Академический Документы
Профессиональный Документы
Культура Документы
20mA
Part No. 2390710
GAMMA series
Active current measuring
Analog output 4...20mA
Suitable for VFI (10 to 400Hz)
Zoom voltage 24V to 240V d.c. and 48V to 240V a.c.
Width 22.5mm
Industrial design
Technical data
1. Functions 5. Output circuit
Active current measuring with analog output 4 ... 20mA and the following 1 analog output 4...20mA
settings (selectable by means of rotary switch): Terminals: X1(+) - X2(-)
Settling time: <1s
Zero setting of zero point Burden: max. 500W
(0%, 25%, 50%, 75% of nominal value) Galvanic isolation: 3kV d.c.
Zero Fine fine setting of zero point
(0% ... 25% of nominal value) 6. Measuring circuit
Span span Measuring range IN: 5A, 10A and 15A selectable
(100%, 75%, 50%, 25% of nominal value) Measuring input: current; terminals i-k
Range measuring range reversible between Wave form: optional
5A, 10A, 15A Frequency range: 10 to 400Hz
Overload capacity: 20A permanent
2. Indicators Input resistance: <10mΩ
Green LED U ON: indication of supply voltage Overvoltage category: III (in accordance with IEC 60664-1)
Yellow LED‘s: indication of measured value Rated surge voltage: 4kV
www.tele-online.com
G2IA15A 4...20mA
Part No. 2390710
Functions Connections
L
Zero = 0% / Span = 25% ; Zero = 0% / Span = 100%
N
I OUT
[mA]
20
i k A1
Span 25%
Span 100%
I X1 X2 A2
25% 50% 75% 100%
IN
Load
4...20mA
Zero = 25% / Span = 25% ; Zero = 25% / Span = 75%
L1
I OUT
N
[mA]
20
Span 75%
Span 100%
Span 25%
i k A1
I
25% 50% 75% 100%
IN
X1 X2 A2
I OUT
[mA]
20
Dimensions
Span 50%
Span 100%
I
25% 50% 75% 100%
IN
37,5% 87,5%
RELEASE 2017/01
www.tele-online.com