Вы находитесь на странице: 1из 4

PROJECT: SUPPLY, TESTING AND COMMISSIONING OF STP EFLOCT 710m3/day Revision No.

: 01
Dated : 10-04-2016
CLIENT : ABUDHABI COMPANY FOR ONSHORE OIL OPERATION (ADCO) Prepared By : MF
Checked By : SH
MAIN CONTRACTOR: PIVOT ENGINEERING & GENERAL CONTRACTING

SUPPLIER: CORODEX INDUSTRIES LLC

INSTRUMENT SCHEDULE
INSTRUMENT
Sr.
TAG NUMBER SERVICE LINE / EQUIPMENT TAG LOCATION CALIBRATION OPERATING REV
No. INSTRUMENT TYPE MAKE MODEL RANGE Eng. Units
RANGE / SET PT VOLTAGE
Endress & PROMAG 10L
1 02-90-FT-25-01-01 Sewage Lifting's Pumps Discharge EM Flow DN150 / PVC Field Electromagnetic 0-120 20 to 600 m3/hr 24 VDC 0
Hauser 10L1F-QL1A1AG4A5AA

Aeration Tank-1 (Settling Tank-1) inlet EM Endress & PROMAG 10L


2 02-90-FT-25-02-01 DN80 / PVC Field Electromagnetic 0-40 5.4 to 180 m3/hr 24 VDC 0
Flow Hauser 10L80-QL1A1AG4A5AA

Aeration Tank-1 (Settling Tank-1) Outlet EM Endress & PROMAG 10L


3 02-90-FT-25-03-01 DN50 / PVC Field Electromagnetic 0-15 2.1 to 66 m3/hr 24 VDC 0
Flow Hauser 10L50-QL1A1AG4A5AA

Aeration Tank-2 (Settling Tank-2) inlet EM Endress & PROMAG 10L


4 02-90-FT-25-04-01 DN80 / PVC Field Electromagnetic 0-40 5.4 to 180 m3/hr 24 VDC 0
Flow Hauser 10L80-QL1A1AG4A5AA

Aeration Tank-2 (Settling Tank-2) Outlet EM Endress & PROMAG 10L


5 02-90-FT-25-05-01 DN50 / PVC Field Electromagnetic 0-15 2.1 to 66 m3/hr 24 VDC 0
Flow Hauser 10L50-QL1A1AG4A5AA

Endress & PROMAG 10L


6 02-90-FT-25-06-01 Media Filter Outlet Flow DN100 / PVC Field Electromagnetic 0-45 8.7 to 282 m3/hr 24 VDC 0
Hauser 10L1H-QL1A1AG4A5AA

Endress & FMU41 24 VDC LOOP


7 02-90-LT-25-01-01 FOG & Grit Removal Tank Level Open Tank Field Ultrasonic 0-5 0-8 m 0
Hauser FMU41-ANB2A21 POWERED

Endress & FMU41 24 VDC LOOP


8 02-90-LT-25-02-01 Sewage Lifting's Tank Level Closed Tank Field Ultrasonic 0-5 0-8 m 0
Hauser FMU41-ANB2A21 POWERED

Endress & FMB50 0-0.5/ 24 VDC LOOP


9 02-90-LT-25-03-01 Sewage Balancing Tank Level Open Tank Field Hydrostatic 1.2 / 0-12 Bar / m 0
Hauser FMB50-AA21JA1HGKAFJB3U+AA 0-5 POWERED

Endress & FMU41 24 VDC LOOP


10 02-90-LT-25-04-01 Sludge Holding Tank Level Open Tank Field Ultrasonic 0-5 0-8 m 0
Hauser FMU41-ANB2A21 POWERED

Endress & FMB50 0-0.5/ 24 VDC LOOP


11 02-90-LT-25-05-01 Chlorine Contact Tank Level Open Tank Field Hydrostatic 1.2 / 0-12 Bar / m 0
Hauser FMB50-AA21JA1HGKAFJB3U+AA 0-5 POWERED

Endress & FMB50 0-0.5/ 24 VDC LOOP


12 02-90-LT-25-06-01 TSE Tank Level Open Tank Field Hydrostatic 1.2 / 0-12 Bar / m 0
Hauser FMB50-AA21JA1HGKAFJB3U+AA 0-5 POWERED

