Вы находитесь на странице: 1из 3

Mini-ComTM Shielded Jack Modules -

TG Style Termination
Part Numbers: CJS6X88TG**Y, CJSK6X88TG**, CJSQ6X88TGBL, CJSH6X88TG**Y, CJS688TG**Y, CJSK688TG**,
CJSQ688TGBL, CJSH688TG**Y, CJS5E88TG**Y, CJSK5E88TG**, CJSH5E88TG**Y

© Panduit Corp. 2017 INSTALLATION INSTRUCTIONS PN366P

Strain relief clip

Jack

Wire cap
Blue - Cat. 6A
White - Cat. 6
Red - Cat. 5e

CABLE PREPARATION STEPS

S/FTP
Individual foil 2.00"
pair screen CWST
(50.8mm)
Conductors

Braid 0.50"
(12.7mm)

SF/UTP

Overall foil 2.00"


screen (50.8mm) CWST
Conductors

Braid 0.50"
(12.7mm)

U/FTP
Individual foil 2.00" Drain
pair screen (50.8mm) Wire
Conductors

Drain wire CWST

F/UTP Drain Wire

Overall foil 2.00"


screen (50.8mm)

Conductors CWST

0.50"
(12.7mm)
Drain wire

For Technical Support: www.panduit.com/resources/install_maintain.asp


** = color. Page 1 of 3
© Panduit Corp. 2017 INSTALLATION INSTRUCTIONS PN366P

TERMINATION STEPS

1 2 3 4
R

0.5" F
(12.7mm)

Trim pair separator and/or ripcord, if present.

5 6
EGJT

Do not pre-arrange
conductors.

(OR)

7 T568B Wiring 7 T568A Wiring

1. 1. 2.
R R

F F

(OR) (OR)

1. 2. 1. 2.
R R

F F

For Technical Support: www.panduit.com/resources/install_maintain.asp


Page 2 of 3
© Panduit Corp. 2017 INSTALLATION INSTRUCTIONS PN366P

8 Trim conductors 9 10
flush

Trim drain wire,


if present

11 12 13
EGJT

Grounding Kit,
CJSGK-X
(See note 5)

REMOVAL STEPS

1 2 3

Notes:
1. For specified performance, follow TIA/EIA 568-C installation guidelines.
2. Shielded jack modules can terminate 22-26 AWG solid or stranded IWC data cable with 0.062" (1.57mm) maximum insulated conductor outside diameter.
3. Shielded jack modules may be re-terminated a minimum of 20 times.
4. For technical and performance information, contact Panduit Technical Support.
5. CJSGK-X Grounding Kit is REQUIRED for all Mini-Com Modular Patch Panels, but is optional for Mini-Com All Metal Shielded Modular Patch Panels.
As with all Communication Components, the following statements apply:
1. Never install communications wiring during a lightning storm.
2. Never install communications wiring in wet locations unless the jack is specifically designed for use in wet locations.
3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4. Use caution when installing or modifying communication wiring.

For Instructions in Local Languages E-mail:


and Technical Support: techsupport@panduit.com

www.panduit.com/resources/install_maintain.asp Phone:
www.panduit.com 866-405-6654

Page 3 of 3

Вам также может понравиться