Accuracy Class of Current Transformer


April 29, 2020 by admin

Accuracy Class of Current Transformer (CT) is defined in Indian Standard IS 2705 Part-2 and
Part-3. This accuracy class of CT is defined so as to provide the permissible error in the current
measurement of CT.

As we know that, there are three types of errors defined for a CT: Current Error (or Ratio Error),
Phase Angle Error and Composite Error. Thus, the accuracy class of CT must be defined using
these errors. The accuracy class of protection class and metering class CTs are defined by
Composite Error and Current Error & Phase Angle Error respectively. Let us now discuss the
accuracy class of Protection Class and Metering Class CT individually.

Accuracy Class of Metering CT:

As per IS 2705 Part-3, the accuracy class of metering CT is defined by the maximum
permissible current error at the rated current. Standard Accuracy Class of Metering CT are 0.1,
0.2, 0.5, 1, 3 and 5. Each of these class have different maximum permissible current error. Let
us now have a look at errors specified for these accuracy classes:

Limit of Error for Standard Accuracy Classes 0.1, 0.2, 0.5 and 1:

The limiting error shall not exceed the value tabulated below at rated frequency and burden
from 25% to 100% of the rated burden.

https://electricalbaba.com/accuracy-class-ct/ 1/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

Limit of Error for Standard Accuracy Classes 3 and 5:

The limiting error shall not exceed the value tabulated below at rated frequency and burden
from 50% to 100% of the rated burden. It shall be noted that phase displacement error is not
defined for these accuracy class.

Special Application Metering CT:

Special application metering CTs are a special category in which it is desired that the CT should
accurately measure the current from 1% to 120% of the rated current. If the secondary rated
current is 5A, this meter shall measure current from 50 mA to 6A accurately. This type of CT is
used for revenue meters and in energy meters.

Two accuracy classes 0.2S and 0.5S has been defined in IS 2705. These classes are only
applicable for rated secondary current of 5A and for the ratio 25/5, 50/5 and 100/5 and their
decimal multiples.

Limit of Error for Standard Accuracy Classes 0.2S and 0.5S:

The limiting error shall not exceed the value tabulated below at rated frequency and burden
from 25% to 100% of the rated burden.

https://electricalbaba.com/accuracy-class-ct/ 2/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

Accuracy Class of Protection CT:

Accuracy Class of Protection Current Transformer (CT) is defined by the maximum permissible
Composite Error at the rated accuracy limit primary current followed by letter “P” (meaning
protection). Here, accuracy limit primary current is the value of primary current corresponding to
Accuracy Limit Factor (ALF).

The standard accuracy classes for protection current transformer are 5P, 10P and 15P. 5, 10
and 15 in these classes are the maximum composite error corresponding to accuracy limit
primary current.

Limit of Error for Accuracy Classes 5P, 10P and 15P:

The current error (or ratio error), phase displacement error and composite error, at rated
frequency and rated burden, shall not exceed the values tabulated below:

On the name plate of Current Transformer, rated accuracy limit factor is indicated following the
corresponding output and accuracy class. For example, on name plate of CT, you may find 30
VA, 5P10 or 30/5P10. This marking means that, the burden of CT is 30 VA and the maximum
composite error at 10 times of rated current is 5%. Here, accuracy limit factor is 10.

https://electricalbaba.com/accuracy-class-ct/ 3/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

 Measurement and Instrumentation


 Current Transformer
 Composite Error of CT – Definition, Calculation & Formula
 Can Protection CT be used as Metering CT & Vice Versa?

Leave a Comment

Name *

Email *

Website

 Notify me when new comments are added.

Post Comment

Topics

Power System
Power System Protection
https://electricalbaba.com/accuracy-class-ct/ 4/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

Electrical Machines
DC Machine
Measurement and Instrumentation
AC Circuit
Digital Electronics
Electrical Drives
Power Electronics
EM Theory

Recent Posts

RTD Sensor
Voltage Commutated Chopper Explained
Types of Chopper Explained
Four Quadrant Chopper or Class-E Chopper
Class-D or Type-D Chopper Explained

Subscribe to our mailing list and get interesting stuff and updates to your email
inbox.

Your Email Please

I consent to my submitted data being collected via this form*

https://electricalbaba.com/accuracy-class-ct/ 5/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

SUBSCRIBE NOW

we respect your privacy and take protecting it seriously

https://electricalbaba.com/accuracy-class-ct/ 6/7
6/13/2020 Accuracy Class of Current Transformer | Electrical Concepts

© 2020 Electrical Concepts • Powered by GeneratePress

https://electricalbaba.com/accuracy-class-ct/ 7/7

Вам также может понравиться