset is configured.
Active (Alarm)
Interlocked
Interlocked
ID
OD
Interlocked
OD
ID ID
OD
ID
Zone 1 Zone 2
Except the limitations of zone setting per addressable device in section 6.21.2., any number of addressable
devices can be configured in a zone. However, only 1 unit of addressable module for initiating device for which
alarm verification time has been configured can be configured per zone. (See section 6.24.)
Active (Alarm)
Interlocked
Input zone Analog smoke
014 detector 1035
Active (Alarm)
*Note: (1) Addressable input devices in output zones are completely unaffected by any cross zone interlocking
that may occur.
(2) Alarm verification time shall not be configured for any addressable module for initiating device in
input zones. (See section 6.24.)
A maximum of 10 sets of cross zones are configurable per system/FACP. A maximum of 5 zones can be
programmed for output zones per set.
Active (Alarm)
Interlocked
Analog smoke
detector 1028
Wet output type
Input zone
module 1067
021
Active (Alarm)
*Note: (1) Addressable input devices in output zones are completely unaffected by any counting zone interlocking
that may occur.
(2) Alarm verification time shall not be configured for any addressable module for initiating device in
input zones. (See section 6.24.)
A maximum of 10 sets of counting zones are configurable per system/FACP. Input zones can be configured with
count numbers ranging from 1 to 5. Up to 5 zones can be programmed for output zones per set.
Bell Circuit in
suppression zone
120 pulse Continuously ON
Horn Circuit in
suppression zone
Continuously ON
Strobe Circuit in
suppression zone
Power Shutdown in
suppression zone
HVAC Shutdown in
suppression zone
Timer expiry
1) The output device with “Bell Circuit” classification is activated at 60ppm upon receiving the 1st active signal in
the input zone.
• In the case of a counting zone, the output device with “Bell Circuit” classification belongs not only to the
output zone but also to the input zone. (See Figure 19 below.) In the meantime, the zone attribute of the
input zone shall be 60ppm.
ID ID
Horn Circuit
Release Circuit
Bell Circuit Strobe Circuit
HVAC Shutdown
Power Shutdown
In the case of a cross zone, the output device with “Bell Circuit” classification belongs not only to the output zone
but also to two input zones. (It belongs to three zones in total.) (See Figure 20 below.) In the meantime, the zone
attribute of the input zones shall be 60ppm.
ID ID
Horn Circuit
Release Circuit
Bell Circuit Power Shutdown
HVAC Shutdown
Strobe Circuit
ID
ID
2) The following steps (1) to (6) are implemented in a suppression zone (i.e. output zone) upon receiving the 2nd
active signal in the same zone in the case of a counting zone, or an active signal from another zone in the
case of a cross zone.
(1) The output with “Bell Circuit” classification is deactivated.
(2) The output with “Power Shutdown” classification is activated.
(3) The output with “HVAC (i.e. Heat, Ventilation, Air Conditioning) Shutdown” classification is activated.
(4) Outputs with “Release Circuit” classification and Blank Classifications with suppression type classifica-
tion are activated.
(5) The output with “Horn Circuit” classification is activated as “Continuously ON”.
(6) The output with “Strobe Circuit” classification is activated.
3) If delay times have been programmed for outputs with “Release Circuit” classification and for Blank Classifi-
cations with suppression type classification, those outputs are not activated, and therefore the delay timers
are started. Also, the above steps (5) and (6) are not implemented, and instead, the following operation is
performed.
(7) The output with “Horn Circuit” classification is activated at 120ppm.
While the delay timers are operating, the abort activation function (see section 6.32. for details) is
effective.
4) When the delay timers for outputs with Release Circuit” classification and Blank Classifications with suppres-
sion type classification have expired, the following operations are implemented.
(8) Outputs with “Release Circuit” classification and Blank Classifications with suppression type classifica-
tion are activated.
(9) Activation of the output with “Horn Circuit” classification is changed from 120ppm to “Continuously ON”.
(10) The output with “Strobe Circuit” classification is activated.
*Note: 1) Outputs with “Bell Circuit” and “Horn Circuit” classifications must be the MCU’s wet outputs, MCU’s
dry outputs, OCU-W’s wet outputs, or OCU-D’s dry outputs. Wet and dry output type addressable
modules are NOT operated as described above.
2) Any outputs other than the above mentioned classifications are activated as “Continuously ON”.
