Вы находитесь на странице: 1из 8

Design and Drawing of

Rural Water Supply Scheme

Design and Drawing of


Rural Water Supply Scheme
Spreadsheet
Spreadsheet Developed
Developed by:
by:
View
View Pipe
Pipe Data
Data

Goto Data Input

Goto
Goto PD-Sample
PD-Sample
GPO Box 1062, Kathmandu, Nepal
Phone : 977-01-4115581/4115582
Email : softwel@mos.com.np

Annex - I
COST-11000
DATA INPUT FORM
Spread Sheets Developed by SOFTWEL (P) Ltd.

Organization DWSS
Scheme Code 11000
Scheme Name Geta-7 WSP
Name of the Community Geta
Name of the Support Organization WSSDO
Location : Ward No.: 7
VDC : Geta (Attariya)
District : Kailali
Kailali

SCHEME TYPE Pumping

SURVEY / DESIGN INFORMATION


District Pop Growth Rate (r) 1.50 % From District Growth Rates
Construction Period (n1) 3 years
Design Period (n) 15 years
Peak Factor 3 Factor
Per Capita Domestic Water Demand 70 l/d
Per Capita Water Demand for Students 10 l/d
Present Year ( Survey Year) 2015 AD
Base Year ( Project Completion Year) 2018 AD
Design Year 2033 AD
Minimum Flow Rate per Tap 0.10 lps
Table C.2 : Reservoir Tank Sizing
DWSS
SCHEME NAME : Geta-7 WSP
LOCATION : WARD NO : 7 VDC : Geta (Attariya) DISTRICT : Kailali

a) Scheme Information
a.1 Reservoir Tank No: 1
a.2 Served Standposts 1 to 8
a.3 Average Design Demand to be Supplied through Reservoir #REF! l/s = #REF! l/day
a.4 Available Minimum flow from the Source (Safe Yield) 0.400 l/s
#REF!
a.5 Adjusted/Optimized supply to Reservoir from Source 0.250 l/s = 21600.0 l/day
a.6 Total Design Flows of all Standposts : #REF! l/s
b) Reservoir sizing assuming Continuous System using Consumption Patterns

Time Period Hours Water Cummu. Cummu. Surplus Deficit


From To Consumption Supply Demand
(%) (lt) (lt) (lt) (lt)
5:00 AM 7:00 AM 2 25.0% 1800 #REF! #REF! #REF!
7:00 AM 12:00 AM 5 35.0% 6300 #REF! #REF! #REF!
12:00 AM 5:00 PM 5 20.0% 10800 #REF! #REF! #REF!
5:00 PM 7:00 PM 2 20.0% 12600 #REF! #REF! #REF!
7:00 PM 5:00 AM 10 0.0% 21600 #REF! #REF! #REF!

Maximum Deficit #REF! lt


Minimum required Reservoir capacity #REF! cum
Provide Reservoir of capacity #REF! cum #REF! of Average Demand
Check if Reservoir gets filled during night (7:00 PM - 5:00 AM)
Volume of water collected during night 9.00 cum

25000

20000

15000

10000

5000

0
04:48 AM

02:24 PM

12:00 AM
12:00 AM

09:36 AM

07:12 PM

04:48 AM

09:36 AM

Supply Demand

c) Reservoir sizing assuming Intermittent System (Optional)

Maximum Required supply hours based on Supply from Source #REF! hours
Maximum Required supply hours based on Demand #REF! hours
Adopted hours of Supply #REF! hours
Recommended Supply Hours and Period
First Shift 5:00 AM To #REF!
Second Shift #REF! To 7:00 PM

Time Period Hours Cum. Inflow Cum. Con- Surplus Deficit


From To In Out (lt) sumption (lt) (lt) (lt)
5:00 AM #REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! 7:00 PM #REF! #REF! #REF! #REF! #REF! #REF!
7:00 PM 5:00 AM 10.00 #REF! #REF! #REF! #REF! #REF!

