GPH ISPAT LIMITED, CHITTAGONG - LIST OF PREMISES TO BE VENTILATED

ANNEXURE - II

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC
A EAF
Tube axial supply
VS-1 1 10000 30
Cable cellar ( The ventilation within 5° C over air fan
16.5 x 5.85 x
1 system of cable cellar for LF 8 ambient
4.5 Tube axial
VE-1 Transformer building included) temperature 1 9000 15
exhaust air fan

Tube axial supply


VS-2 2 20000 30
air fan
(17.85 x 8.5 + within 5° C over
2 Hydraulic room 6.95 x 3.5) x 70 ambient
6.25 temperature
Exhaust through
VE-2 1 Size 2000 mm x 1000 mm
gravity louver

Tube axial supply


VS-3 1 5000 20
EAF air fan
within 5° C over
Transformer 10.5 x 3.2 x
3 Fire fighting 8 ambient
Building - 6.25
temperature
Exhaust through
VE-3 1 Size 700 mm x 400 mm
gravity louver

Tube axial supply


VS-4 1 7000 30
air fan
within 5° C over
Water distribution valve stand air 11.7 x 5 x
4 11 ambient
room 5.15
temperature
Exhaust through
VE-4 1 Size 700 mm x 500 mm
gravity louver

within 5° C over
Tube axial supply
5 VS-5 Switchgear room (HVAC room) 9.1 x 5.7 x 5 8 ambient 1 7000 30
air fan
temperature

1
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Exhaust through
VE-5 1 Size 700 mm x 500 mm
gravity louver

within 5° C over
12.4 x 11.7 x Tube axial
6 VE-6 Transformer room 60 ambient 2 18000 20
8.55 exhaust air fan
temperature

Supply through Size 700 mm x 300


VS-7 2
air intake louver mm
within 5° C over
EAF Utilities
7 Water room 7.6 x 8.2 x 3.7 ambient
building
temperature
Tube axial
VE-7 1 4000 15
exhaust air fan

Scrap yard
building (SO- within 5° C over
Propeller type Free air
8 VE-8 1) near E-row Toilets 3.5 x 6 x 3.5 ambient 3 2000
Exhaust air fan delivery
between Col. temperature
1&2
Shift Office - 3
within 5° C over
along C-row Propeller type Free air
9 VE-9 Toilets 3.5 x 3 x 3.5 ambient 2 2000
between Col. Exhaust air fan delivery
temperature
16 & 17
Toilet Block
within 5° C over
along C-row Propeller type Free air
10 VE-10 Toilet 3.5 x 4 x 3.5 ambient 3 2000
between Col. Exhaust air fan delivery
temperature
6&7
Toilet Block
within 5° C over
along C-row Propeller type Free air
11 VE-11 Toilet 3.5 x 4 x 3.5 ambient 3 2000
between Col. Exhaust air fan delivery
temperature
13 & 14

Toilet Block
within 5° C over
along D' row Propeller type Free air
12 VE-12 Toilet 3.5 x 4 x 3.5 ambient 3 2000
between Col. Exhaust air fan delivery
temperature
11 & 11A

SMS crane AT D-E bay between col. Nos. 17.5 x 6.9 x within 5° C over Tube axial supply
13 VS-13 45 2 15000
substation 11 & 12 4.5 ambient air fan

2
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC
temperature
Tube axial
VE-13 2 13000 20
exhaust air fan

B LF
Tube axial supply
VS-14 _ _ _
air fan
Cable cellar (Considered under within 5° C over
14 cellar ventilation system of LF 7 x 7 x 3.8 7 ambient
Transformer building) temperature Tube axial
VE-14 _ _ _
exhaust air fan

