CFL

GENERAL NOTES AND SPECIFICATIONS PANELBOARD (UNIT II)

CAPACITY OCPD
VOLTAG CURRENT SIZEAND TYPE OF SIZE OF PIN LIGHT
DESCRIPTION (VA) RATING
E (A) CONDUCTOR (mm2)
1. ALL WORKS SHALL COMPLY WITH THE (V)
CONDUIT AT POLE

PROVISIONS OF THE LATEST APPROVED EDITION 1


LIGHTING LOAD (5-100W LIGHTING OUTLET, 9-25W
PINLIGHTS) 725 230 3.15
2-2.0 THHN cu WIRE
15 15 2 DUPLEX CONVENIENCE
OF THE PHILIPPINES ELECTRICAL CODE, WITH THE OUTLET
2

LIGHTING LOAD (7-100W LIGHTING OUTLET, 10-25W 2-2.0 THHN cu WIRE


950 230 4.13 15 15 2
RULES AND REGULATIONS OF THE NATIONAL AND 2 PINLIGHTS)
DUPLEX
LOCAL AUTHORITY CONCERNED IN THE 3
CONVINIENCE OUTLET (7-360W DUPLEX)
2520 230 10.96
2-3.5 THHN cu WIRE
15 20 2
WP WHEATHERPROOF
CONVENIENCE
ENFORCEMENT OF ELECTRICAL LAWS AND CONVINIENCE OUTLET (8-360W DUPLEX) 2-3.5 THHN cu WIRE
4 2880 230 12.52 15 20 2 POWER PANEL BOARD
ORDINANCES AND WITH THEIR REGULATIONS OF
THE UTILITY COMPANY CONCERNED. 5 SPARE 2880 230 12.52 2-3.5 THHN cu WIRE
15 20 2

2-3.5 THHN cu WIRE


6 SPARE 2520 230 10.96 15 20 2
2. TYPE OF SERVICE SHALL BE 230/110V,
1Ø(SINGLE PHASE), 2-WIRE SYSTEM, 60Hz AND
THERE SHALL BE ONLY ONE SERVICE TO THE
BUILDING. 2 LOAD SCHEDULE 6 LEGENDS AND SYMBOLS
E3 E3

3. METHOD OF WIRING SHALL BE IN RIGID NON- NTS NTS


METALLIC CONDUIT FOR BOTH EXPOSED AND
EMBEDDED WORK WITH PROPER FITTINGS AND BRANCH CIRCUIT 1: LIGHTING OUTLET BRANCH CIRCUIT 3 : POWER OUTLET

SUPPORTS, UNLESS OTHERWISE SPECIFIED. A. L.O. : 5 x 100 VA = 500 VA DUPLEX CONVENIENCE: 7 x 360 VA = 2520 VA
P.L. : 9 x 25 VA = 225 VA
725 VA
FLA : 2520 VA / 230 V = 10.96 A
2520 VA
M ELECTRICAL SERVICE METER

4. ALL MATERIAL AND OR EQUIPMENTS SHALL BE FLA : 725 VA / 230 V = 3.15A


BRAND NEW AND OF APPROVED TYPE AS TO Q. CONDUCTOR AND CONDUIT SIZE
A. CONDUCTOR AND CONDUIT SIZE
FLA x 125%
LOCATION AND PURPOSE. THE SELECTION OF THE FLA x 100%
3.15 A x 100% = 3.15 A
10.96 A x 125% = 13.7 A
LIGHTING OUTLET 1
15 AT
2.0mm² 2.0mm²
15 AT
2 LIGHTING OUTLET
MATERIALS FOR MATERIALS FOR ELECTRICAL CONDUCTOR SIZE
CONDUCTOR SIZE
USE 2-2.0 mm² THHN Cu WIRE
20 AT 20 AT
CONVENIENCE OUTLET 3 3.5mm² 3.5mm²
4 CONVENIENCE OUTLET
WORKS SHALL BE OWNERS CHOICE. USE 2-2.0 mm² THW Cu WIRE
WITH AN AMPACITY OF 20 A
WITH AN AMPACITY OF 25 A
20 AT 20 AT
CONDUIT SIZE 5 3.5mm² 3.5mm²
6
CONDUIT SIZE USE 15 mm Ø RIGID PVC
SPARE SPARE
5. ALL WALL OUTLETS SHALL BE INTALLED AT USE 15 mm Ø RIGID PVC
B. OVERCURRENT PROTECTION DEVICE
THE FOLLOWING HEIGHTS ABOVE FINISHED FLOOR R. OVERCURRENT PROTECTION DEVICE
FLA x 125%
FLA x 150%
10.96 A x 150% = 16.44 A
LEVEL OTHERWISE NOTED 3.15 A x 125% = 3.94 A
USE 1 - 15 AMPERE TRIP
USE 1 - 20 AMPERE TRIP
2 - POLE CIRCUIT BREAKER
2 - POLE CIRCUIT BREAKER

