Microwave Hood Combination

PRODUCT MODEL NUMBERS CABINET OPENING DIMENSIONS

GH6208XR A B
GH7208XR
NOTE: The grounded 3 prong outlet
must be inside the upper cabinet.
Electrical: A 120-volt, 60-Hz, AC-only, 15- or
20-amp electrical supply located in the upper *30" (76.2 cm) is typical for 66"
(167.6 cm) installation height. Exact
cabinet as close as possible to the microwave dimension may vary depending on
oven hood. A time-delay fuse or circuit breaker 30" type of range/cooktop below.
and separate circuit is recommended. (76.2 cm)
30" min.
(76.2 cm)
typical*
12" (30.5 cm) min.
13" (33.0 cm) max.

OVERALL DIMENSIONS
66" (167.6 cm) min.

18¹⁄₄" 29⁷⁄₈" (76.0 cm)


m)
(46.4 c

18¹⁄₄" 15¹⁄₂"
(46.4 cm) (39.4 cm)

A. 2" x 4" wall stud


B. Grounded 3 prong outlet

VENTING REQUIREMENTS
Roof venting roof cap Wall venting Recommended vent length
wall cap
Use 3-1/4" x 10" or 6" vent. The total length of the vent system
including straight vent, elbow, transitions, wall or roof caps
must not exceed the equivalent of 140 feet of
3-1/4" x 10" rectangular or 6" diameter round vent. For best
performance, use no more than three 90° elbows. To calculate
3-1/4" x 10" the length of system you need, add the equivalent feet for
through-the-wall
each vent piece used in the system. See examples below.
3-1/4" x 10"
through-the-roof
3-1/4" x 10" vent system
Recommended standard fittings For wall or roof venting methods:
3-1/4" x 10"
If the wall exhaust method is chosen, be sure that 90° elbow wall cap
6 ft.
there is proper clearance within the wall so the vent
fits properly and the damper blade opens fully.
Wall and roof caps must have back-draft damper.
We recommend: 2 ft. 1 - 3-1/4" x 10"
3-1/4" x 10" 3-1/4" x 10" 3-1/4" x 10"
✔ using rigid metal vent. 90° elbow = 25 ft.
to 6" = 5 ft. roof cap = 24 ft. 90° elbow = 25 ft. ✔ that length of vent and number of elbows should 1 - wall cap = 40 ft.
be kept to a minimum to provide efficient 8 feet straight = 8 ft.
performance. Length of
✔ that size of vent should be uniform. 3-1/4" x 10" system = 73 ft.
✔ using duct tape to seal all joints in the vent
system. 6" vent system
90° elbow 3-1/4" x 10" 45° elbow 3-1/4" x 10" ✔ using caulking compound to seal exterior wall or 90° elbows 6 ft.
6" = 10 ft. wall cap = 6" = 5 ft. 90° flat
roof opening around cap. wall cap
40 ft. elbow= 10 ft.
✔ two elbows should not be installed together.
If the existing vent is round, a rectangular-
to-round adapter must be used and a We do NOT recommend: 1 - transition = 5 ft.
rectangular 3" extension vent between the 2 ft.
damper assembly and the adapter must be
✔ flexible metal vent. 2 - 90° elbows = 20 ft.
installed to prevent sticking of the exhaust 1 - wall cap = 40 ft.
damper. NOTE: If flexible metal vent must be used, calculate 8 feet straight = 8 ft.
each foot of flexible metal vent as two feet of rigid
Length of 6" system = 73 ft.
metal vent. Flexible metal elbows count twice as
much as standard elbows. transition

Because Whirlpool Corporation policy includes a continuous commitment to improve Dimensions are for planning purposes only. For complete details, see Installation Ref. 8206589
our products, we reserve the right to change materials and specifications without notice. Instructions packed with product. Specifications subject to change without notice. 01-03-07