Вы находитесь на странице: 1из 10

Technical Note No 33

BREATHER MEMBRANES AND VAPOUR CONTROL


LAYERS IN WALLS

Introduction • Corrosion of components


• Saturation and impairment of
This Technical Note concerns the use insulation
of vapour control layers and breather • Mould growth
membranes in built-up elements of
curtain walling and rainscreen This Note deals with the appropriate
cladding. Vapour control layers are use of vapour control layers and
provided where required to control the breather membranes within walls. It
migration of water vapour in to describes materials, condensation risk
elements of construction vulnerable to assessment and references relevant
condensation. The function of standards. A terminology is also
breather membranes is to provide a provided.
barrier against water penetration whilst
allowing migration of water vapour
through the membrane to the outside Water penetration resistance
of the building. The use of such layers
and membranes will depend upon the Resistance to water penetration may
anticipated performance of the be achieved by different means
element concerned. Means of depending on the type of construction.
assessing the risk of condensation is In drained and ventilated systems, any
given in the ‘Standard for specifying water passing though the outer water
and assessing condensation risk’, barrier drains in to a rebate or cavity
CWCT. and then out via drainage slots. Such
systems are generally designed to
Walls have to be constructed to prevent rainwater coming in to contact
provide water penetration resistance with materials that are intolerant of
so that: water.

• No water reaches the inner face of Walls such as ventilated rainscreen


the wall. walls are constructed with open joints
• No water reaches parts of the wall in the rainscreen. Some water may
where it might cause degradation pass the rainscreen and enter the
of the wall or adversely affect any cavity behind. Water in a wall cavity
aspect of its performance. may come into contact with the rear
face of the cavity (the insulation or
A wall has to be constructed to limit backing wall).
the moisture content within the wall to
acceptable levels. No condensation A breather membrane should be
should be allowed to form or collect in provided unless it can be established
any voids or interstices where such that:
water may have a deleterious effect on
the materials or on the wall’s • Any insulation in the cavity is
performance. resistant to wetting, for instance
some closed cell foams.
Water within a wall may cause
damage by: and

© CWCT 2003
October 2003
Breather membranes and vapour control layers in walls TN33

• No water reaches the backing wall, under which condensation will form
either directly or by migration and the need for any vapour control
through the insulation. layer. Suitable procedures for
condensation assessment are given
The breather membrane should be below.
placed either:
A condensation risk analysis may
• On the cavity face of any insulation show that no vapour control layer is
that is intolerant of water. required. However, designers may
• On the cavity face of the backing choose to incorporate an effective
wall if any insulation is resistant to vapour control layer rather than carry
wetting. out a condensation risk analysis. The
• On the cavity face of the backing provision of an effective vapour control
wall if no insulation is present in layer also adds to the robustness of
the cavity. the wall. It will limit moisture content
(Figure 1a) throughout the wall and help reduce
condensation at any cold bridges
remaining within the design or
A breather membrane will prevent introduced by shortcomings in
water passing inward through the wall workmanship.
but will allow water vapour to move
outward through the wall (see below). Where a vapour control layer is used
without calculating the wall
Further guidance on the specification temperatures it should be placed to
and design of rainscreen walls is given limit water vapour migrating from the
in ‘Standard and guide to good warm parts of the wall to the cooler
practice for ventilated rainscreen parts of the wall. Typically vapour
walls’, CWCT. control layers are placed:

• At the warm side of the dominant


Vapour control insulating layer,
- Between the insulation and
Water vapour control may be backing wall in a ventilated
necessary to maintain acceptable rainscreen wall.
moisture content throughout the wall.
The need for a vapour control layer will • At, or near, the inner face of the
depend on: wall,
• Vapour permeability of each - A dense plaster finish to a
layer blockwork wall.
• Temperatures within the wall - Foil backed plasterboard as a
• Internal and external moisture drylining behind a blockwork wall.
levels (Figure 1b)
• The effectiveness of any
ventilation of the cavities within A vapour control layer will control the
the wall. passage of both water and water
vapour. A breather membrane is not a
Condensation will form at any point in vapour control layer.
the wall where the moisture content is
high enough to give a dewpoint
greater than the actual temperature Vapour control layers
(Figure 2).
Vapour control layers may comprise
A condensation risk analysis may be metal sheets, metal foils, plastics,
performed to show the conditions polymeric sealants and liquid applied