Active (Alarm)
FACP FACP
ID
No. 1 No. 2
Network Interlocked
FACP
OD
No.4
FACP ID: Addressable input device
No.3 OD: Addressable output device
Same IP zone
*Note: The zone attribute of any IP zone is fixed to the “System NAC Code Type” described in section 6.22.1.
The interlocking of IP zones is, for example, used for activating notification appliances on floors above and
below the alarm floor when multiple FACPs have been installed in multiple floors. (See Figure 22 below.)
Interlocked
Active (Alarm)
th
15 floor: Alarm floor FACP
ID
No. 6
Interlocked
FACP
14th floor: Lower floor OD
No.5
Same IP zone
However, it is necessary to divide carefully the addressable input devices and addressable output devices when
IP zones are configured vertically as in Figure 22 above.
Conv. zone A
16th floor FACP
OD ID
No.7
Conv. zone B
Conv. zone C
14th floor OD ID
IP zone A
If IP zones are configured as in Figure 23 above, the conventional zones are not effective, as IP zone A encom-
passes all of them. Therefore, when IP zones are configured vertically, addressable input devices and addres-
sable output devices shall be divided as shown in Figure 24.
IP zone A
Conv. zone A
ID OD
17th floor
Conv. zone B
Conv. zone C
Conv. zone D
14th floor OD ID
IP zone B
13th floor
Conv. zone E
ID OD
Conv. zone F
Using the features of IP zones, it is also possible to configure IP zones horizontally just like conventional zones.
(See Figure 25 below.)
Conv. zone A
FACP
ID OD ID OD
No. 6
IP zone A
Conv. zone B
FACP
ID OD ID OD
No.5
The addressable output devices in an IP zone can be reset by the SYSTEM RESET switch of an FACP to which
the devices are directly connected or the SYSTEM RESET switches of FACPs which have the same group
number as that of the FACP. (See section 6.40.1. for grouping.)
Interlocked Interlocked
OD ID ID OD
OD ID
Active (Alarm)
Interlocked
OD ID ID OD
OD ID
Interlocked
Zone 000
Figure 27: Interlocking by activation of addressable input device in a conventional zone with Z000
60 seconds (fixed)
Time
A B C D
• Point A: Alarm verification starts upon receipt of an active signal from the addressable module for initiating
device (i.e. when conventional smoke detectors, connected to the addressable module, initiate
an active signal upon detecting smoke).
• Point B: The addressable module is reset after a fixed time passes. The conventional two-wire smoke
detectors are reset by turning off power to them (i.e. the conventional detectors resume monitoring).
• Point C: Alarm verification confirmation is started.
• Point A to C: A fire alarm signal is not initiated during this period. The time from A to C is the alarm verification
time (i.e. 30 seconds or 55 seconds) value that is configured in the FACP. The time from A to C is
called the Alarm Verification Period.
• Point C to D: During alarm verification confirmation, an alarm signal is initiated and the alarm verification
management is ended as soon as an active signal is received from the same address as the
addressable module.
An alarm signal is also initiated by the addressable module when an alarm signal is received from
another addressable device.
The time from C to D is called the Confirmation Period. The period is fixed at 60 seconds.
• Point D: During the confirmation period, if no active signal is received, the alarm verification management
is ended at point D.
If an active signal is received from an addressable module for initiating device after alarm verification management
has already been ended, alarm verification is restarted from the beginning (i.e. Point A).
Note that the following items are stipulated in NFPA72 and UL standards.
1) Alarm verification shall not be applied to heat detectors and waterflow detectors (i.e. Waterflow Monitor in the
Integlex system.)
2) Smoke detectors for which alarm verification has been configured shall neither be used in a counting zone nor
cross zone for activating suppression systems.
Due to system functionality, only one addressable module for initiating device for which alarm verification has
been configured shall be used per zone. Use of multiple addressable modules for initiating device with an alarm
verification feature is prohibited within a zone.
(A single addressable module for initiating device is able to have a maximum of 20 units of two-wire smoke
detectors. Therefore, although it depends on the height of the site, it may be possible to monitor 20,000ft2 with
a single addressable module for initiating device.)
For analog detectors, according to the application site conditions, alarm verification times in the range of 5 to 55
seconds can be configured.
1. Code 3
A=0.5 sec
0.5 sec 0.5 sec 1.5sec 0.5 sec 0.5 sec 1.5sec 0.5 sec 0.5 sec
2. March Time
A=0.25 sec
B=0.25 sec
T=0.5 sec
T x 120=60 sec (i.e. There will be 120 on/off changes per minute.)
