Indicating Devices
Features
■ Solid metal enclosure
■ NEMA 4 / IP 55 watertight and dust proof - For indoor
or outdoor use
■ 17 bar (250 psi) system pressure rated [1] [2]
■ One SPDT or two SPDT version for DPDT action
■ Global approvals
[3]
■ Reliable and dependable device
[7]
Approvals
■ UL Listed
■ FM Approved [6] [4]
■ VdS Approved [5]
■ LPC Approved
■ CE Certified
Materials
■ Wetted parts: Thermo plastic, corrosion resistant
■ Cover: Die Cast Aluminum with textured red powder coat finish
■ Base: Zinc-plated Steel
Technical Data
Pressure Rating
■ 17 bar (250 psi) P
Pressure Setting & Ronge
■ Model PS10 H
❏ Factory set: +/- 1.0 bar (15 psi)
❏ Adjusting range: 0.3 - 1.4 bar (4 to 20 psi)
❏ Deadband: 0.13 bar (2 psi) typical 12 mm (1/2”)
Electrical Ratings Conduit Hole
■ 15 Amps @ 125/250VAC
■ 2.5 Amps @ 30VDC
■ Single or dual SPDT (from C) L R
Enclosure Class C
■
NEMA 4 weather-proof IP 55 rated
Ambient Temperature mm inch
■
-40°C to 60°C (-40°F to 140°F)
Weight H 107.2 4.22
■ Approx. 0.60 kg (21 oz) P 73 2.87
L 63 2.48
Installation - Caution
C 96 3.78
An uninsulated section of a single conductor
should not be looped around the terminal to R 40.7 1.60
serve as two separate connections.
The wire must be severed, thereby providing
supervision of the connection in the event that
the wire becomes dislodged from under the
terminal. Typical Electrical Connections
N.C.
Note:
To prevent leakage, apply teflon tape sealant to male To N.O. Alarm COM COM To COM End Of
threads only. Power Device
N.C.
N.O.
N.C. N.O. Panel
N.C. N.O. Line
Resistor
Warning:
Local Alarm Style D (Class A) Style B (Class B)
Use of pipe joint cement may result in obstruction of the
Non-Supervised Supervised Loop Supervised Circuit
aperture and loss of signal.