In the optimising control system, the following control inputs are used:
• additive control signal to fuel flow, if/fuel,add
• additive control signal to feedwater flow, rhfw,add.
The following controlled output variables are used:
• control error on outlet steam pressure, Psh3,err
• control error on steam temperature after superheater lb, Tshlb,err
• evaporator temperature, Teva.
Feedforward control and parameter scheduling are introduced using the boiler load
demand PB.
Eleventh-order linear state space models of the following form are the basis for
the controller design:
for the operating points JsKv2 = {115 MW, 130 MW, 187 MW, 240 MW} = {43%,
49%, 71%, 91%}. The load range to be covered was chosen so that the normal operat-
ing range is covered. The number of load points (four) was chosen to be the minimum
possible while allowing for the non-linear dynamic behaviour of the combined boiler
and existing control system. The distribution was not chosen to be equally spaced
because of dedicated load intervals for start/stop of coal mills.
The models were estimated from SKV2 data (PRBS excitation of control-
lable inputs (u : Uadd) and ramps in boiler load demand (d = PB)) using
the N4SID, subspace system-identification method (Van Overschee and Moor, 1994;
MathWorks, 1995).