Tube axial supply


VS-15 within 5° C over 2 5000 20
12.3 x 7.2 x air fan
15 Hydraulic room 13 ambient
5.1 Exhaust through
VE-15 LF temperature 3 Size 700 mm x 400 mm
gravity louver
Transformer
building Tube axial supply
VS-16 within 5° C over 1 5000 20
air fan
16 HV switchgear room 5.6 x 6.8 x 5 2 ambient
temperature Exhaust through
VE-16 1 4000 15
gravity louver
Tube axial supply
VS-17 within 5° C over 1 5000 20
air fan
17 HV room 6.4 x 3.85 x 5 2 ambient
temperature Exhaust through
VE-17 1 4000 15
gravity louver
within 5° C over
Tube axial
18 VE-18 Transformer room 7.2 x 10 x 5 20 ambient 2 7000 20
exhaust air fan
temperature
Tube axial supply
VS-19 20 sqm x 5 5 within 5° C over 1 5000 20
air fan
19 Laboratory Sample Preparation room ambient
temperature Tube axial
VE-19 1 4000 15
exhaust air fan
C Foundation Meltshop
Tube axial supply
VS-20 within 5° C over 1 6000 20
air fan
20 Winch house 8 x 7.5 x 4.7 ambient
temperature Exhaust through
VE-20 Building and 1 Size 700 mm x 500 mm
gravity louver
support
inclined hoist Tube axial supply
VS-21 within 5° C over 1 5000 20
4.2 x 5.5 x air fan
21 Hydraulic room 6 ambient
3.75 Exhaust through
VE-21 temperature 1 Size 700 mm x 400 mm
gravity louver
D CCM AREA
CCM 15.7 x 8.1 x within 5° C over Tube axial supply
22 VS-22 Hydraulic room-1 42 2 12000 30
buildings 5.1 ambient air fan

3
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC
temperature Exhaust through
VE-22 4 Size 500 mm x 700 mm
gravity louver
Tube axial supply
VS-23 within 5° C over 1 12000 30
air fan
23 Hydraulic room-2 3.8 x 6 x 5.1 22 ambient
temperature Exhaust through
VE-23 2 Size 700 mm x 500 mm
gravity louver
Tube axial supply
VS-24 within 5° C over 2 7000 30
15.7 x 8.4 x air fan
24 Water room-1 22 ambient
4.65 Exhaust through
VE-24 temperature 2 Size 700 mm x 500 mm
gravity louver
Tube axial supply
VS-25 within 5° C over 1 5000 20
air fan
25 Water room-2 3.8 x 6 x 3.28 5 ambient
temperature Exhaust through
VE-25 1 Size 700 mm x 400 mm
gravity louver
Tube axial supply
VS-26 within 5° C over 1 5000 20
air fan
26 Steam Exhaust room 6.2 x 7 x 4 5 ambient
temperature Exhaust through
VE-26 1 Size 700 mm x 400 mm
gravity louver
Tube axial supply
VS-27 within 5° C over 2 5000 20
8.4 x 6.05 x air fan
27 Hydraulic room-3 10 ambient
3.4 Exhaust through
VE-27 temperature 2 Size 700 mm x 400 mm
gravity louver
E Dedusting Plant

within 5° C over
Electrical 14.4 x 13 x Propeller type Free air
28 VE-28 Store 1 ambient 8 2000
building 4.7 Exhaust air fan delivery
temperature

F. Bar Mill Area


F.1 Electrical control room (ECR)
within 50 C over
Propeller type Free air
29 VE-29 ECR Toilet - Gr. Floor 6 x 7.5 x 4 _ ambient 4 2000
Exhaust air fan delivery
temperature

Tube axial supply


VS-30 11 15000 30
0
within 5 C over air fan
112.7 x 7.5 x
30 ECR Cable room - 1st Floor 230 ambient
3.5
temperature Tube axial
VE-30 11 13000 20
exhaust air fan

4
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Tube axial supply


VS-31 1 5000 20
0
within 5 C over air fan
ECR Breaking Resistor room
31 ECR 8x6x4 1 KW ambient
(1st) - 3rd floor
temperature Tube axial
VE-31 1 4000 15
exhaust air fan

Tube axial supply


VS-32 1 5000 20
0
within 5 C over air fan
ECR Breaking Resistor room
32 ECR 8x6x4 1 KW ambient
(2nd) - 3rd floo
temperature Tube axial
VE-32 1 4000 15
exhaust air fan

Tube axial supply


VS-33 within 50 C over air fan
3 6000 20
rd
33 ECR Compensation room - 3 floo 39 x 7.5 x 4 _ ambient
temperature Tube axial
VE-33 3 5400 15
exhaust air fan

