Вы находитесь на странице: 1из 7

Data sheet 3VT1710-2DC36-0AA0

CIRCUIT BREAKER 3VT1 STANDARD BREAKING CAPACITY


ICU=25KA, 415V AC 3-POLE, SYSTEM PROTECTION
OVERCURRENT RELEASE TM, LI IN= 100A RATED CURRENT
IR= 80... 100A OVERLOAD PROT. II= 500... 1000A, SHORT-
CIRCUIT PROTECTION WITHOUT AUXILIARY RELEASE
WITHOUT AUXILIARY/ALARM SWITCH

Model
Product brand name SENTRON
Product designation 3VT1_5 molded case circuit breakers
Design of the operating mechanism toggle handle
Type of the driving mechanism / motor drive No
Design of the overcurrent release TM

General technical data


Number of poles 3
Size of the circuit-breaker 3VT1
Electrical endurance (switching cycles) / typical 6 000
Usage category A
Performance class for circuit breaker N
Mechanical service life (switching cycles) / typical 20 000
Operating frequency / maximum 120 1/h

Voltage
Insulation voltage / rated value 690 V
Surge voltage resistance / rated value 8 kV

3VT1710-2DC36-0AA0 Subject to change without notice


Page 1/7 09/26/2017 © Copyright Siemens
Protection class
Protection class IP IP40
Protective function of the overcurrent release LI

Dissipation
Power loss [W]
● for rated value of the current / at AC / in hot 3.33 W
operating state / per pole
● maximum 10 W

Electricity
Operating current / at 45 °C / rated value 91 A
Continuous current / rated value 100 A
Derating temperature / for the rated value of the 40 °C
continuous current
Adjustable pick-up value current
● of the current-dependent overload release / 100 A
Full-scale value
● of instantaneous short-circuit trip unit / initial 500 A
value
● of instantaneous short-circuit trip unit / Full- 1 000 A
scale value

Main circuit
Operating frequency
● 1 / rated value 50 Hz
● 2 / rated value 60 Hz
Operating voltage
● rated value / maximum 690 V
● for main current circuit / at AC / at 50 Hz / 690 V
maximum
● for main current circuit / at AC / at 60 Hz / 690 V
maximum
● for main current circuit / at DC / maximum 250 V
Operating current
● at 40 °C / rated value 100 A
● at 50 °C / rated value 91 A

Suitability
Suitability for use system protection
● Disconnecting means Yes

Adjustable parameters
Adjustable pick-up value current / of the current- 80 A
dependent overload release / initial value

Product details

3VT1710-2DC36-0AA0 Subject to change without notice


Page 2/7 09/26/2017 © Copyright Siemens
Product component
● Trip indicator No
● Auxiliary switch No
● Voltage trigger No
● undervoltage release No
● undervoltage release with leading contact No
Product extension / optional / motor drive Yes

Product function
Product function
● of thermal overload trip unit adjustable
● Ground fault protection No
● for neutral conductors / Short-circuit and No
overload proof
● Phase failure detection No
● Overload protection Yes

Short circuit
Operational short-circuit current breaking capacity
(Ics)
● at 240 V / rated value 20 kA
● at 415 V / rated value 13 kA
● at 500 V / rated value 6 kA
● at 690 V / rated value 3 kA
Maximum short-circuit current breaking capacity (Icu)
● at 240 V / rated value 40 kA
● at 415 V / rated value 25 kA
● at 500 V / rated value 12 kA
● at 690 V / rated value 6 kA

Connections
Arrangement of electrical connectors / for main front side
current circuit
Type of electrical connection / for main current circuit box terminals

Mechanical Design
Height 130 mm
Width 75 mm
Depth 80 mm
Mounting position with vertical mounting surface +/-180° rotatable, with vertical
mounting surface +/- 30° tiltable to the front and back
Mounting type fixed mounting
Net weight 1.05 kg

Environmental conditions
Ambient temperature

3VT1710-2DC36-0AA0 Subject to change without notice


Page 3/7 09/26/2017 © Copyright Siemens
● during operation / minimum -40 °C
● during operation / maximum 55 °C
● during storage / minimum -40 °C
● during storage / maximum 55 °C

Certificates
Equipment marking
● acc. to DIN EN 61346-2 Q
● acc. to DIN EN 81346-2 Q

General Product Declaration of Test Certificates other


Approval Conformity
Type Test Miscellaneous
Certificates/Test Report

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/lowvoltage/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3VT1710-2DC36-0AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3VT1710-2DC36-0AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3VT1710-2DC36-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications

3VT1710-2DC36-0AA0 Subject to change without notice


Page 4/7 09/26/2017 © Copyright Siemens
98
68,5

18 20 2
6, 12 1,5
4
7

s 25 3VT1

14,7

100
14°
38
111

93
100

118
130

45

13°

3
M
63

R5
5

40,5

15
25 12,5
25 25 20
75 70
80

3VT1710-2DC36-0AA0 Subject to change without notice


Page 5/7 09/26/2017 © Copyright Siemens
3VT1710-2DC36-0AA0 Subject to change without notice
Page 6/7 09/26/2017 © Copyright Siemens
3VT1710-2DC36-0AA0 Subject to change without notice
Page 7/7 09/26/2017 © Copyright Siemens

Вам также может понравиться