3. California
10 sec 5 sec
4. Two-Stage
A=1.5 sec
Continuously ON
B=1.5 sec
5 minutes
5. Continuous
Continuously ON
These NAC codes are applicable to the following classifications and blank classifications with NAC classification
type in the Integlex system.
•NAC type classifications: Control Output, Bell Circuit, Horn Circuit, Strobe Circuit, Audible Circuit, Speaker Circuit,
Release End Bell, and Release Audible
*Note: 1) If the “System NAC Code Type” attribute is not configured for a zone (see section 6.22.1.), the outputs
with these NAC type classifications belonging to the zone are not activated according to the selected
NAC code.
2) The outputs of addressable modules, both wet and dry output types, activate as “Continuously ON”
regardless of the configuration of NAC codes. Therefore, notification appliances that possess NAC
code activation functionality must be used if the notification appliances connected to addressable
modules have to be activated according to the selected NAC code.
6.26. Pre-signal
The pre-signal function delays the activation of outputs with NAC type classifications.
Pre-signal can be enabled or disabled for each addressable output device with NAC type classification.
The delay is implemented using a dedicated timer. The configurable time range of the pre-signal timer is 0, or 60
to 180 seconds per FACP/system. A pre-signal timer can be applied to each address.
The pre-signal timer is started not only by Alarm, AlarmF1, and AlarmF2 signals but also by Alert, Action, and
Active signal of input type addressable module if any interlocking with addressable output devices having NAC
type classifications were configured for those signals.
When the pre-signal timer is cancelled, intended addressable output devices are activated when any of following
conditions occurs.
1) If there is an Alarm or AlarmF1 at any address or zone after the pre-signal timer is started.
2) If there is another interlocking reason/factor for addressable outputs with NAC type classifications at any
address or zone.
In this case, the addressable output devices with NAC type classifications, which are interlocked with this
interlocking reason/factor, are activated immediately even if pre-signal enable setting has been configured for
them. (i.e. The pre-signal timer does not start.)
*Note: The pre-signal timer for the address which was cancelled or expired is not restarted until the system is
reset.
3) Operating the DRILL switch for Drill On.
While the pre-signal timer is counting, if the SILENCE switch is operated to switch Silence ON, the counting of
the timer is paused. Timer counting is resumed from the paused moment by operating the SILENCE switch to
Silence OFF.
Activated
Addressable input
device
Zone 335
Addressable output
device with NAC Activated after the configured
type classification pre-signal time (60 to 180
seconds)
Activated
Addressable input
device
Zone 226
Addressable output
device with NAC
type classification
Activated
Addressable input
device
Activated
Addressable input
device
Zone 188
Addressable output Activated, but deactivated after
device with NAC the configured auto silence
type classification time (600 to 900 seconds).
Activated
Addressable
input device
Zone 456
Addressable Activated after the configured
output device delay time (1 to 60 seconds).
Addressable Activated
input device
Zone 047
Addressable Activated only for the configured
output device soak time (1 to 999 seconds).
Interlocking Activated
reason/factor
Zone 273
Zone 273
Zone 273
Zone 092
Interlocking Activated
reason/factor
Zone 441
Zone 441
Zone 441
*Note: (1) Maximum 4 seconds shall be required for FACP to detect the Abort switch activation.
(2) The “Abort” function is not available in IP zones.
Activated
Addressable Addressable input
input device device with second shot
Activated
Activated
Addressable input device
with manual release
Zone 391
Addressable output device Activated immediately even if the
with suppression type delay time has been configured.
classification
Activated
Interlocking
reason/factor
Interlocking
reason/factor
Group 0
Events of all groups
can be displayed and
controlled. (i.e. Events
of FACP 1, 2, 3, and
4 in this case.)
FACP 1
Group 1
FACP 2
Events of only
FACP 2 can be
displayed and
SIU NohmiNET FACP 3 Group 2
FACP 4
SMP
*Note: (1) Each node shall belong to a group. However, a node cannot belong to multiple groups.
(2) A maximum of 64 groups can be configured on a network. The available group numbers are 0 to 99.
Any desired 64 numbers within that range can be used. The group numbers to be used may not be
consecutive, so that undesired numbers can be skipped. (E.g. Group numbers to be used: 0, 1, 4, 6,
7, 11, 14, 20, 33, 34, 47, 58, 66)
(3) The event display and operation of control switches of LCD-RA are same as those of the FACP to
which the LCD-RA is connected.
(4) Details of trouble events are not shared among FACPs, even in the same group. When a FACP has
some type of trouble, only a general trouble signal is sent from that FACP to other FACPs in the
same group and to group 0.