Max Deficit #REF! lt = #REF! cum


Provide Reservoir Capacity of #REF! cum
c) Recommended Reservoir Size

Recommended Size for RVT 01 = #VALUE! cum Time to Fill the RVT #VALUE! Hr
PIPELINE DESIGN Sheet No. : 4 of 8

(HYDRAULIC CALCULATIONS)

Table C.3 : Pipeline Design Pipe Class abbreviation HC Soil Code GMS OS
MC (Ctrl+a for using solver) HR BMS
PROJECT: Tuka Irrigation project DI Run
SR MR
Run Macro
Macro HereHere
Name of Source : Tuka Khola CI Ctrl
Ctrl ++ ee HS SS Pipe Line Design from CW Method
HS Steel

S. Pipe Line Length Design Direction Reduced Level Level New Total Max. PIPE USED Friction Head Residual Flow Hydraulic Gradient L Soil

No. Dis. (UL/UR Diff. Static Head Static HDPE G.I. Factor Loss Head Velocity Type
From To Actual Design Q /DL/DR) From To Level Available Pressure O.D. Class I.D. N.B. Class From To Remarks
(m) (m) (lps) (L/R/U/D) (m) (m) (m) (m) (m) (m) (mm) (kg/cm²) (mm) (mm) (m) (m) (m/s) (m) (m)
[0] [1] [2] [3] 0 [5] (6) (7) (8) (9) (10) (11) (12) (13) (14) (15) (16) (17) (18) (19) (20) (21) (22) (23) (24) (25)

1 Intake B 67 73.7 10.200 D 1355.00 1331.00 24.00 1355.00 24.00 24.00 125 6 106.10 0.0221 1.04 22.96 1.15 1355.00 1353.96 BMS
2B C 49 53.9 10.200 D 1331.00 1326.00 5.00 1355.00 27.96 29.00 125 6 106.10 0.0221 0.76 27.20 1.15 1353.96 1353.20 BMS
3C D 139 152.9 10.200 D 1326.00 1323.00 3.00 1355.00 30.20 32.00 125 6 106.10 0.0221 2.15 28.05 1.15 1353.20 1351.05 BMS
4D E 270 297 10.200 D 1323.00 1317.00 6.00 1355.00 34.05 38.00 125 6 106.10 0.0221 4.18 29.87 1.15 1351.05 1346.87 BMS
5E F 375 412.5 10.200 D 1317.00 1303.00 14.00 1355.00 43.87 52.00 125 6 106.10 0.0221 5.80 38.07 1.15 1346.87 1341.07 BMS
6F G 390 429 10.200 D 1303.00 1301.00 2.00 1355.00 40.07 54.00 125 6 106.10 0.0221 6.03 34.04 1.15 1341.07 1335.04 BMS
7G H 450 495 10.200 D 1301.00 1287.00 14.00 1355.00 48.04 68.00 125 10 95.10 0.0223 12.24 35.80 1.44 1335.04 1322.80 BMS
8H I 570 627 10.200 D 1287.00 1270.00 17.00 1355.00 52.80 85.00 125 10 95.10 0.0223 15.51 37.29 1.44 1322.80 1307.29 BMS
Table C.2 : Reservoir Tank Sizing
CBWSS
SCHEME NAME : Geta-7 WSP
LOCATION : WARD NO : 7 VDC : Geta (Attariya) DISTRICT : Kailali

a) Scheme Information
a.1 Reservoir Tank No: 1
a.2 Served Standposts 1 to 8
a.3 Average Design Demand to be Supplied through Reservoir 3.268 l/s = 282339.000 l/day
a.4 Available Minimum flow from the Source (Safe Yield) 10.000 l/s

a.5 Adjusted/Optimized supply to Reservoir from Source 10.000 l/s = 864000.0 l/day
a.6 Total Design Flows of all Standposts : 16.410 l/s
b) Reservoir sizing assuming Continuous System using Consumption Patterns

Time Period Hours Water Cummu. Cummu. Surplus Deficit


From To Consumption Supply Demand
(%) (lt) (lt) (lt) (lt)
5:00 AM 7:00 AM 2 25.0% 72000 70585 1415
7:00 AM 12:00 AM 5 35.0% 252000 169403 82597
12:00 AM 5:00 PM 5 20.0% 432000 225871 206129
5:00 PM 7:00 PM 2 20.0% 504000 282339 221661
7:00 PM 5:00 AM 10 0.0% 864000 282339 581661

Maximum Deficit 0 lt
Minimum required Reservoir capacity 14.12 cum
Provide Reservoir of capacity 15.00 cum 5% of Average Demand
Check if Reservoir gets filled during night (7:00 PM - 5:00 AM)
Volume of water collected during night 360.00 cum

1000000
900000
800000
700000
600000
500000
400000
300000
200000
100000
0
07:12 PM

12:00 AM

04:48 AM

09:36 AM
12:00 AM

04:48 AM

09:36 AM

02:24 PM

Column P C olumn Q

c) Reservoir sizing assuming Intermittent System (Optional)