Differential Endress & Transmitter - FMX167-A2BBB1B71


13 02-90-LT-25-07-01 Manual Screen-1 Differential level Open Tank Field 0-0.1 / 0-1 0 to 0.2 Bar ;/ m 24 VDC 0
Level Hauser Panel meter - RIA46-A1B1AA1B1

Differential Endress & Transmitter - FMX167-A2BBB1B71


14 02-90-LT-25-08-01 Manual Screen-2 Differential level Open Tank Field 0-0.1 / 0-1 0 to 0.2 Bar ;/ m 24 VDC 0
Level Hauser Panel meter - RIA46-A1B1AA1B1

Sensor - CPF81D-7LH11
PH Sensor & Endress &
15 02-90-AIT-25-01-01 Aeration Tank-1 (Settling Tank-1) Outlet PH Open Tank Field Transmitter -CM442-AAM1A2F060A+AA 0-10 0 to 14 PH 24 VDC 0
Transmitter Hauser
Cable - CYK10-A151

Sensor - CPF81D-7LH11
PH Sensor & Endress &
16 02-90-AIT-25-02-01 Aeration Tank-2 (Settling Tank-2) Outlet PH Open Tank Field Transmitter -CM442-AAM1A2F060A+AA 0-10 0 to 14 PH 24 VDC 0
Transmitter Hauser
Cable - CYK10-A151

Chlorine Sensor - CCS142D-GAS80,


pH Sensor -CPS11D-7BA21
Endress &
17 02-90-AIT-25-03-01 Media Filter Outlet Chlorine DN50 / PVC Field Chlorine Analyzer Transmitter -CM442-AAM2A1F060A+AA 0-1 0.01 to 5 PPM 24 VDC 0
Hauser
Flow assembly - CCA250-M1,
Measuring cable - CYK10-A101

DO Sensor & Endress & Sensor - COS61D-AAA1A4


18 02-90-AIT-25-04-01 Aeration Tank-1 (Settling Tank-1) Inlet DO Open Tank Field 0-6 0 to 20 PPM 24 VDC 0
Transmitter Hauser Transmitter -CM442-AAM1A2F060A+AA

DO Sensor & Endress & Sensor - COS61D-AAA1A4


19 02-90-AIT-25-05-01 Aeration Tank-2 (Settling Tank-2) Inlet DO Open Tank Field 0-6 0 to 20 PPM 24 VDC 0
Transmitter Hauser Transmitter -CM442-AAM1A2F060A+AA

DO Sensor & Endress & Sensor - COS61D-AAA1A4


20 02-90-AIT-25-06-01 Sludge Holding Tank DO Open Tank Field 0-6 0 to 20 PPM 24 VDC 0
Transmitter Hauser Transmitter -CM442-AAM1A2F060A+AA

Page 1
PROJECT: SUPPLY, TESTING AND COMMISSIONING OF STP EFLOCT 710m3/day Revision No. : 01
Dated : 10-04-2016
CLIENT : ABUDHABI COMPANY FOR ONSHORE OIL OPERATION (ADCO) Prepared By : MF
Checked By : SH
MAIN CONTRACTOR: PIVOT ENGINEERING & GENERAL CONTRACTING

SUPPLIER: CORODEX INDUSTRIES LLC

INSTRUMENT SCHEDULE
Aeration Tank-1 (Settling Tank-1) Outlet MLSS Sensor & Endress & Sensor - CUS51D-AAD1A4
21 02-90-AIT-25-07-01 Open Tank Field 0-6 0 to 300 g/l 24 VDC 0
MLSS Transmitter Hauser Transmitter -CM442-AAM1A2F060A+AA

Aeration Tank-2 (Settling Tank-2) Outlet MLSS Sensor & Endress & Sensor - CUS51D-AAD1A4
22 02-90-AIT-25-08-01 Open Tank Field 0-6 0 to 300 g/l 24 VDC 0
MLSS Transmitter Hauser Transmitter -CM442-AAM1A2F060A+AA

