FRAME 2014C / 2024C WINDING 6

MODELS LL2014C / LL2024C / LL2034C REF: F2004CW6-3 APRIL 2010

WINDING DETAILS MECHANICAL DETAILS


Code 6 Insulation class H Standard protection IP23
Phase 3 Leads 12 Overspeed rpm 2250
Pole number 4 Pitch 2/3 Air flow 50Hz/60Hz m3/s 0.27 / 0.32

EXCITATION DETAILS WAVEFORM


Excitation system SHUNT AREP/PMG Line voltage on no load or balanced linear rated load
AVR model R250 R438 Total harmonic content THC <4%
Sustained short-circuit current - 300%:10s Telephone influence factor TIF (NEMA) <50
Steady state voltage regulation ±0.5% ±0.5% Telephone harmonic factor THF (IEC) <2%

LINE VOLTAGE No overvoltage tolerance for 440V 50Hz excitation level


Frequency / speed 50Hz / 1500rpm 60Hz / 1800rpm
Series star V 380 400 415 440 380 400 416 440 460 480
Series delta V 220 230 240 220 230 240
Parallel star V 200 208 220 200 208 220 230 240
1 2 3 4 6 7 8 9 10 11
RATING Power factor 0.8, Altitude <=1000m
Class H rise BR 125/40 kVA 48.0 48.0 48.0 46.0 52.0 55.0 56.0 59.0 61.0 63.0
kW 38.4 38.4 38.4 36.8 41.6 44.0 44.8 47.2 48.8 50.4
Class H rise PR 150/40 kVA 50.9 50.9 50.9 48.8 55.1 58.3 59.4 62.5 64.7 66.8
kW 40.7 40.7 40.7 39.0 44.1 46.6 47.5 50.0 51.8 53.4
Class H rise PR 163/27 kVA 53.0 53.0 53.0 51.0 57.0 61.0 62.0 65.0 67.0 69.0
kW 42.4 42.4 42.4 40.8 45.6 48.8 49.6 52.0 53.6 55.2
Class F rise BR 105/40 kVA 43.0 43.0 43.0 41.9 47.3 50.1 51.0 53.7 55.5 57.3
kW 34.4 34.4 34.4 33.5 37.9 40.0 40.8 43.0 44.4 45.9

EFFICIENCIES Power factor 0.8


110% Class H BR % 86.4 86.9 87.1 87.1 85.7 86.0 86.5 86.9 87.2 87.4
100% Class H BR % 87.1 87.6 87.7 87.6 86.5 86.8 87.2 87.6 87.8 88.0
75% Class H BR % 88.8 89.0 89.0 88.5 88.2 88.5 88.8 89.0 89.2 89.2
50% Class H BR % 89.9 89.8 89.5 88.4 89.4 89.6 89.7 89.8 89.8 89.7
25% Class H BR % 88.6 87.8 87.1 84.8 88.1 88.2 88.1 87.9 87.7 87.3

CHARACTERISTIC PARAMETERS Reactance base class H BR rating


Kc Short-circuit ratio 0.32 0.38 0.46 0.62 0.22 0.24 0.27 0.30 0.32 0.35
Xd D-Axis synchronous reactance (unsaturated) pu 3.39 3.06 2.84 2.42 4.40 4.20 3.96 3.73 3.52 3.34
X'd D-Axis transient reactance (saturated) pu 0.15 0.13 0.12 0.11 0.19 0.18 0.17 0.16 0.15 0.15
X''d D-Axis sub-transient reactance (saturated) pu 0.075 0.068 0.063 0.053 0.097 0.093 0.087 0.082 0.078 0.074
Xq Q-Axis synchronous reactance (unsaturated) pu 2.03 1.83 1.70 1.45 2.64 2.52 2.37 2.24 2.11 2.01
X''q Q-Axis sub-transient reactance (saturated) pu 0.094 0.085 0.079 0.067 0.122 0.116 0.110 0.103 0.098 0.093
X2 Negative-sequence reactance (saturated) pu 0.084 0.076 0.070 0.060 0.109 0.104 0.098 0.092 0.087 0.083
X0 Zero-sequence reactance (independent) pu 0.006 0.005 0.005 0.004 0.007 0.007 0.006 0.006 0.006 0.005
T'd D-Axis transient time constant ms 50 50
T''d D-Axis sub-transient time constant ms 5 5
T'do D-Axis open-circuit time constant ms 1131 1131
Ta Armature time constant ms 8 8
Tr Voltage recovery time ms < 500 < 500

