UNIVERSITI TEKNOLOGI MARA (UiTM) PERAK

KAMPUS SERI ISKANDAR


FACULTY OF ARCHITECTURE, PLANNING & SURVEYING
BSC.(HONS) CONSTRUCTION TECHNOLOGY AP256

ENVIRONMENTAL GREEN STUDIES


(BCT 533)
OTTV CALCULATION

NAME: SUAIDAH SHIMA BINTI SHAHRIN


NO MATRIC: 2019695192
GROUP: AP256 3A
LECTURER NAME : DR. ASMAT ISMAIL
DATE OF SUBMISSION: DECEMBER 2019
STEP FOR OTTV CALCULATION
1. Determine the orientation of each elevation.
2. Determine the wall for OTTV calculation
3. Calculate the wall areas.

Total wall area at North /South elevation = 1149 m²


Total wall area at West /East elevation = 1,322 m²

4. Determine the Solar Absorption Factor (α)

Wall to be light colour painted, assumed α = 0.20

Table 6. Solar absorptivity

Colour Suggested value of α


Light < 0.40
Medium 0.40 to 0.70
Dark > 0.70

5. Calculate the window to wall ratio (WWR).

NORTH ELEVATION SOUTH ELEVATION EAST/ WEST ELEVATION


Total Wall Area(y)=1,149 m² Total Wall Area(y)=1,149 m² Total Wall Area(y)=1,322 m²
Total window area(x)=740m² Total window area(x)=710m² Total window area(x)=810m²
WWR=x/y=740/1,149 WWR=x/y=710/1,149 WWR=x/y=810/1,322
WWR=0.64 WWR=0.62 WWR=0.61
6. Calculate the wall U-Value.

Table 1: Wall U-value

Thermal Conductivity Thermal Resistance, R


Item Material Thickness (m)
(W/mk) (m2k/W)
1 External Surface - - 0.040
2 External Wall Plaster 0.018 0.570 0.0316
3 Bricks Wall 0.115 0.77 0.149
4 Internal wall plaster 0.018 0.570 0.0316
5 Internal Surface - - 0.130
0.151 Total R 0.3822

1 2 3 4 5

1 1
Exterior Interior Wall U-value = = = 2.62 W/m²k
𝑅 0.3822

0.018 0.115 0.018

Figure 1: Thickness of wall material


7. Done heat conduction through walls
8. Fill the SC and U-Value for glazing provided.

The u-value of 5 mm thick glass = 5.7 W/m2k


SC value for glazing is 0.51

9. Done for heat conduction through windows.


10. Fill in the Orientation Factor according Table 5 [Solar Correction Factors] in MS1525:2014

Table 5. Solar orientation factors

Orientation OF

North 0.90

Northeast 1.09

East 1.23

Southeast 1.13

South 0.92

Southwest 0.90

West 0.94

Northwest 0.90
NOTES:
1. Table 5 specifies OF for the various orientation of the fenestration. For the calculation of OF, it is recommended that
the nearest predominant orientation be selected.
2. A fenestration system may consist of a glazing material such as glass, a shading device and a combination of both.

Figure 2: The MS1525 2014 of Orientation Factor


Source: Malaysian Standard MS 1525:2014 (2014)

11. Determine the SC2 Shading Devices according sun shading design and refer to Table 5,6,7 MS1525:2014. [SC2 = 1, no sun shading
devices]
WAYS TO IMPROVE OTTV
1. Review sunshades and its Shading Coefficient (SC) in Table 5, 6 and 7.
Proposal: Provision of two layer of horizontal sun shading (450mm) refer to table of Shading Coefficient Horizontal Projection from
MS1525:2014

0.48

Figure 3: Horizontal sun shading diagram

𝑋 480
R= = = 0.36
𝑌 1350
Figure 4: The MS1525 2014 of Shading Coefficient Horizontal Projection
Source: Malaysian Standard MS 1525:2014 (2014)
2.Review glass selection and its Shading Coefficient (SC1).
Proposal: Changing the glass to double glazed glass: ASG Green Float with 30% coverage ceramic printing on surface and Clear Low E Float
[U-value = 1.92; SC = 0.21].
Table 2:Performance Data Table for Glass Selection from AJIYA
Source: http://www.ajiya.com

Double glazed glass consisting of:


8mm ASG Green Float with 30%
Coverage ceramic printing on surface #2+
12mm Airspace+ 8mm ASG Clear Low E
Float #3
REFERENCES
1. AJIYA performance data .(2007). Retrieved from AJIYA safety Glass Catalogue :
http://www.ajiya.com/global_files/catalog/Ajiya%20Safety%20Glass%20Catalogue.pdf

2. Malaysian Standard MS 1525:2014 (2014)