Maximum Required supply hours based on Supply from Source 14.63 hours
Maximum Required supply hours based on Demand 4.78 hours
Adopted hours of Supply 5.00 hours
Recommended Supply Hours and Period
First Shift
Second Shift 5:00:00 PM To 7:00 PM

Time Period Hours Cum. Inflow Cum. Con- Surplus Deficit


From To In Out (lt) sumption (lt) (lt) (lt)
12:00 AM 5:00:00 71280.00 71280 0 71280
5:00:00 PM 7:00 PM 118152.0 71280 118152 46872
7:00 PM 12:00 PM 0.0 71280 118152 46872
12:00 PM 12:00 AM 0.0 71280 118152 46872

Max surplus 71280 lt = 71.28 cum


Provide Reservoir Capacity of 72.00 cum
c) Recommended Reservoir Size

Recommended Size for RVT 01 = #VALUE! cum Time to Fill the RVT #VALUE! Hr
Table C.2 : Reservoir Tank Sizing
CBWSS
SCHEME NAME : Baletaksar bazzar Lift
LOCATION : WARD NO : 4,5 VDC : Baletaksar DISTRICT : Gulmi

a) Scheme Information
a.1 Reservoir Tank No: 1
a.2 Served Standposts 1 to 8
a.3 Average Design Demand to be Supplied through Reservoir 1.313 l/s = 113475.000 l/day
a.4 Available Minimum flow from the Source (Safe Yield) 6.600 l/s

a.5 Adjusted/Optimized supply to Reservoir from Source 6.600 l/s = 570240.0 l/day
a.6 Total Design Flows of all Standposts : 15.760 l/s
b) Reservoir sizing assuming Continuous System using Consumption Patterns

Time Period Hours Water Cummu. Cummu. Surplus Deficit


From To Consumption Supply Demand
(%) (lt) (lt) (lt) (lt)
5:00 AM 7:00 AM 2 25.0% 47520 28369 19151
7:00 AM 12:00 AM 5 35.0% 166320 68085 98235
12:00 AM 5:00 PM 5 20.0% 285120 90780 194340
5:00 PM 7:00 PM 2 20.0% 332640 113475 219165
7:00 PM 5:00 AM 10 0.0% 570240 113475 456765

Maximum Deficit 0 lt
Minimum required Reservoir capacity 5.67 cum
Provide Reservoir of capacity 6.00 cum 5% of Average Demand
Check if Reservoir gets filled during night (7:00 PM - 5:00 AM)
Volume of water collected during night 237.60 cum

600000

500000

400000

300000

200000

100000

0
04:48 AM

02:24 PM

12:00 AM

04:48 AM
12:00 AM

09:36 AM

07:12 PM

09:36 AM

Column P Column Q

c) Reservoir sizing assuming Intermittent System (Optional)

Maximum Required supply hours based on Supply from Source 10.05 hours
Maximum Required supply hours based on Demand 2.00 hours
Adopted hours of Supply 2.00 hours
Recommended Supply Hours and Period
First Shift 7:00 AM To 9:00:00 AM
Second Shift To

Time Period Hours Cum. Inflow Cum. Con- Surplus Deficit


From To In Out (lt) sumption (lt) (lt) (lt)
7:00 AM 9:00:00 A 47520.00 113475.0 47520 113475 65955
9:00:00 AM 12:00 AM 23760.00 0.0 71280 113475 42195
12:00 AM 5:00 PM 71280.00 71280.0 142560 184755 42195
5:00 PM 7:00 AM 47520.00 0.0 190080 184755 5325

Max Deficit 65955 lt = 65.96 cum


Provide Reservoir Capacity of 66.00 cum
c) Recommended Reservoir Size

Recommended Size for RVT 01 = #VALUE! cum Time to Fill the RVT #VALUE! Hr
Table C.1 : Water Demand and Tap Flow Calculation Sheet

SCHEME NAME : Baletaksar bazzar Lift


SUPPORT ORGANIZATION :
LOCATION : WARD NO : 4,5 VDC : Baletaksar DISTRICT : Gulmi
Name of Community : baletaksar bazzar
Required Datas:
Peak Factor: 3
Per Capita Demand : 65 lpcd
Per Capita Demand for Students: 10 lpcd Minimum flow rate 0.10 lps Create RVT Sheets