EXCITATION VOLTAGE AND CURRENT


Quoted for SHUNT. For AREP/PMG multiply voltage by 0.5 and multiply current by 2
No load excitation voltage V 7.7 8.5 9.4 11.4 5.7 6.3 6.4 7.2 7.7 8.5
No load excitation current A 0.42 0.46 0.51 0.62 0.31 0.34 0.35 0.39 0.42 0.46
Class H BR excitation voltage V 31.3 31.6 32.4 33.7 30.4 30.9 30.9 31.6 32.4 33.5
Class H BR excitation current A 1.70 1.72 1.76 1.83 1.65 1.68 1.68 1.72 1.76 1.82

WINDING RESISTANCE At 20 o C
Stator line-to-line (series star) Ω 0.310 Exciter field (series connection -SHUNT) Ω 18.40
Main field Ω 1.35 Exciter field (parallel connection -AREP/PMG) Ω 4.60

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 2014C / 2024C WINDING 6

MODELS LL2014C / LL2024C / LL2034C REF: F2004CW6-3 APRIL 2010

LOCKED ROTOR MOTOR STARTING CURVES Power factor 0.6

50 Hz SHUNT

380V

400V
415V

440V
35

30

25
voltage dip %

20

15

10

0
0 20 40 60 80 100 120 140 160 180
kVA

50 Hz AREP / PMG
380V

400V

415V

440V

35

30

25
voltage dip %

20

15

10

0
0 20 40 60 80 100 120 140 160 180
kVA

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 2014C / 2024C WINDING 6

MODELS LL2014C / LL2024C / LL2034C REF: F2004CW6-3 APRIL 2010

LOCKED ROTOR MOTOR STARTING CURVES Power factor 0.6

60 Hz SHUNT

380V
400V
416V

440V

460V

480V
35

30

25
voltage dip %

20

15

10

0
0 20 40 60 80 100 120 140 160 180
kVA

60 Hz AREP / PMG
380V

400V

416V

440V

460V

480V

35

30

25
voltage dip %

20

15

10

0
0 20 40 60 80 100 120 140 160 180
kVA

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33
Values quoted are typical. In line with our policy of continuous improvement, we reserve the right to change specification without notice.
FRAME 2014C / 2024C WINDING 6

MODELS LL2014C / LL2024C / LL2034C REF: F2004CW6-3 APRIL 2010

THREE-PHASE SHORT-CIRCUIT DECREMENT CURVES No-load excitation at rated speed

400V 50Hz, 480V 60Hz Series Star

10000

asymmetrical
RMS current (A)

1000
symmetrical AREP/PMG

100

SHUNT

10
1 10 100 1000 10000
time (ms)

Multiplication Factors

50Hz Voltages 380 400 415 440

Multiplication Factor 0.95 1.00 1.04 1.10

Apply factor up to 2xT'd, remainder of curve unchanged

60Hz Voltages 380 400 416 440 460 480

Multiplication Factor 0.79 0.83 0.87 0.92 0.96 1.00

Apply factor up to 2xT'd, remainder of curve unchanged

Winding Connection Series Star Parallel Star Series Delta

Multiplication Factor 1.00 2.00 1.73

Apply factor to the complete curve

According to: IEC 60034, UTE NFC51.111, VDE 0530, BS 4999/5000, NEMA MG 1-33