Академический Документы
Профессиональный Документы
Культура Документы
© CWCT 2003
October 2003
Breather membranes and vapour control layers in walls TN33
• No water reaches the backing wall, under which condensation will form
either directly or by migration and the need for any vapour control
through the insulation. layer. Suitable procedures for
condensation assessment are given
The breather membrane should be below.
placed either:
A condensation risk analysis may
• On the cavity face of any insulation show that no vapour control layer is
that is intolerant of water. required. However, designers may
• On the cavity face of the backing choose to incorporate an effective
wall if any insulation is resistant to vapour control layer rather than carry
wetting. out a condensation risk analysis. The
• On the cavity face of the backing provision of an effective vapour control
wall if no insulation is present in layer also adds to the robustness of
the cavity. the wall. It will limit moisture content
(Figure 1a) throughout the wall and help reduce
condensation at any cold bridges
remaining within the design or
A breather membrane will prevent introduced by shortcomings in
water passing inward through the wall workmanship.
but will allow water vapour to move
outward through the wall (see below). Where a vapour control layer is used
without calculating the wall
Further guidance on the specification temperatures it should be placed to
and design of rainscreen walls is given limit water vapour migrating from the
in ‘Standard and guide to good warm parts of the wall to the cooler
practice for ventilated rainscreen parts of the wall. Typically vapour
walls’, CWCT. control layers are placed:
2/10
Breather membranes and vapour control layers in walls TN33
3/10
Breather membranes and vapour control layers in walls TN33
low humidity environments include the much lower than for vapour control
small gaps between foil backing on materials.
adjacent sheets of plasterboard. In a
rainscreen wall the vapour control Breather membranes also have to
material may be lapped behind a have tear resistance.
horizontal rail to ensure a closer
contact between adjacent sheets of BS 4016 covers watertightness,
material. vapour transmission and tear
resistance of breather membranes.
In the detailing of buildings, it is
commonplace for significant Having decided in principle to use a
discontinuities in vapour control layers breather membrane, care is required
to occur at the interfaces of adjacent in selection. Some membrane
elements, such as window reveals. It materials will transmit liquid water if
is therefore essential that interfaces they are in contact with a material
between different elements and beneath. The phenomenon is
subcontract packages are duly sometimes referred to as “tenting”.
considered and addressed during the Some membranes may deteriorate
design and detailing stages. with age or if subjected to
contaminated water run-off, again
Flexible sheet materials used for increasing their susceptibility to liquid
vapour resistance also have to be tear water transmission. Consideration
resistant and durable. Some materials also needs to be given as to whether
have been tested to standards that the membrane needs to be fire-
apply to fabrics for garments these resistant. In rainscreen cladding, the
tests are not suitable for building membrane and its jointing may also
materials. need to resist wind suction loads.
4/10
Breather membranes and vapour control layers in walls TN33
5/10
Breather membranes and vapour control layers in walls TN33
BS 6229 gives the following values for Walls of complex geometry may
use in the UK: contain elements such as framing
members that form thermal bridges.
R.H. (%) T (oC) These make it difficult to calculate
Internal temperatures within the wall.
Storage 35 15 However, these walls often comprise a
Offices/shops 40 20 series of layers that offer resistance to
High occupancy 55 20 moisture movement within the wall. A
dwellings simple layered system may be
Swimming pools >70 25 analysed to determine the moisture
and similar content at the different layers through
the wall. From this can be determined
External the dewpoint temperatures. If actual
Summer 65 18 temperatures within the wall can be
Winter 90 -5 estimated then a rough assessment
can be made of the risk of
Although originally intended for the condensation forming within the wall.
design of roofs these values have
been widely used for all building Temperatures can be estimated using
envelopes in the UK. the following:
BS EN ISO 13788 gives moisture For materials that are good and
levels as moisture content in kg m-3, uniform insulators throughout their
which is independent of internal thickness the temperature gradient
temperature. The values given are through the material will be uniform.
lower than those given in BS 6229.
BS EN ISO 13788 gives even lower For thermally broken aluminium
internal moisture levels for buildings in profiles (and similarly isolated good
warmer climates. conductors) the two metal profiles will
be at uniform but different
Plane layered walls such as a block temperatures. Each will be at or near
or brick cavity wall can be assessed the temperature of the extreme
for condensation risk using a method surface of the metal profile.
of the Glaser type. Such a procedure
is used in BS 5250 and DIN 4108. Unless the simple procedure
described above shows conclusively
Firstly temperatures and vapour that condensation risk is acceptable
pressures are calculated throughout then a full condensation risk analysis
the wall then either: should be carried out. Standard for
specifying and assessing for
• Dewpoint temperatures are condensation risk, CWCT, describes
calculated from the vapour suitable procedures, which include
pressures and compared with calculation of temperatures throughout
the actual temperatures. the wall by a finite element or finite
Or difference method.
6/10
Breather membranes and vapour control layers in walls TN33
Standards
Terminology
BS 4016:1997 - Specification for
Breather membrane – Flexible sheet flexible building membranes (breather
that resists the passage of liquid water type) - Current
but allows water vapour to pass.
BS 5250:1989 - Code of practice for
Dewpoint – Temperature at which control of condensation in buildings -
vapour pressure becomes saturated Current, Work In Hand
vapour pressure.
BS 6229:1982 - Flat roofs with
Moisture content – Proportion of continuously supported coverings
water contained within a material.
BS EN ISO 7783-2:1999 - Paints and
Relative humidity – Ratio of vapour varnishes. Coating materials and
pressure in air at a given temperature coating systems for exterior masonry
to the saturation vapour pressure at and concrete. Determination and
the same temperature. classification of water-vapour
transmission rate (permeability) -
Current
7/10
Breather membranes and vapour control layers in walls TN33
8/10
Breather membranes and vapour control layers in walls TN33
9/10
Breather membranes and vapour control layers in walls TN33
© CWCT 2000
CWCT Technical Notes 1 – 30 have been part-
funded by the DETR under research contract
39/3/338 (CI 1354)
10/10