Description of Tap Population forecast Institutional Water Demand Total Tap Flow Calculation
Tap Cluster Name Ward Nos Present YearBase Year Design Year Total No. of Other Total Live Water Average Peak Peak Design Adjusted Remarks
No or No. of 2014 2017 2037 Domestic Pupil in Institutional Institutional Stock Demand Tap Flow Factor Flow flow Peak
Locality HH (P) (Po) (Pn) Demand School Demand Demand Demand factor
(Nos) (Nos) P(1+r)^n1 P(l+r)^(n1+n) (lpd) (Nos) (lpd) (lpd) (lpd) (lpd) (lps) (Factor) (lps) (lps) (lps)
[1] [2] [2-1] [3] [4] [5] [6] [8] [9] [10] [11] [11-1] [12] [13] [14] [15] [16] [17] [18]
RVT1
T1-T47 Bazzar Rightside 47 266 279 348 24,360 24,360 0.28 3.00 0.85 0.85 3.00
T48-T87 Bazzar Leftside 40 190 199 249 17,430 350 3,500 20,930 0.24 3.00 0.73 0.73 3.00
T88-T111 GEU Tole 23 109 114 143 10,010 500 5,000 15,010 0.17 3.00 0.52 0.52 3.00
T112-T133 Aampokhara line 22 107 112 140 9,800 9,800 0.11 3.00 0.34 0.34 3.00
T134-T152 Bhairabthan line 19 139 146 182 12,740 12,740 0.15 3.00 0.44 0.44 3.00
T153-T158 Bajhkot 6 45 48 59 4,130 4,130 0.05 3.00 0.14 0.14 3.00
T159-T161 Bhairab than 3 22 24 29 2,030 2,030 0.02 3.00 0.07 0.10 4.35
T162-T166 Thadabato 5 26 28 34 2,380 2,380 0.03 3.00 0.08 0.10 3.57
T167-T182 Pariyar tole 16 122 128 160 11,200 11,200 0.13 3.00 0.39 0.39 3.00
T183-T190 Bajheri tole 8 41 43 54 3,780 3,780 0.04 3.00 0.13 0.13 3.00
T191-T193 Aarantole 3 19 20 25 1,750 1,750 0.02 3.00 0.06 0.10 5.00
T194-T196 Patira tole 3 17 18 23 1,610 1,610 0.02 3.00 0.06 0.10 5.26
T197-T213 Noonthala 17 94 99 123 8,610 8,610 0.10 3.00 0.30 0.30 3.00
T214-T231 Purano taksar right 18 73 77 96 6,720 6,720 0.08 3.00 0.23 0.23 3.00
T232-T243 Purano taksar Left 12 67 71 88 6,160 6,160 0.07 3.00 0.21 0.21 3.00

sub total 242 1,337 1,406 1,753 122,710 850 - 8,500 - 131,210 1.52 4.56 4.69

RVT2
T244-T263 Ranibas right side 20 100 105 131 9,170 9,170 0.11 3.00 0.32 0.32 3.00
T264-T293 Ghamtara 30 175 183 229 16,030 16,030 0.19 3.00 0.56 0.56 3.00
T294-T313 Ranibas left side 20 111 117 146 10,220 10,220 0.12 3.00 0.35 0.35 3.00
T314-T320 campus line 7 30 32 40 2,800 1,000 10,000 12,800 0.15 3.00 0.44 0.44 3.00
T321-T348 bamgha 28 151 158 198 13,860 250 2,500 16,360 0.19 3.00 0.57 0.57 3.00
T349-T365 Kunwar tole 17 90 95 118 8,260 10 10 50 8,320 0.10 3.00 0.29 0.29 3.00
T366-T373 Panitanki muni 8 55 58 72 5,040 95 95 45 5,180 0.06 3.00 0.18 0.18 3.00
T374-T382 Thaplung 9 68 72 89 6,230 6,230 0.07 3.00 0.22 0.22 3.00

sub total 139 780 820 1,023 71,610 1,250 105 12,605 95 84,310 0.98 2.93 2.93

Grand Total 381 2117 2226 2776 194320 2100 105 21105 215520 2.49 7.48 7.61 0.00

NOTE : 1 Peak factor of 3 has been adopted


2 Design Tap Flow has been adjusted for the Peak flow by rounding off to nearest 0.01lps.
3 If flow is less than 0.1 lps then it has been adjusted to 0.1 lps and if flow is greater than 0.25 lps provide additional tapstand.