TABLE: By PPWSA
Ability to provide water per Ability to provide water per
Item Water meter
1hr 1day
1 Dia. 15mm 1.5m3 to 3m3 36m3 to 72m3
2 Dia. 20mm 2.5m3 to 5m3 60m3 to 120m3
3 Dia. 25mm 3.5m3 to 3m3 84m3 to 168m3
4 Dia. 30mm 6m3 to 12m3 144m3 to 288m3
5 Dia. 40mm 10m3 to 20m3 240m3 to 460m3
6 Dia. 80mm 40m3 to 80m3 960m3 to 1920m3
7 Dia. 100mm 60m3 to 120m3 1440m3 to 2880m3
8 Dia. 150mm 150m3 to 300m3 3600m3 to 7200m3
I. Domestic water tank
Volume required per day Volume required per 2days
(water usage) (water usage)
Domestic water tank 7 m3 14 m3
Water flow required Dia.40mm (SEE TABLE: By PPWSA) to fil 14m3 for using 2days
Pipe diameter required Dia.OD50mm
II. Fire tank
Volume required per 2h
Tank volume
(fire operation)
133 m3 Can store only 100 m3
Fire tank To fil water more into fire tank while fire
To fil 33m3 more
pump is running for 2hr operation.
Water flow required Dia.80mm (SEE TABLE: By PPWSA) to fil 33m3
Pipe diameter required Dia.OD90mm
III. Domestic water tank and Fire tank
Volume required per 2days Volume required per 2h
Tank volume
(water usage) (fire operation)
Domestic water tank 14 m3
Can store only 100 m3 To fil water more into fire tank while
Fire tank 133 m3
To fil 33m3 more fire pump is running for 2hr operation.
Water flow required Dia.80mm (SEE TABLE: By PPWSA)
Pipe diameter required Dia.OD90mm