2/10
Breather membranes and vapour control layers in walls TN33

coatings. The effectiveness of any


vapour control layer will depend on the Sometimes values of permeability are
material used and its installation. given in kg m s-1 Pa-1. Permeability is
the inverse of resistivity. Vapour
Materials used as vapour control control layers are more effective if
layers have to resist the passage of either:
water vapour. • The resistivity is greater
• The permeability is lower
For membranes and sheet materials
the vapour resistance of the material is Materials may be assessed according
given using units of MN s g-1 or Pa m2 to their water vapour resistance factor
s kg-1. For materials that are available (µ).
in various thicknesses a vapour
resistivity is given using units of MN s Vapour resistivity of material
g-1m-1or Pa m s kg-1. To calculate the µ=
Vapour resistivity of dry air
vapour resistance of a layer the
vapour resistivity is multiplied by the
This compares their performance with
thickness of the layer in metres.
the vapour resistance of dry air, which
is 5000 Pa s kg-1 m-1.
Note that the value of resistance
measured in Pa s kg-1 is 1000 times
Flexible sheet materials for use as
the value measured in MN s g-1.
vapour control layers are described in:
Typical vapour resistivity and vapour
resistance for various materials are • prEN 13970 - for bituminous
given below. In practice vapour materials
resistance achieved will be lower due • prEN 13984 - for plastic and
to holes and joints. rubber materials

For all materials watertightness is


Vapour assessed according to pr EN 1928 and
resistivity vapour transmission is assessed
Material (MN s g-1m-1) according to pr EN 1931.
Air space 5
Polyurethane 500-1000
Concrete Installation of a vapour control layer
Lightweight 30-80 may require the material to be lapped
Dense 200
Blockwork 20-150
or pierced by fixings. The materials
Brickwork 25-250 may also become pierced as a result
Stonework 150-450 of workmanship. The design should
Timber 40-70 have due regard for the means of
installation and the susceptibility to
condensation related problems.
Vapour
resistance
Where required, taping or sealing of
Material (MN s g-1) joints should be specified and
precautions taken to ensure that any
Sheet glass >10000 discontinuity or piercing of the layer by
Sheet metal >10000 essential fixings does not compromise
Aluminium foil 200-4000
Polyethylene (1000 gauge) 200-350 the performance. The objective
Polyethylene (500 gauge) 200-350 should be to provide a continuous
Vapour resistant paint 25 vapour control layer with any
Bitumen impregnated building 10 discontinuities limited so as not to
paper
100mm dense concrete 20
cause any significant reduction in
100mm brickwork 2-25 performance. An example of
100mm blockwork 2-15 discontinuities that may be harmless in

3/10
Breather membranes and vapour control layers in walls TN33

low humidity environments include the much lower than for vapour control
small gaps between foil backing on materials.
adjacent sheets of plasterboard. In a
rainscreen wall the vapour control Breather membranes also have to
material may be lapped behind a have tear resistance.
horizontal rail to ensure a closer
contact between adjacent sheets of BS 4016 covers watertightness,
material. vapour transmission and tear
resistance of breather membranes.
In the detailing of buildings, it is
commonplace for significant Having decided in principle to use a
discontinuities in vapour control layers breather membrane, care is required
to occur at the interfaces of adjacent in selection. Some membrane
elements, such as window reveals. It materials will transmit liquid water if
is therefore essential that interfaces they are in contact with a material
between different elements and beneath. The phenomenon is
subcontract packages are duly sometimes referred to as “tenting”.
considered and addressed during the Some membranes may deteriorate
design and detailing stages. with age or if subjected to
contaminated water run-off, again
Flexible sheet materials used for increasing their susceptibility to liquid
vapour resistance also have to be tear water transmission. Consideration
resistant and durable. Some materials also needs to be given as to whether
have been tested to standards that the membrane needs to be fire-
apply to fabrics for garments these resistant. In rainscreen cladding, the
tests are not suitable for building membrane and its jointing may also
materials. need to resist wind suction loads.

Properties of non-sheet materials to Design principles


be used in walls can be obtained from
BS EN 12524 or determined in Moisture is introduced into buildings
accordance with BS EN ISO through life processes, heating
12572:2001. equipment and activities such as
cooking, bathing and so on. Water
BS EN 12086:1997 and BS EN ISO vapour may be removed by natural
7783-2:1999 also give test methods ventilation or air conditioning.
for water vapour resistance. BS However, there must be water vapour
7374:1990 has been withdrawn. in the air to make a room comfortable
for habitation.