In the meantime, the SMP in the same group is able to receive details of trouble events.
7. Stipulations of NFPA
The following items are stipulated by the National Fire Code of the NFPA.
7.4.1. Local
The fire alarm system monitors only a building as shown in Figure 43 below. 24 hours of standby power is
required.
Fire alarm
system
Building
7.4.2. Auxiliary
The functionality of this system style is the same as that of the “Local” style except that there is an additional
Master Box(*). 60 hours of standby power is required.
*Note: The Master Box is a manual fire alarm device that is connected to the fire department, and is typically
located in public streets in North America.
Building
Fire alarm
DACT DACR
system
Fire alarm
DACT
system
Restaurant (CSPPU)
Security company, etc.
CSRU
Fire alarm
DACT DACR
system
Fire alarm
DACT
system
School (CSPPU)
End-of-line resistor
10k ohm,1/2W
(FZE019-10)
EOL resistor
10k ohm,1/2W
(FZE019-10)
Required in Style Z
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by the following formula.
Formula: Rmax (ohm) = (24V - Vmin)/It
Vmin : Minimum operation voltage of connected notification appliance (V)
It : Total operating current of connected notification appliances (A)
End-of-line device
R=10k ohm Releasing device
(FZE019-10D)
End-of-line device
R=10k ohm Releasing device
(FZE019-10D)
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by the following formula.
Rmax (ohm) = (24V - Vmin - VR)/It
Vmin : Lowest operable voltage of connected devices (V)
VR : Forward voltage of diode in end-of-line device (i.e. 0.95V)
It : Total operating current of connected devices (A)
When these outputs are used for Trouble Status (i.e. status zone 702), the contact operation is reversed as
shown in Figure 51 below.
NO COM NC NO COM NC
TB1 (Dry 1) TB1 (Dry 1)
No trouble Trouble
condition condition
S+ S+
S- S-
S+ S+
S- S-
FRR01U-SS
S+
S- S+
S+ S-
S- S+
S-
FRR01U-DA
FRR01U-F FRR01U-SL
Area B Area C
S+
S-
S+
S-
FRR01U-M
8
Detector base FZB01U-N or FZB02U-N used
for installing analog detectors FDK38U,
FDL25U, and FDPL25U
Area A
*Note: •The maximum wiring resistance including branch wiring shall be less than 25 ohms in total.
7Example: Area A plus area B equals or is less than 25 ohms.
Area A plus area C equals or is less than 25 ohms.
•The maximum capacitance between wires including branch wiring shall be 0.4 micro F in total.
S+ S+
S- S-
S+ S+
S- S-
FRR01U-DA FRR01U-SS
S+ S+
S- S-
S+ S+
S- S-
FRR01U-F FRR01U-SL
S+
S-
S+
S-
FRR01U-M
8
Detector base FZB01U-N or FZB02U-N used
for installing analog detectors FDK38U, FDL25U
and FDPL25U.
*Note: •The maximum wiring resistance shall be less than 25 ohms in total.
•The maximum capacitance between wires shall be 0.4 micro F in total.
S+2
S+2
S-2
S-2
S+1
S+1
S-1
S-1
S+
S-
S+
S-
FQI01U
FRR01U-SS
S+
S-
S+
S-
S+1
S+1
FRR01U-DA
S-1
S-1
S+2
S+2
S-2
S-2
S+2
S+2
S-2
S-2
FRR01U-SL
S+1
S+1
S-1
S-1
FQI01U FQI01U
S+
S-
S+ S+
S- S-
S+
S-
S+2
S+2
S-2
S-2
FRR01U-F
S+1
S+1
S-1
S-1
S+1
S+1
S-1
S-1
FQI01U
S+2
S+2
S-2
S-2
6
FQI01U
8
Detector base FZB01U-N or FZB02U-N
used for installing analog detectors S+
S-
FDK38U, FDL25U, and FDPL25U. S+
S-
FRR01U-M
S+1
S+1
S+2
S+2
S-2
S-2
S-1
S-1
S+1
S+1
S-1
S-1
S+2
S+2
S-2
S-2
FQI01U FQI01U
*Note: •The maximum wiring resistance between an SCI and another SCI shall be less than 10 ohms, and the
maximum total wiring resistance shall not exceed 25 ohms.
•The maximum capacitance between wires shall be 0.4 micro F in total.
•The line resistance is calculated defining 0.1 ohm per SCI.
