Generator protection with machine differential protection 2 Product introduction

Easergy P3 Standard Easergy P3 Advanced

Withdrawability (Pluggable ■ –
connector)

Remote UMI – ■

NOTE: The numbers in the following tables represent the amount of stages
available for each Easergy P3 type.
Table 4 - Protection functions for P3U

Protection functions ANSI Feeder Feeder P3U30 Motor P3U10/20 Motor P3U30
code P3U10/20

Fault locator 21FL – 1 – 1

Synchronization check4 25 – 2 – 2

Undervoltage 27 – 3 – 3

Directional active 32 – 2 – 2
underpower

Phase undercurrent 37 1 1 1 1

Temperature monitoring5 38/49T 12 12 12 12

Negative sequence 46 – – 2 2
overcurrent (motor,
generator)

Incorrect phase sequence 46 – – 1 1

Cur. unbalance, broken 46BC 1 1 – –


conductor

Negative sequence 47 – 3 – 3
overvoltage protection

Excessive start time, 48/51LR – – 1 1


locked rotor

Thermal overload 49 1 1 1 1

Phase overcurrent 50/51 3 3 3 3

Earth fault overcurrent 50N/51N 5 5 5 5

Breaker failure 50BF 1 1 1 1

SOTF 50HS 1 1 1 1

Capacitor bank 51C 2 2 2 2


unbalance6

Voltage-dependent 51V – 1 – 1
overcurrent

Overvoltage 59 – 3 – 3

Capacitor overvoltage 59C 1 1 – –

Neutral voltage 59N 3 3 3 3


displacement

CT supervision 60 1 1 1 1

22 P3G/en M/F006