Breather membranes Water vapour disperses through the


air and migrates through porous solids
Materials used as breather in an attempt to give uniform vapour
membranes comprise sheet materials pressure. In the UK external air
that contain many very small holes or moisture contents are lower than
pores. These are large enough to internal levels and water vapour
allow water vapour to pass but resist moves outward through the wall. For
the passage of liquid water. air-conditioned buildings in some
warm and humid climates water
Vapour resistance is measured in vapour moves inward through the wall.
ways similar to those described for
vapour control layers. However, the Water vapour should not migrate past
vapour resistance values will be very one vapour control layer only to be

4/10
Breather membranes and vapour control layers in walls TN33

stopped by a subsequent breather internal panels are added. These will


membrane which incorrectly acts as a often provide insulation so that the
vapour control layer, or by a second cavity is cooler than the room but
vapour control layer. provide very little resistance to vapour
movement. Solutions are ventilating
• Breather membranes marketed as these cavities to the room so that they
products should have a vapour are warm and incorporating the vapour
resistance less than 0.6 MN s g-1 control layer in the inner wall panel as
so that the vapour resistance is is done with foil backed dry lining.
always much less than that of any
other layers in the wall. A Rainscreen cavities should be
condensation risk analysis may ventilated so that any water ingress
show that a higher vapour stopped by a breather membrane will
resistance is acceptable but values dry out after drainage has removed
in excess of 5 MN s g-1 are most of the water.
unnecessary and may lead to
problems if the vapour control Two layers having similar vapour
layer is impaired. resistance should be avoided. A
metal sheet can be perforated to avoid
• There should normally be only one the creation of an unwanted vapour
vapour control layer in a wall. If barrier. Note that it may then be
there are two or more vapour necessary to provide a breather
control layers. For instance a membrane to prevent water entering
panel with metal skins on both by passing the perforated sheet.
sides. Then particular
consideration has to be given to Avoidance of mould growth on the
the air moisture content in any internal surface is achieved by limiting
cavities between vapour control the moisture level at the internal
layers. Two vapour control layers surface. This can be achieved by
may be constructed of the same ventilating the room or better insulating
material but if the inner layer is the wall to raise the temperature of the
perforated then water vapour will internal surface. BS EN ISO
migrate in to the cavity where it will 13788 recommends that the relative
be retained. humidity at the internal surface should
be less than 80% to avoid mould
• As a general rule, in the UK, the growth.
vapour resistivity of successive
layers should decrease from inside
to outside. Condensation assessment

• As a general principle all cavities Condensation assessment requires


should be either ventilated or knowledge of the moisture contents
hermetically sealed, for instance and temperatures within a wall.
an insulated glazing unit. Building envelopes containing a single
well defined layer offering high vapour
resistivity at the warm side of the
Precautions construction can often be assessed as
acceptable by inspection. For walls
Cavities formed on the warm and with no well-defined vapour control
humid side of a vapour control layer or one that is in a cooler part of
barrier may be affected by severe the construction an analysis is
condensation. Cavities may be required.
formed as part of the internal building
fit out when window boards and

5/10
Breather membranes and vapour control layers in walls TN33

To assess condensation risk it is • The actual temperatures are


necessary to know the internal and used to calculate saturation
external temperatures and moisture vapour pressures that are
levels, the psychrometric conditions. compared with the vapour
pressures, (This is the method
Psychrometric conditions depend used in BS 5250).
on the time of year and the activities
within a building.

BS 6229 gives the following values for Walls of complex geometry may
use in the UK: contain elements such as framing
members that form thermal bridges.
R.H. (%) T (oC) These make it difficult to calculate
Internal temperatures within the wall.
Storage 35 15 However, these walls often comprise a
Offices/shops 40 20 series of layers that offer resistance to
High occupancy 55 20 moisture movement within the wall. A
dwellings simple layered system may be
Swimming pools >70 25 analysed to determine the moisture
and similar content at the different layers through
the wall. From this can be determined
External the dewpoint temperatures. If actual
Summer 65 18 temperatures within the wall can be
Winter 90 -5 estimated then a rough assessment
can be made of the risk of
Although originally intended for the condensation forming within the wall.
design of roofs these values have
been widely used for all building Temperatures can be estimated using
envelopes in the UK. the following:

BS EN ISO 13788 gives moisture For materials that are good and
levels as moisture content in kg m-3, uniform insulators throughout their
which is independent of internal thickness the temperature gradient
temperature. The values given are through the material will be uniform.
lower than those given in BS 6229.
BS EN ISO 13788 gives even lower For thermally broken aluminium
internal moisture levels for buildings in profiles (and similarly isolated good
warmer climates. conductors) the two metal profiles will
be at uniform but different
Plane layered walls such as a block temperatures. Each will be at or near
or brick cavity wall can be assessed the temperature of the extreme
for condensation risk using a method surface of the metal profile.
of the Glaser type. Such a procedure
is used in BS 5250 and DIN 4108. Unless the simple procedure
described above shows conclusively
Firstly temperatures and vapour that condensation risk is acceptable
pressures are calculated throughout then a full condensation risk analysis
the wall then either: should be carried out. Standard for
specifying and assessing for
• Dewpoint temperatures are condensation risk, CWCT, describes
calculated from the vapour suitable procedures, which include
pressures and compared with calculation of temperatures throughout
the actual temperatures. the wall by a finite element or finite
Or difference method.