Supply through
VS-34 1 0.35 sqm
0
within 5 C over air intake louver
34 ECR Battery room - 3rd floo 4.75 x 6 x 4 _ ambient
temperature Belt driven/Bi-
VE-34 furcated exhaust 1 3000 15
air fan
F.2 Hydraulic and lubrication cellar/room

Centrifugal
VS-35 3 20000 30
0
within 5 C over supply air fan
Lubrication Lubrication cellar for Mill (at -5
35 108 x 7 x 5 80 ambient
cellar m) - Between Col. No. Y6-Y15
temperature
VE-35 Natural exhaust

Lubrication cellar for long Bar Centrifugal


VS-36 1 15000 40
Mill (at -5 m) - Near
0
within 5 C over supply air fan
Lubrication (16 x 5 + 15 x
36 straightening m/c between axes 10 ambient
cellar 7) x 5
17 & 19 in both XY and partly in temperature
VE-36 WX bays. Natural exhaust

F.3 Cable Tunnel

5
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Tube axial supply


VS-37 1 20000 30
0
within 5 C over air fan
37 Cable tunnel RVSS-01 to RVET-02A 65 X 2.4 X 2.4 33 ambient
temperature Tube axial
VE-37 1 18000 20
exhaust air fan

Tube axial supply


VS-38 1 15000 30
0
within 5 C over air fan
38 Cable tunnel RVET-02B to RVES-03 50 X 2.4 X 2.4 25 ambient
temperature Tube axial
VE-38 1 13000 20
exhaust air fan

Tube axial supply


VS-39 1 10000 30
air fan

within 50 C over Exhaust through


Cable tunnel below
39 Cable tunnel 20 x 1.8 x 3 15 ambient gravity louver to
Macroetching laboratory
temperature cable basement
VE-39 of LBDS-1 1 Size 800 mm x 700 mm
building. One
common exhaust
fan has been
considered
F.4 Rolling Mill and Macroetching Laboratory
Supply through
VS-40 within 50 C over air intake louver
_ _ _
Macroetching laboaratory - Gr.
40 4.75 x 3.5 x 6 15 ambient
Floor Tube axial
VE-40 temperature 1 9000 20
Lab - Gr. exhaust air fan
Floor 0 Tube axial supply
VS-41 within 5 C over 2 6000 20
10 x 5 x 6 + 4 air fan
41 Sample Preparation room 20 ambient
x5x6 Tube axial
VE-41 temperature 2 5400 15
exhaust air fan
within 50 C over
Propeller type Free air
42 VE-42 Gents toilet 1.75 x 5 x 3 _ ambient 1 2000
Exhaust air fan delivery
st
temperature
Lab - 1 Floor 0
within 5 C over
Propeller type Free air
43 VE-43 Ladies Toilet 1.25 x 3 x 3 _ ambient 1 2000
Exhaust air fan delivery
temperature

6
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

within 50 C over
Propeller type Free air
44 VE-44 Store 3x3x6 _ ambient 1 2000
Exhaust air fan delivery
temperature
within 50 C over
Propeller type Free air
45 VE-45 Gents toilet 3x5x3 _ ambient 1 2000
Exhaust air fan delivery
temperature

within 50 C over
nd Propeller type Free air
46 VE-46 Lab - 2 Floor Ladies Toilet 1.8 x 3 x 3 _ ambient 1 2000
Exhaust air fan delivery
temperature

within 50 C over
Propeller type Free air
47 VE-47 Pantry 1.4 x 3 x 6 _ ambient 1 2000
Exhaust air fan delivery
temperature

F.5 LBDS CUM LCSS Building

Tube axial supply


VS-48 1 5000 20
air fan
within 5°C over Tube axial
48 Cable Basement 16 x 10 x 3.5 10 ambient exhaust air fan
temperature including exhaust
VE-48 1 18000 20
ventilation system
of cable tunnel
(Refer G.3 - 44)

Tube axial supply


VS-49 2 10000 30
air fan
LBDS cum
LCSS
Tube axial supply
within 5°C over air fan including
16 x 10 x 4.5 -
49 VS-49a Electrical room 40 ambient partly suuply air 1 15000 30
7 x 3.5 x 4.5
temperature system to cable
basement