A. WALL SWITCHES 1.2 METERS BRANCH CIRCUIT 2: LIGHTING OUTLET


BRANCH CIRCUIT 4 : POWER OUTLET

DUPLEX CONVENIENCE: 6 x 360 VA = 2880 VA


4 RISER DIAGRAM
E3
B. CONVENIENCE OUTLET 0.30 METERS A. L.O. : 7 x 100 VA = 700 VA
W.L. : 10 x 25 VA = 250 VA 2880 VA NTS
C. CONVENIENCE OUTLET 0.15 METERS 950 VA
FLA : 2880 VA / 230 V = 12.5217 A
ABOVE COUNTER
ACU
FLA : 950 VA / 230 V = 4.13 A PANEL BOARD BLANK PLATE
A. CONDUCTOR AND CONDUIT SIZE
D. FIRE ALARM STATION OUTLET1.50 METERS
COUNTERTOP
X. CONDUCTOR AND CONDUIT SIZE FLA x 125% CONVENIENVE OUTLET
FLA x 100% 12.5217 A x 125% = 15.6521 A
E. FIRE ALARM BELL OUTLET 2.75 METERS 4.13 A x 100% = 4.13 A
CONDUCTOR SIZE
ELECTRIC
METER

F. PANELBOARD AND SAFETY 1.35 METERS CONDUCTOR SIZE


USE 2-2.0 mm² THW Cu WIRE
USE 2-2.0 mm² THHN Cu WIRE
WITH AN AMPACITY OF 25 A
SWITCH

SWITCHES WITH AN AMPACITY OF 20 A


CONDUIT SIZE
G.SERVICE KILOWATT-HOUR 1.60 METERS

300
CONDUIT SIZE USE 15 mm Ø RIGID PVC
USE 15 mm Ø RIGID PVC
METER

1800

1800
B. OVERCURRENT PROTECTION DEVICE CONVENIENCE
WATER PROOF OUTLET
Y. OVERCURRENT PROTECTION DEVICE FLA x 150%
OUTLET
FLA x 125% 12.5217 A x 150% = 18.7826 A

1300

1600
4.13 A x 125% = 5.16 A USE 1 - 20 AMPERE TRIP
USE 1 - 15 AMPERE TRIP 2 - POLE CIRCUIT BREAKER
2 - POLE CIRCUIT BREAKER

300
500
FFL

1 GENERAL NOTES & SPECIFICATIONS FGL


E3

NTS 3 LOAD ANALYSIS


E3 5 MOUNTING HEIGHT DETAILS
NTS E3

NTS

Project Title Owner Sheet Content Project number 001


GENERAL NOTE AND SPECIFICATION
1
Date 06/12/2020
Emelita De La Cruz 2 LOAD SCHEDULE
ENGINEER
De La Cruz Residential Building(Upgrade) 3 LOAD ANALYSIS
PRC. REG no . E3

23/06/2020 11:10:03 AM
Drawn by
4 RISER DIAGRAM Date
ENGR. JULIUS MAE TOLENTINO

Gumamela St. Villa Antonio Subd. Phase II, Gumamela St. Villa Antonio Subd. Phase II, 5 MOUNTING HEIGHT DETAILS Place
Location San Pablo CIty
Location San Pablo CIty Scale As indicated
6 LEGEND AND SYMBOLS