Академический Документы
Профессиональный Документы
Культура Документы
13 14
A
Function AI 1 B
C Function AI 2
Error AI 1 D Error AI 2
+TC +TC
Data contacts
1 5
+TC 1 +TC 2 +TC 1 +TC 2 +TC
—TC —TC
270 pF
2 6
–TC 1 –TC 2 –TC 1 –TC 2 –TC
270 pF A
MUX Logic
M M D
3 7 Error
Common Common Common Common ϑComp Function
(ground) (ground) (ground) (ground) 20 nF
S S
4 8
Shield Shield Shield Shield
(screen) (screen) (screen) (screen)
750-469 750-469
The thermocouple input module allows the direct connection of two thermocouples. Cold junction compensation is utilized to
compensate for the clamping unit offset voltage over the 0 °C ... 55 °C operating range.
The module linearizes the entire temperature range automatically.
A line break is indicated by a red LED. A green LED indicates readiness for operation and trouble-free communication with
the buscoupler.
The shield (screen) is directly connected to the DIN rail.
Item-No. Pack.-unit
Description pcs Technical Data
2AI Thermocouple/ K / Diagn. 750-469 1 No. of inputs 2
-100 °C ... +1370 °C; type K Voltage supply via system voltage DC /DC
2AI Thermocouple/S / Diagn. 750-469/000-001 1 Current consumption max. (internal) 65 mA
0 °C ... +1700 °C; type S Sensor types Type K; -100 °C ... +1370 °C (factory preset)
2AI Thermocouple/ T/ Diagn. 750-469/000-002 1 J, B, E, N, R, S, T, U, L
-100 °C ... +400 °C; type T Cold junction compensation at each pair of terminal blocks
2AI ±120mV/ Diagn. 750-469/000-003 1 Resolution (over whole range) 0.1 °C
2AI Thermocouple/J / Diagn. 750-469/000-006 1 Conversion time 320 ms (both channels)
-100 °C ... +1200 °C; type J Measuring error 25°C < ± 0.4 % of the full scale value
2AI Thermocouple/E / Diagn. 750-469/000-008 1 Temperature coefficient < ± 0.01 % /K of the full scale value
-100 °C ... +1000 °C; type E Isolation 500 V system /supply
2AI Thermocouple/L / Diagn. 750-469/000-012 1 Bit width 2 x 16 bits data
-25 °C ... +900 °C; type L 2 x 8 bits control/status (option)
2AI Thermocouple/K/Diagn./S5 1) 750-469/000-200 1
2AI Thermocouple/J/Diagn./S5 1) 750-469/000-206 1
2AI Thermocouple/free configurable 750-469/003-000 1
Subject to design changes WAGO Kontakttechnik GmbH Postfach 2880 • D-32385 Minden Tel.: +49(0)5 71 /8 87- 0 E-Mail: info@wago.com
21.01.2004 Hansastr. 27 • D-32423 Minden Fax.: +49(0)5 71 /8 87-169 www.wago.com