TB2
+
-
+
-
TB1
+
-
+
-
ZIU-O
TB2
+
-
+
-
TB1
+
-
+
-
ZOCU
TB2
+
-
+
-
TB1
+
-
+
-
ZIU
+
-
24VDC(+)
+ TB3
-
24VDC(-)
+
- TB1
TB7 of MCU
1+ +
1- - TB2
RS-485 LCD-RA
Power limited
TD RD SG TD RD SG
Figure 56: Serial ports of MCU
Cables for these ports must be less than 15 meters in length in the same room where the ports are located.
Contact of device to
initiate the trouble signal
TR1
TR2
TB10
Figure 57: Connection of trouble input terminal
Cable for this terminal must be less than 15 meters in length in the same room where the terminal is located.
When EPSMs are used, in order to receive trouble signals from EPSMs, the wiring shall be made as following
figure.
TB10
TR1
MCU
TR2
TB7
T1
T2
EPSM#1
T1
T2
TB7
T1
T2
EPSM#2
T1
T2
Figure 58: Wiring between MCU’s trouble input and EPSMs’ trouble outputs
TB3
+
-
PSM
TB4 +
-
Devices listed in the “List of Compatible Devices with Wet Outputs for the Integlex fire alarm system” in the
Appendix of section 13 can be connected to the PSM’s two wet outputs. Check with Nohmi Bosai Ltd. or its
distributor in your country/region if any other devices are connected to the outputs.
TB3
EPSM TB4
TB5
TB6
Devices in the “List of Compatible Devices with Wet Outputs for the Integlex fire alarm system” in the Appendix
of section 13 can be connected to the wet outputs of EPSM. Check with Nohmi Bosai Ltd. or its distributor in your
country/region if any other devices are connected to the outputs.
*Note: The power for remote printer connected to the serial ports of MCU (i.e. Serial 1 and 2) shall not be
supplied from the wet outputs of EPSM.
TB1
RPA
Reverse polarity output
RPB
CTM MBA
MBB
*Note: When the Reverse Polarity output is used, the Secondary Protector for Communication Circuits (QVRG)
shall be used.
TB1
Solenoid
RPA
Coil voltage: 3.65V
RPB
CTM Coil resistance: 14.5 ohm
MBA
Operating current: 250mA
MBB
*Note: 1) The Master Box is a manual fire alarm device that is typically located in the city streets of North
America.
2) When the Reverse Polarity output is used, the Secondary Protector for Communication Circuits
(QVRG) shall be used.
TB1
RS485 +
2
HTM To ancillary systems
1 -
Devices in the “List of Compatible Devices with Wet Outputs for the Integlex fire alarm system” in the Appendix
of section 13 can be connected to the wet outputs of OCU-W. Check with Nohmi Bosai Ltd. or its distributor in
your country/region if any other devices are connected to the outputs.
B+
Wet 1 - 4
End-of-line resistor
TB1
-
10 K ohm,1/2W
A-
(FZE019-10)
B-
End-of-line resistor
10K ohm,1/2W
A-
+
24VDC(+) (FZE019-10)
B-
TB4
24VDC(-)
In the case of Style Z wiring
-
OCU-W
*Note: The end-of-line resistor is not required
in the case of Style Z wiring.
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by the following formula.
Formula: Rmax (ohm) = (24V - Vmin)/It
Vmin : Minimum operation voltage of connected notification appliance (V)
It : Total operating current of connected notification appliances (A)
A+
TB3
B+
Wet 1 - 4
TB1
-
A-
(FZE019-10D)
B-
A+
B+
Wet 5 - 8
TB2
24VDC(+) (FZE019-10D)
B-
TB4
24VDC(-)
-
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by the following formula.
Rmax (ohm) = (24V - Vmin - VR)/It
Vmin : Lowest operable voltage of connected devices (V)
VR : Forward voltage of diode in end-of-line device (i.e. 0.95V)
It : Total operating current of connected devices (A)
Audio Device
A+
TB3
B+
Wet 1 - 4
End-of-line resistor
TB1
-
10 K ohm,1/2W
A-
(FZE019-10)
B-
End-of-line resistor
10K ohm,1/2W
A-
+
(FZE019-10)
B-
TB4
AC Audio Power
OCU-W
*Note: The end-of-line resistor is not required
in the case of Style Z wiring.
Figure 66: Connection of audio devices to wet outputs of OCU-W
Devices in the “List of Compatible Devices with Wet Outputs for the Integlex fire alarm system” in the Appendix
of section 13 can be connected to the dry outputs of OCU-D. Check with Nohmi Bosai Ltd. or its distributor in
your country/region if any other devices are connected to the outputs.