Tube axial
VE-49 2 13000 20
exhaust air fan
º
within 5 C over
Supply through
50 VS-50 Battery room 3.5 x 4 x 4 _ ambient 1 Size 700 mm x 500 mm
air intake louver
temperature

7
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Belt driven/Bi-
VE-50 furcated exhaust 1 3000 15
air fan

within 5º C over
Propeller type Free air
51 VE-51 Store room 3.5 x 4 x 4 _ ambient 1 2000
Exhaust air fan delivery
temperature

0
RR - Between within 5 C over
Propeller type Free air
52 VE-52 Col. No. W21- Toilet Block 3.3 x 4 x 3.5 _ ambient 2 2000
Exhaust air fan delivery
W22 temperature

Between Col. within 50 C over


Propeller type Free air
53 VE-53 No. W-8 & W- Toilet Block 4 x 4.5 x 3.5 _ ambient 3 2000
Exhaust air fan delivery
9 temperature

Substore-I
within 50 C over
between Col. Propeller type Free air
54 VE-54 Sub-store 10 x 4 x 3.5 _ ambient 3 2000
No. W-5 & W- Exhaust air fan delivery
temperature
6

Between Col. within 50 C over


Propeller type Free air
55 VE-55 No. X-24 & X- Toilet Block 4 x 4.5 x 3.5 _ ambient 3 2000
Exhaust air fan delivery
25 temperature

Between Col. within 50 C over


Propeller type Free air
56 VE-56 No. Y-15 & Y- Toilet Block 4 x 4.5 x 3.5 _ ambient 3 2000
Exhaust air fan delivery
16 temperature

G Central Store

Supply through
VS-57 1.2 Sq. m
air intake louver

Propeller type Free air


57 VE-57 Store room at Gr. Floor 5 2000
Exhaust air fan delivery
Central Store

MC-1 Man coolers 3 7500

Supply through
58 VS-58 Store room at +13.0 M Level 1.2 Sq. m
air intake louver

8
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Propeller type Free air


VE-58 5 2000
Exhaust air fan delivery

MC-2 Man coolers 3 7500

Supply through
VS-59 1.2 Sq. m
air intake louver

Propeller type Free air


59 VE-59 Store room at +18.0 M Level 5 2000
Exhaust air fan delivery

MC-3 Man coolers 3 7500

H Compressor House

Supply through
VS-60 3 Size 2000 mm x 1000 mm
air intake louver
within 5° C over
Compressor
60 Compressor Room 16.5 x 12 x 8 100 ambient
building
temperature
Tube axial
VE-60 3 18000 20
exhaust air fan

Supply through
VS-61 1 20000 30
air intake louver
within 5° C over
Electrical
61 MCC room 6 x 12 x 4 30 ambient
room
temperature
Tube axial
VE-61 1 18000 20
exhaust air fan

I Natural gas metering station


Central within 5° C over
Propeller type Free air
62 VS-62 metering CMS 14 x 4 x 5 _ ambient 4 2000
Exhaust air fan delivery
station temperature
Air Separation
J
Plant

