Jun 18, 2020 Coordinaide™ - The S&C Protection & 1

Coordination Assistant
System Settings
Frequency Voltage Available Fault Current
60 Hz 34.5 kV 10000 A

1.Recloser Equation-Based (MicroProcessor Control)


Curve Property Value
Recloser Equation-Based Manufacturer SEL 351R/651R
(MicroProcessor Control) -
Global Settings
Minimum Trip Current-Phase 85
Minimum Trip Current-Ground 70

Recloser Equation-Based Curve C1 Standard Inverse


(MicroProcessor Control)-
phase-fast
Time Multiplier 1
Time Adder 0
Minimum Response Time 1.989
Current at MRT 3299.412
Enable High Current Trip? false
High Current Trip 12500
High Current Trip (time) 0.017
Recloser Clearing Time 0.05
Negative Current Tolerance 8
Positive Current Tolerance 8
Negative Time Tolerance 4
Positive Time Tolerance 4
Negative Fixed Time (CTI) 0.025
Positive Fixed Time (CTI) 0.025

Recloser Equation-Based Curve C1 Standard Inverse


(MicroProcessor Control)-
phase-slow
Time Multiplier 1
Time Adder 0
Minimum Response Time 1.989
Current at MRT 3299.412
Enable High Current Trip? false
High Current Trip 12500
High Current Trip (time) 0.017

Jun 18, 2020 Coordinaide™ - The S&C Protection & 2


Coordination Assistant
Recloser Clearing Time 0.05
Negative Current Tolerance 8
Positive Current Tolerance 8
Negative Time Tolerance 4
Positive Time Tolerance 4
Negative Fixed Time (CTI) 0.025
Positive Fixed Time (CTI) 0.025

Recloser Equation-Based Curve C1 Standard Inverse


(MicroProcessor Control)-
ground-fast
Time Multiplier 1
Time Adder 0
Minimum Response Time 1.989
Current at MRT 2699.519
Enable High Current Trip? false
High Current Trip 12500
High Current Trip (time) 0.017
Recloser Clearing Time 0.05
Negative Current Tolerance 8
Positive Current Tolerance 8
Negative Time Tolerance 4
Positive Time Tolerance 4
Negative Fixed Time (CTI) 0.025
Positive Fixed Time (CTI) 0.025

Recloser Equation-Based Curve C1 Standard Inverse


(MicroProcessor Control)-
ground-slow
Time Multiplier 1
Time Adder 0
Minimum Response Time 1.989
Current at MRT 2699.519
Enable High Current Trip? false
High Current Trip 12500
High Current Trip (time) 0.017
Recloser Clearing Time 0.05
Negative Current Tolerance 8
Positive Current Tolerance 8

Jun 18, 2020 Coordinaide™ - The S&C Protection & 3


Coordination Assistant
Negative Time Tolerance 4
Positive Time Tolerance 4
Negative Fixed Time (CTI) 0.025
Positive Fixed Time (CTI) 0.025

2.Relayed Circuit Breaker


Curve Property Value
phase Manufacturer Basler BE1-51
Relay Type B2: Long-Time Inverse
Minimum Pickup Current 200
Include Instantaneous false
Pickup?
Instantaneous Pickup 1000
Low-Current Cutoff 0
Definite Time 0
Time Dial Setting 20
Negative Current Tolerance 0
Positive Current Tolerance 0
Negative Time Tolerance 0
Positive Time Tolerance 0
Negative CTI 0
Positive CTI 0
Breaker Clearing Time 0

ground Manufacturer Basler BE1-51


Relay Type B2: Long-Time Inverse
Minimum Pickup Current 125
Include Instantaneous false
Pickup?
Instantaneous Pickup 1000
Low-Current Cutoff 0
Definite Time 0
Time Dial Setting 20
Negative Current Tolerance 0
Positive Current Tolerance 0
Negative Time Tolerance 0
Positive Time Tolerance 0
Negative CTI 0

Jun 18, 2020 Coordinaide™ - The S&C Protection & 4


Coordination Assistant
Positive CTI 0
Breaker Clearing Time 0

3.Transformer (Damage Curve)


Curve Property Value
Transformer (Damage Curve) Connection: Delta-Grd.Y
3-Phase Secondary kV 4.16
3-Phase Rating kVA 10500
Impedance 5.91
Display Magnetizing Inrush false
Points?
@ 0.01 second 25
Magnetizing Inrush 4392.875
@ 0.1 second 12
Magnetizing Inrush 2108.58
@ 1 second 6
Cold-Load Pickup Inrush 1054.29
@ 10 second 3
Cold-Load Pickup Inrush 527.145
@ 900 second 2
Cold-Load Pickup Inrush 351.43
Primary_kV/Full Load Amps 34.5/175.715
Secondary_kV/Full Load 4.16/1457.254
Amps

Jun 18, 2020 Coordinaide™ - The S&C Protection & 5