NO COM NC NO COM NC
TB1 (Dry 1 - 4) TB2 (Dry 5 - 8)
1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G
TB1 TB2 TB1 TB2 TB1 TB2
Port A Port B Port A Port B Port A Port B
NIU in FACP SIU for SMP NIU in FACP
Node No.1 Node No.2 Node No.3
1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G
TB1 TB2 TB1 TB2 TB1 TB2
Port A Port B Port A Port B Port A Port B
NIU in FACP SIU for SMP NIU in FACP
Node No.64 Node No.5 Node No.4
1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G
TB1 TB2 TB1 TB2 TB1 TB2
Port A Port B Port A Port B Port A Port B
NIU in FACP NIU in FACP SIU for SMP
Node No.1 Node No.2 Node No.3
1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G 1+ 1- G 2+ 2- G
TB1 TB2 TB1 TB2 TB1 TB2
Port A Port B Port A Port B Port A Port B
NIU in FACP NIU in FACP SIU for SMP
Node No.64 Node No.5 Node No.4
When copper/metal cable is used, the distance between two nodes shall be less than 600 meters.
The G terminals of TB1 and TB2 on NIU shall not be used.
The following specifications shall be noted for wiring between FACPs.
•NEC FPLP, CMP, MPR, or FPLR cable (See section 9)
•Max. line resistance: Less than 72 ohms
•Max. static capacitance: Less than 80nF
•Characteristic impedance: 100±10 ohms
FRX
FRX
FRX
FRX
FRX
FTX
FTX
FTX
FTX
FTX
FTX
FRX
FTX
FTX
FRX
FRX
FRX
FRX
FTX
FTX
FTX
FTX
No. of Max. network length No. of Max. network length
FACPs [meter] FACPs [meter]
2 4,000 33 26,700
3 6,000 34 26,400
4 8,000 35 26,200
5 10,000 36 25,900
6 12,000 37 25,600
7 14,000 38 25,300
8 16,000 39 25,000
9 18,000 40 24,800
10 20,000 41 24,500
11 22,000 42 24,200
12 24,000 43 23,900
13 26,000 44 23,600
14 28,000 45 23,400
15 30,000 46 23,100
16 31,500 47 22,800
17 30,200 48 22,500
18 30,900 49 22,200
19 30,600 50 22,000
20 30,400 51 21,700
21 30,100 52 21,400
22 29,800 53 21,100
23 29,500 54 20,800
24 29,200 55 20,600
25 29,000 56 20,300
26 28,700 57 20,000
27 28,400 58 19,700
28 28,100 59 19,400
29 27,800 60 19,200
30 27,600 61 18,900
31 27,300 62 18,600
32 27,000 63 18,300
64 18,000
Table 9: Limitation for fiber optic network length
Conventional detector
To the next
To the next addressable device on the loop
addressable module
Power limited
24VDC(+)
24VDC(-)
M+
M-
S+ M+ 24VDC(+)
S- M- 24VDC(-)
S+ C
S- L
RC
RL
FRR01U-F
Figure 71: Connection of initiating devices and addressable module for initiating device in Style B
Conventional detector
24VDC(+)
24VDC(-)
M+
M-
S+ M+
24VDC(+)
S- M- 24VDC(-)
S+ C
S- L
RC
RL
FRR01U-F
Figure 72: Connection of initiating devices and addressable module for initiating device in Style D
Normally-open contact
End-of-line resistor
*Note: The resistance of external wiring relay or switch
56k ohm, 1/4W
shall be less than 50 ohm. (FZE019-56)
Power limited
C
A
S+
S-
S+
S-
FRR01U-DA
Figure 73: Connection of device and input type addressable module (normally-open contact)
•All wiring to be used shall be between AWG#14 (1.5mm2) and AWG#18 (0.75mm2).
C
B
S+
S-
S+
S-
FRR01U-DB
Figure 74: Connection of device and normally-closed contact input type addressable module
•All wiring to be used shall be between AWG#14 (1.5mm2) and AWG#18 (0.75mm2).
*Note: According to NFPA72 1999 edition, any fire alarm initiating devices shall not be connected to the
addressable module input type normally-closed contact.
8.17. Connection of manual station to addressable module for the manual station
Connection of an addressable module for a manual station shall be as shown in Figure 75 below.
