Maximum travel distance (A use, sprinkled): 250 feet (facility meets minimum
requirements)
• From the basement, the path of egress is less than 72” and does not meet
the requirements for A2nc.
• On the first floor, the existing front main entrance/exit door is 60” nominal
width.
o This door meets the A2r requirements,
o This door does not meet the A2nc requirements
• On the first floor, the existing rear egress door next to the bar is 72”. (two
36” nominal width doors)
o This door meets the A2r and A2nc requirements.
T H O M A S D O U G L A S
A r c h it e c t s I n c 196 Pleasant Street Northampton, MA 01060
phone: 413.585.0641
6. Synopsis:
For existing A2r use and existing seat count (106): The facility meets the
minimum requirements.
For existing A2r use and area calculation for occupancy (113): The facility meets
the minimum requirements.
For proposed A2nc use and area calculation for occupancy (229): The facility
does not meet the minimum code requirements because of inadequate toilet
fixture counts and inadequate egress (front door) width.
The basement level has further limitations: The path of egress is less than 72”
and does not meet the minimum requirements for A2nc
End of Document