Subject: Fw d: Re: Huhtam aki -Egypt tendering com m ent Date: 17/08/17 10:46

To: AL JASSIM ENGINEERING CONSULTANTS <ajeconsl@ajeconsl.ae> From: Delmont Technical <delmonttech@gmail.com>

design criteria.pdf (26kB) CO2 CALCULATION.pdf (19kB)

Dear Sir,

Please find our below reply to your queries.

Regards,

Pushkar Thakkar
Delmont Fire & Safety LLC
055-5125049

Dear Pushkar,

with reference to the above mail,please clarify what has to be done.

. Missing documents:-
a. Firefighting specifications.

2. Firefighting:-
a. Required capacity for the following items
i. (foam trolley - 20 gal.) - factory area -14 nos. & Ink and adhesive area - 3 nos.
b. Required description for the following items
i. All sprinkler required (k- factor , temperature rating , response type )- upright k-5.6,pendent k 5.6 foam water sprinkler head upright k-115,
esfr sprinkler head k -14 @ 5.2 bar,inrack sprinkler head - upright/pendent -k 5.6 with guard- AS ATTACHED
ii. Foam suppression system (system equipment with required size and capacity )- Generator room - 74.6 sq.m required 80 gal. afff foam
concentrate and upright foam bladder tank 100 gal. - 1 no. Ink and Adhesive area
required -288 gal. afff foam concentrate and upright foam bladder tank 300 gal. - 1 no. Ink mixing factory area required -288 gal. afff foam
concentrate and upright foam bladder tank 300 gal. - 1 no. AS ATTACHED
iii. All cabinet -
Surafce mounted Full Mild Steel - 19 nos. factory area & Ink and Adhesive area - 3 Nos. & scrap yard - 1 nos.
Surafce mounted Full Stainless Stell - 9 nos.
c. Required size for the following items
a. Zone control station item
factory area: groundf floor
Cold seal ,office coriidor,corridor changing room,product manger- 4" ZCV - 5 no. Corridor 3" ZCV- 1 nos. Slitting
area- 6" ZCV - 1 No.
Factory area: Mezzanine floor
Office ,Prayer room & canteen - 4" ZCV - 3 nos. Ink mixing,esfr ring quality sample,pouching - 6" - 8 nos.
Factory area Inrack sprinkler system 6" - 1 nos & 4" - 1 Nos. with 2" GV -19 Nos. Ink and Adhesive sprinkler
system 6" - 1no. and inrack sprinkler 6" - 1no. with 2" GV -8 Nos.
6" Fire Hydrant with 6" Nrs Gate Valve - 13 NOs.

C o2 System - 3 Nos. AS ATTAC HED as assumed height as 5 m.


FM200 SYSTEM : Trans former room - 75.3 sq.mm x 4 assumed ht. 120 kg. cylinder - 2 nos.
Electrical room - 42.84 sq.mm x 4 assumed ht. 120 kg. cylinder - 1 nos.

Pump C apacity : 2500 Gpm at 11 bar

---------- Forwarded message ----------


From: AL JASSIM ENGINEERING CONSULTANTS <ajeconsl@ajeconsl.ae>
Date: Wednesday, August 9, 2017
Subject: Huhtamaki -Egypt tendering comment
To: Pushkar Thakkar <pushkar@delmont.ae>

Dear Sir,

With reference to the subject project, please find below the comments and documents required.

1. Missing documents:-
a. Firefighting specifications.

2. Firefighting:-
a. Required capacity for the following items
i. item -1 (foam trolley ) , item -6 (fm200) , item 20 foam tank , item 21 co2 system
b. Required description for the following items
i. All sprinkler required (k- factor , temperature rating , response type )
ii. Foam suppression system (system equipment with required size and capacity
iii. All cabinet
c. Required size for the following items
a. Zone control station item -9 , fire hydrant item -17 , hose reel pipe item 16 fire hydrant pipe item 17
d. Required fire 2000 gpm while the required according to calculation 2500 gpm @ 11.5 bar
--
Thanking you,

For Al Jassim Engineering Consultants


Sunil / NNT
Tel: 04-2834436
Fax: 04-2834437