Manual station
C
A
S+
S-
S+
S-
FRR01U-M
•All wiring to be used shall be between AWG#14 (1.5mm2) and AWG#18 (0.75mm2).
Devices listed in the “List of Compatible Devices with Wet Outputs for the Integlex fire alarm system” in the
Appendix of section 13 can be connected to the wet output. Check with Nohmi Bosai Ltd. or its distributor in your
country/region if any other devices are connected to the outputs.
End-of-line resistor
56k ohm, 1/4W
(FZE019-56)
24VDC(-)
M+
M-
S+ M+ 24VDC(+)
S- M- 24VDC(-)
S+ C
S- D
RC
RD
Figure 76: Connection of notification appliances and wet output type addressable module
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by following formula.
Formula: Rmax (ohm) = (24V - Vmin)/It
Vmin : Lowest operable voltage of connected devices (V)
It : Total operating current of connected devices (A)
*Note: The output of a wet output type addressable module is “Continuously ON” regardless of the System
NAC Code Type setting. Therefore, notification appliances which contain NAC codes activation shall
be used if NAC codes should be applied.
Releasing Device
Non-Power Limited
However, it is power limited if the power
supply to M+ and M- is power limited.
End-of-line device
R=56k ohm
(FZE019-56D)
24VDC(+)
24VDC(-)
M+
M-
S+ M+ 24VDC(+)
S- M- 24VDC(-)
S+ C
S- D
RC
RD
FRR01U-SL
Figure 77: Connection of releasing device and wet output type addressable module
The maximum wiring resistance [Rmax] shall be smaller than the value calculated by following formula.
Formula: Rmax (ohm) = (24V - Vmin - VR)/It
Vmin : Lowest operable voltage of connected devices (V)
VR : Forward voltage of diode in end-of-line device (i.e. 0.95V)
It : Total operating current of connected devices (A)
End-of-line resistor
56k ohm, 1/4W
(FZE019-56)
Audio device
Non-Power Limited
However, it is power limited if the power
supply to M+ and M- is power limited,.
*Note: is a condenser.
Audio device
M+
M-
S+ M+
AC audio power
S- M-
S+ C
S- D
RC
RD
Figure 78: Connection of audio devices and wet output type addressable module
B
C Contact rating: 30VDC 2.0A
To the next addressable A 125VAC 0.5A
device on the loop
B
C
A
S+
S-
S+
S-
FRR01U-SS
S+1 S+2
S-1 S-2
S+1 S+2
S-1 S-2
FQI01U
Figure 80: Short circuit isolator
*Note: Regarding the current consumption issue, the available number of addresses per loop changes depending
on whether short circuit isolators are used in the loop.
In the case of Style 7, it is required to deduct 1 address per SCI from the maximum number of addresses
of the loop (i.e. 255 addresses).
•Example: If 5 SCI modules are used in a loop, 250 addressable devices can be used in the loop. (i.e.
255 - 5 = 250)
In the case of Style 4, it is required to deduct 8 addresses per SCI from 255.
•Example: If 5 SCI modules are used, 215 addresses can be used. (i.e. 255 - (5 6 8) = 215)
FQI01U FQI01U
Up to 50 addressable Up to 50 addressable
devices can be devices can be
connected. connected.
FQI01U FQI01U
*Note: • A short circuit isolator is not mandatory to satisfy the requirements of Style 4.
• Resistance of the SCI’s secondary line (i.e. line after SCI) shall be less than 10 ohms.
• Up to 50 addressable devices can be connected in the secondary line (i.e. line after an SCI including
the line between two SCIs).
• The line resistance is calculated by defining 0.1 ohm per SCI.
FRR01U-SS,
FRR01U-F
FRR01U-DA,
or FRR01U-SL
or FRR01U-M
8
6
FDL25U, and FDPL25U.
S+
S+
S-
S-
S+
S+
S-
S-
S+2
S+2
S+1
S+1
S-2
S-2
S-1
S-1
S+1
S+1
S+2
S+2
S-1
S-1
S-2
S-2
Detector base FZB01U-N or FZB02U-N used for
installing analog detectors FDK38U, FDL25U,
and FDPL25U.
FQI01U FQI01U
FRR01U-SS,
FRR01U-DA, 8
or FRR01U-M
S+
S-
S+
S-
FRR01U-F
or
S+ FRR01U-SL
S-
S+ S-
S- S+
S-
FRR01U-F S+
or
FRR01U-SL
6
S-
S+
S-
S+
FRR01US,
8 FRR01U-DA,
or FRR01U-M
S+2
S+1
S+1
S-2
S-2
S-1
S-1
S+1
S+2
S+2
S-1
S-1
S-2
S-2
FQI01U FQI01U
*Note: • A short circuit isolator is not mandatory to satisfy the requirements of Style 6.
