Вы находитесь на странице: 1из 1

750-469

2-Channel Input Module for Thermocouples

13 14
A

Function AI 1 B
C Function AI 2
Error AI 1 D Error AI 2
+TC +TC
Data contacts
1 5
+TC 1 +TC 2 +TC 1 +TC 2 +TC
—TC —TC
270 pF
2 6
–TC 1 –TC 2 –TC 1 –TC 2 –TC
270 pF A
MUX Logic
M M D

3 7 Error
Common Common Common Common ϑComp Function
(ground) (ground) (ground) (ground) 20 nF
S S

4 8
Shield Shield Shield Shield
(screen) (screen) (screen) (screen)
750-469 750-469

Delivery without miniature WSB

The thermocouple input module allows the direct connection of two thermocouples. Cold junction compensation is utilized to
compensate for the clamping unit offset voltage over the 0 °C ... 55 °C operating range.
The module linearizes the entire temperature range automatically.
A line break is indicated by a red LED. A green LED indicates readiness for operation and trouble-free communication with
the buscoupler.
The shield (screen) is directly connected to the DIN rail.

Item-No. Pack.-unit
Description pcs Technical Data
2AI Thermocouple/ K / Diagn. 750-469 1 No. of inputs 2
-100 °C ... +1370 °C; type K Voltage supply via system voltage DC /DC
2AI Thermocouple/S / Diagn. 750-469/000-001 1 Current consumption max. (internal) 65 mA
0 °C ... +1700 °C; type S Sensor types Type K; -100 °C ... +1370 °C (factory preset)
2AI Thermocouple/ T/ Diagn. 750-469/000-002 1 J, B, E, N, R, S, T, U, L
-100 °C ... +400 °C; type T Cold junction compensation at each pair of terminal blocks
2AI ±120mV/ Diagn. 750-469/000-003 1 Resolution (over whole range) 0.1 °C
2AI Thermocouple/J / Diagn. 750-469/000-006 1 Conversion time 320 ms (both channels)
-100 °C ... +1200 °C; type J Measuring error 25°C < ± 0.4 % of the full scale value
2AI Thermocouple/E / Diagn. 750-469/000-008 1 Temperature coefficient < ± 0.01 % /K of the full scale value
-100 °C ... +1000 °C; type E Isolation 500 V system /supply
2AI Thermocouple/L / Diagn. 750-469/000-012 1 Bit width 2 x 16 bits data
-25 °C ... +900 °C; type L 2 x 8 bits control/status (option)
2AI Thermocouple/K/Diagn./S5 1) 750-469/000-200 1
2AI Thermocouple/J/Diagn./S5 1) 750-469/000-206 1
2AI Thermocouple/free configurable 750-469/003-000 1

Other variations are available upon request:


General specifications
600 °C ... +1800 °C; type B Operating temperature 0 °C ... +55 °C
-100 °C ... +1300 °C; type N Wire connection CAGE CLAMP® 0.08 mm2 ... 2.5 mm2; AWG 28 ... 14
0 °C ... +1700 °C; type R 8 ... 9 mm /0.33 in stripped length
-25 °C ... + 600 °C; type U Dimensions (mm) W x H x L 12 x 64* x 100
-120 mV ... +120 mV * from upper edge of 35 DIN rail
1)
Data format for S5 control with FB 250. Weight ca 55 g
Storage temperature -25 °C ... +85 °C
Approvals Relative air humidity 95 % no condensation
r and marine applications see pages 1.10 ... 1.13 Vibration and acc. to IEC 60068-2-6
4 II 3 G EEx nA II T4 shock resistance acc. to IEC 60068-2-27
Conformity marking 1 Degree of protection IP 20
Item-No. Pack.-unit EMC 1 -Immunity to interference acc. to EN 50082-2 (1996)
Accessories pcs EMC 1 -Emission of interference acc. to EN 50081-1 (1993)
Miniature WSB quick marking system EMC marine applications -Immunity to interf. acc. to Germanischer Lloyd (1997)
plain 248-501 5 EMC marine applications -Emission of interf. acc. to Germanischer Lloyd (1997)
with marking see pages 1.174 ... 1.175

Subject to design changes WAGO Kontakttechnik GmbH Postfach 2880 • D-32385 Minden Tel.: +49(0)5 71 /8 87- 0 E-Mail: info@wago.com
21.01.2004 Hansastr. 27 • D-32423 Minden Fax.: +49(0)5 71 /8 87-169 www.wago.com

Вам также может понравиться