Sensor - CUS52D-AA1BA4
Turbidity Sensor & Endress &
23 02-90-AIT-25-XX-XX Multi Media Filters Outlet Turbidity DN100 / PVC Field Transmitter -CM442-AAM1A2F060A+AA 0-2 0.000 to 4000 FNU 24 VDC 0
Transmitter Hauser
Flowfit - CUA252-AAB311

Endress &
24 02-90-LSLL-25-02-01 Sewage Lifting Tank Level LO LO Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
25 02-90-LSL-25-08-01 Sewage Lifting Tank Level LO Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
26 02-90-LSH-25-04-01 Sewage Lifting Tank Level HI Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
27 02-90-LSHH-25-02-01 Sewage Lifting Tank Level HI HI Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
28 02-90-LSLL-25-03-01 Sewage Balancing Tank Level LO LO I Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
29 02-90-LSL-25-08-02 Sewage Balancing Tank Level LO Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
30 02-90-LSH-25-04-02 Sewage Balancing Tank Level HI Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
31 02-90-LSHH-25-02-02 Sewage Balancing Tank Level HI HI Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
32 02-90-LSL-25-08-03 Chlorine Contact Tank Level LO Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
33 02-90-LSH-25-04-03 Chlorine Contact Tank Level HI Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
34 02-90-LSL-25-08-04 Sludge Holding Tank Level LO Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
35 02-90-LSH-25-04-04 Sludge Holding Tank Level Hi Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
36 02-90-LSL-25-08-05 TSE Tank Level LO Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
37 02-90-LSH-25-04-05 TSE Tank Level HI Open Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
38 02-90-LSL-25-08-06 Odour Dosing Tank Level LO Closed Tank Field Dosing Switch 52010124 + 52010125 + 52010126 + 52010127 - 0-5 m 24 VDC 0
Hauser

Endress &
39 02-90-LSL-25-08-07 Pre Chlorination Dosing Tank Level LO Closed Tank Field Dosing Switch 52010124 + 52010125 + 52010126 + 52010127 - 0-5 m 24 VDC 0
Hauser

Endress &
40 02-90-LSL-25-08-08 Post Chlorination Dosing Tank Level LO Closed Tank Field Dosing Switch 52010124 + 52010125 + 52010126 + 52010127 - 0-5 m 24 VDC 0
Hauser

Endress &
41 02-90-LSL-25-08-09 Drain Sump Tank Level LO Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
42 02-90-LSH-25-04-06 Drain Sump Tank Level HI Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser

Endress &
43 02-90-LSHH-25-02-03 Drain Sump Tank Level HI HI Closed Tank Field Float Switch 71035520 + 52010125 + 52010126 + 52010127 - 0-20 m 24 VDC 0
Hauser
Page 2
PROJECT: SUPPLY, TESTING AND COMMISSIONING OF STP EFLOCT 710m3/day Revision No. : 01
Dated : 10-04-2016
CLIENT : ABUDHABI COMPANY FOR ONSHORE OIL OPERATION (ADCO) Prepared By : MF
Checked By : SH
MAIN CONTRACTOR: PIVOT ENGINEERING & GENERAL CONTRACTING

SUPPLIER: CORODEX INDUSTRIES LLC

INSTRUMENT SCHEDULE
Indicator - 233.30
44 02-90-PI-25-07-01 Sewage Lifting Pump-1 Discharge Pressure ∅4" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Snubber - 910.12

Indicator - 233.30
45 02-90-PI-25-07-02 Sewage Lifting Pump-2 Discharge Pressure ∅4" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Snubber - 910.12

Indicator - 233.30
46 02-90-PI-25-07-03 Sewage Lifting Pump-3 Discharge Pressure ∅4" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Snubber - 910.12

47 02-90-PI-25-07-04 Air Blower-1 Discharge Pressure ∅4" / GI Field Indicator Wika Indicator - 232.30 0-1 0-1 Bar - 0

48 02-90-PI-25-07-05 Air Blower-2 Discharge Pressure ∅4" / GI Field Indicator Wika Indicator - 232.30 0-1 0-1 Bar - 0

49 02-90-PI-25-07-06 Air Blower-3 Discharge Pressure ∅4" / GI Field Indicator Wika Indicator - 232.30 0-1 0-1 Bar - 0

Sewage Balancing Pump-1 Discharge Indicator - 233.30


50 02-90-PI-25-07-07 ∅3" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Pressure Snubber - 910.12

Sewage Balancing Pump-2 Discharge Indicator - 233.30


51 02-90-PI-25-07-08 ∅3" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Pressure Snubber - 910.12

Sewage Balancing Pump-3 Discharge Indicator - 233.30


52 02-90-PI-25-07-09 ∅3" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Pressure Snubber - 910.12

Indicator - 233.30
53 02-90-PI-25-07-10 Sludge Transfer Pump-1 Discharge Pressure ∅2" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Diaphragm Seal -L990.TB.N4F.N4F.SS.SS.0.SS.2500.