6/10
Breather membranes and vapour control layers in walls TN33

Saturation vapour pressure – Water


Extreme moisture levels may vapour pressure in air at dewpoint
necessitate a more complex model temperature.
than those described above. Most
modelling assumes vapour Thermal bridge – Part of a structure
transmission through the materials. of lower thermal resistance which may
However at very high moisture levels lead to colder or warmer surfaces.
water vapour may be drawn in to
porous materials by capillary action. Vapour control layer – Construction
material that substantially reduces the
Ventilation within cavities and over water vapour transfer through any
surfaces may transport moisture. building element in which it is
incorporated.
Non-steady state models can be
adopted. Unlike the steady state Vapour pressure – That part of
models described above these take atmospheric pressure that is due to
account of the variation of water vapour present in the air.
psychrometric conditions over time.
Vapour resistance – Measure of the
Commercial software is available resistance to water vapour diffusion of
including packages such as GLASTA a material of specific thickness.
and WUFI.
Vapour resistivity – Measure of
Results from the above analyses will resistance of a unit thickness of
be accurate calculations but they are material to water vapour diffusion
based on many assumptions about when a difference of unit vapour
psychrometric conditions, materials pressure exists between the air on
and workmanship. They should be opposite sides of the material.
used with caution and if there is even
a near risk of condensation careful Water vapour – Water in its invisible
consideration should be given to gaseous phase.
improving the wall.

Standards
Terminology
BS 4016:1997 - Specification for
Breather membrane – Flexible sheet flexible building membranes (breather
that resists the passage of liquid water type) - Current
but allows water vapour to pass.
BS 5250:1989 - Code of practice for
Dewpoint – Temperature at which control of condensation in buildings -
vapour pressure becomes saturated Current, Work In Hand
vapour pressure.
BS 6229:1982 - Flat roofs with
Moisture content – Proportion of continuously supported coverings
water contained within a material.
BS EN ISO 7783-2:1999 - Paints and
Relative humidity – Ratio of vapour varnishes. Coating materials and
pressure in air at a given temperature coating systems for exterior masonry
to the saturation vapour pressure at and concrete. Determination and
the same temperature. classification of water-vapour
transmission rate (permeability) -
Current

7/10
Breather membranes and vapour control layers in walls TN33

BS EN 12086:1997 - Thermal rubber sheets for roof waterproofing –


insulating products for building Determination of watertightness.
applications. Determination of water
vapour transmission Properties - BS EN 1931:2000 - Flexible sheets for
Current waterproofing – Bitumen, plastic and
rubber sheets for roof waterproofing –
BS EN 12524:2000 - Building Determination of water vapour
materials and products – Hygrothermal transmission properties
properties – Tabulated design values
prEN 13970 - Flexible sheets for
BS EN ISO 12572:2001 - waterproofing. Bitumen water vapour
Hygrothermal performance of building control layers. Definitions and
materials and products. Determination characteristics - Current, Draft for
of water vapour transmission Public Comment
properties – Current
prEN 13984 - Flexible sheets for
BS EN ISO 13788:2002 – waterproofing. Plastic and rubber
Hygrothermal performance of building vapour control layers. Definitions and
components and building elements – characteristics - Current, Draft for
Internal surface temperature to avoid Public Comment
critical surface humidity and interstitial
condensation - Calculation methods
References
BS EN 1928:2000 - Flexible sheets for Standard for specifying and assessing
waterproofing – Bitumen, plastic and condensation risk (2nd Edition), CWCT,
2002, ISBN 1 87 4003 42 4.

8/10
Breather membranes and vapour control layers in walls TN33

Figure 1a. Position of a breather membrane

Figure 1b. Position of a vapour control layer

9/10
Breather membranes and vapour control layers in walls TN33

Figure 2. Temperatures and dewpoint temperatures in a wall

© CWCT 2000
CWCT Technical Notes 1 – 30 have been part-
funded by the DETR under research contract
39/3/338 (CI 1354)

University of Bath, Claverton Down, Bath,


BA2 7AY
Tel: 01225 386541; Fax: 01225 386556;
email: cwct@bath.ac.uk; website:
www.cwct.co.uk

10/10

Вам также может понравиться