• Less than 50 addressable devices shall be connected between two SCIs. (See the areas enclosed by
dotted lines in Figure 82 above.)
• The wiring resistance is calculated by defining 0.1 ohm per SCI.
• The wiring resistance between two SCIs shall be less than 10 ohms.
S+2
S+2
S-2
S-2
S-1
S+1
S-1
S+1
S+1
S+1
S-1
S-1
S+2
S+2
S-2
S-2
FQI01U
FQI01U
S+2
S+2
S-1
S+1
S-1
S+1
S-2
S-2
S+1
S+1
S+2
S+2
S-1
S-1
S-2
S-2
FQI01U FQI01U
*Note: •The line resistance between two SCIs shall be less than 10 ohms.
•The line resistance is calculated by defining 0.1 ohm per SCI.
1 2 8 C1 9 10 16 C2
TB4 + + + - TB5 + + + -
17 18 24 C3 25 26 32 C4
TB6 + + + - TB7 + + + -
CN1
TB4 TB5
TB1
ZIU-O
TB3
OPT-BS
TB2
CN1
TB6 TB7
CN2
CN2
CN2
OPT-BS
OUT
OUT
OUT
IN
IN
IN
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
CN1
TB3
TB3
TB3
1
1
2
3
4
*Notes: •All the wiring in above figure shall be made in the same enclosure.
•The power to all ZIU-Os shall be supplied from the same source.
SIU
PGMnet
Dedicated cable (5 meters)
Dsub 9-pin
IEC320/3-pin
AC inlet
PC (SMP)
120V/240VAC
9. Wiring
9.1. Stipulations of the National Electric Code (NEC)
All wiring for the Integlex fire alarm system shall be based on following classifications of NEC.
MPP
CMP
CL3
FPLP
PLENUM
CL2P
MPR
CMR
CL3R
RISER FPLR
CL2R
MPG
MP
PLTC
GENERAL CMG
CM FPL
PURPOSE CL3
CL2
CMX CL3X
DWELLINGS
CL2X
Figure 88: Cable Type Hierarchy National Electric Code (NEC) 1999
*Note: In above hierarchy, “j9h ” means that the cable j is acceptable as a substitution for the cable h.
[Cable types]
•CM: Communications wires and cables
•CL2 and CL3: Class 2 and 3 remote-control, signaling, and power-limited cables
•FPL: Power-limited fire alarm cables
•MP: Multipurpose cables
•PLTC: Power-limited tray cables
These addressable modules and SCI can also be installed directly onto plates as shown in Figures 91 and 92
below. Therefore, according to the application site conditions, some addressable modules and SCI may be
installed together in large electric boxes.
Total = Amps
Total = Amps
*Note: Examples of an Auxiliary power supply as listed in the above tables would be power “extender” supplies for
NAC circuits. These devices provide additional 24 VDC power for NAC circuits and need to be included in
the AC power supply requirements.
The system’s 24 VDC power consumption depends on the total amount and type of system devices installed.
Upon determination of system 24 VDC power requirements, battery capacity can be specified. See section 12 for
the battery capacity calculations.
Battery Calculation
Monitoring time (hours) [ ](C)
Alarm time (minutes) [ ](D)
Battery Capacity (AH)=1.26((A6C)+(0.0167(B6D))/1000= [ ] AH
*Note: 1) The value "0.77" in above formulas came from the efficiency of Integlex loop.
2) In the case of Style 4, 8 addresses are automatically consumed per short circuit isolator. Therefore, it is
required to multiply the quantity of short circuit isolator by 8 when the total quantity of addressable
device is checked. (255 is the maximum address capacity in any way.)
*Note: 1) The value “0.77” in above formulas came from the efficiency of Integlex loop.
2) In the case of Style 4, 8 addresses are automatically consumed per short circuit isolator. Therefore, it is
required to multiply the quantity of short circuit isolator by 8 when the total quantity of addressable
device is checked. (255 is the maximum address capacity in any way.)
13. Appendix
INTERNATIONAL DIVISION
Shinjuku Park Tower 10th Floor, P.O. Box 8155, 7-1, Nishi-Shinjuku 3-chome
Shinjuku-ku, Tokyo 163-1010, Japan
www.nohmi.co.jp
Document No:ITN00-001 1