9
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC

Supply through
VS-63 1 0.35 sqm
0
within 5 C over air intake louver
63 Battery room-1 6x6x5 _ ambient
temperature Belt driven/Bi-
VE-63 furcated exhaust 1 3000 15
Air separation air fan
Plant
Supply through
VS-64 1 0.35 sqm
0
within 5 C over air intake louver
64 Battery room-2 6x6x5 _ ambient
temperature Belt driven/Bi-
VE-64 furcated exhaust 1 3000 15
air fan
K Water System
within 5° C over
Scale pit Centrifugal
65 VS-65 Scale pit 13 x 6.5 x 13 35 ambient 1 20000 40
pump house supply air fan
temperature
VS-66 within 5° C over Air intake louver 18 Size 1000 mm x 500 mm
66 RCPH - Gr. Floor 60 x 13 x 7 270 ambient Tube axial
VE-66 temperature 8 18000 20
Recirculating exhaust air fan
pump house
VS-67 within 50 C over Air intake louver 9 Size 1000 mm x 700 mm
67 RCPH - 1st Floor 50 x 13 x 7 210 ambient Tube axial
VE-67 6 18000 20
temperature exhaust air fan
Tube axial supply
VS-68 within 5° C over 2 10000 30
air fan
68 Electrical room - Gr. Floor 9.9 x 13 x 6 30 ambient
temperature Exhaust through
VE-68 2 Size 1000 mm x 700 mm
gravity louver
Tube axial supply
VS-69 within 50 C over air fan
2 5000 20
69 Cable room - 1st Floor 9.9 x 13 x 3.5 10 ambient
temperature Exhaust through
VE-69 Recirculating 2 Size 700 mm x 400 mm
gravity louver
pump house 0
ECR building within 5 C over
Propeller type Free air
70 VE-70 Crew room -1st floor 4.3 x 4 x 3.5 _ ambient 1 2000
Exhaust air fan delivery
temperature
0
within 5 C over
Propeller type Free air
71 VE-71 Store room-1st floor 3.3 x 2.5 x 3.5 _ ambient 1 2000
Exhaust air fan delivery
temperature
within 50 C over Supply through
72 VS-72 Battery room 5x4x5 _ 1 0.35 sqm
ambient air intake louver

10
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC
temperature Belt driven/Bi-
VE-72 furcated exhaust 1 3000 15
air fan

Longitudinal
clarifier- Tube axial supply
VS-73 treated water within 50 C over air fan
2 20000 30
73 pump house Pump room 15 x 7.5 x 6 70 ambient
cum fire temperature
fighting pump
house
Exhaust through
VE-73 3 Size 1000 mm x 700 mm
gravity louver
Tube axial supply
VS-74 within 5° C over 2 10000 30
Raw water air fan
74 Raw water pump house 22 x 6.4 x 6 18 ambient
pump house Exhaust through
VE-74 temperature 2 Size 1000 mm x 500 mm
gravity louver
L Amenity building
Propeller type Free air
75 VE-75 Kitchen 6.5 x 10 x 4 _ _ 2 2000
Exhaust air fan delivery
Propeller type Free air
76 VE-76 Amenity Gas bank 3x4x4 _ _ 1 2000
Exhaust air fan delivery
building - Gr.
Floor Propeller type Free air
77 VE-77 Daaily store 4x4x4 _ _ 1 2000
Exhaust air fan delivery
Propeller type Free air
78 VE-78 Bulk store 6.5 x 3.5 x 4 _ _ 1 2000
Exhaust air fan delivery
Propeller type Free air
79 VE-79 Amenity Ladies toilet 6x7x4 _ _ 3 2000
Exhaust air fan delivery
building - 1st
Floor Propeller type Free air
80 VE-80 Gents toilet 10 x 7 x 4 _ _ 4 2000
Exhaust air fan delivery
M Central Workshop
Central
81 VE-81 Repair & Maintenance shop 18 x 36 x 7 _ _ Trbo-ventilator 12 24" dia. _
workshop
Scrap storage Propeller type Free air
82 VE-82 Toilet 6x4x4 _ _ 2 2000
area - Toilet Exhaust air fan delivery

VS - stands for Ventilation supply air fan/ air intake louver.


VE - stands for Ventilation exhaust air fan / gravity louver.
MC - Stands for Man-coolers

11
GPH-PROC ASST-00BOP07I-UTL-0001, REV. 1

Equipment Details
Inside Room
Building Room Size Heat Load Type of Qty
Sl. No System No. Area to be served temperature to Static
Name (M X M X M) (kW) Equipment (NOS.)
be maintained Capacity in CMH pr in
mm WC
N
Note: 1
The supply air system shall be provided with supply fan, cowl, air intake louver (wherever applicable), filter with filter frame, transition piece, duct with supports, fire damper
(wherever applicable) etc. and exhaust air system with exhaust fan, cowl, bird screen, transition piece, duct with supports, fire damper (wherever applicable).

Note: 2 Equipment Capacity and Quantity indicated above are tentative. This should be finalised during detail engineering stage after furnishing calculation for selection of the
equipments based on heat load data and room configuration.