Indicator - 233.30
54 02-90-PI-25-07-11 Sludge Transfer Pump-2 Discharge Pressure ∅2" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Diaphragm Seal -L990.TB.N4F.N4F.SS.SS.0.SS.2500.

Indicator - 233.30
55 02-90-PI-25-07-12 Filter Feed Pump-1 Suction Pressure ∅2" / uPVC Field Indicator Wika -1 to +1 -1 to +1 Bar - 0
Snubber - 910.12

Indicator - 233.30
56 02-90-PI-25-07-13 Filter Feed Pump-2 Suction Pressure ∅2" / uPVC Field Indicator Wika -1 to +1 -1 to +1 Bar - 0
Snubber - 910.12

Indicator - 233.30
57 02-90-PI-25-07-14 Filter Feed Pump-3 Suction Pressure ∅2" / uPVC Field Indicator Wika -1 to +1 -1 to +1 Bar - 0
Snubber - 910.12

Indicator - 233.30
58 02-90-PI-25-07-15 Filter Feed Pump-1 Discharge Pressure ∅2" / uPVC Field Indicator Wika 0-6 0-6 Bar - 0
Snubber - 910.12

Indicator - 233.30
59 02-90-PI-25-07-16 Filter Feed Pump-2 Discharge Pressure ∅2" / uPVC Field Indicator Wika 0-6 0-6 Bar - 0
Snubber - 910.12

Indicator - 233.30
60 02-90-PI-25-07-17 Filter Feed Pump-3 Discharge Pressure ∅2" / uPVC Field Indicator Wika 0-6 0-6 Bar - 0
Snubber - 910.12

61 02-90-PI-25-07-18 Media Filter-1 Outlet Pressure ∅3" / uPVC Field Indicator Wika Indicator - 233.30 0-6 0-6 Bar - 0

62 02-90-PI-25-07-19 Media Filter-2 Outlet Pressure ∅3" / uPVC Field Indicator Wika Indicator - 233.30 0-6 0-6 Bar - 0

63 02-90-PI-25-07-20 Media Filter-3 Outlet Pressure ∅3" / uPVC Field Indicator Wika Indicator - 233.30 0-6 0-6 Bar - 0

Indicator - 233.30
64 02-90-PI-25-07-21 Drain Sump Pump-1 Discharge Pressure ∅3" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Snubber - 910.12

Indicator - 233.30
65 02-90-PI-25-07-22 Drain Sump Pump-2 Discharge Pressure ∅3" / uPVC Field Indicator Wika 0-2.5 0-2.5 Bar - 0
Snubber - 910.12

Temperature Indicator -S5550 / 4


66 02-90-TI-25-01-01 Air Blower-1 Discharge Temperature ∅4" / GI Field Indicator Wika 0 -160 0 -160 Deg C - 0
Thermowell-TW15

Page 3
PROJECT: SUPPLY, TESTING AND COMMISSIONING OF STP EFLOCT 710m3/day Revision No. : 01
Dated : 10-04-2016
CLIENT : ABUDHABI COMPANY FOR ONSHORE OIL OPERATION (ADCO) Prepared By : MF
Checked By : SH
MAIN CONTRACTOR: PIVOT ENGINEERING & GENERAL CONTRACTING

SUPPLIER: CORODEX INDUSTRIES LLC

INSTRUMENT SCHEDULE
Temperature Indicator -S5550 / 4
67 02-90-TI-25-01-02 Air Blower-2 Discharge Temperature ∅4" / GI Field Indicator Wika 0 -160 0 -160 Deg C - 0
Thermowell-TW15

Temperature Indicator -S5550 / 4


68 02-90-TI-25-01-03 Air Blower-3 Discharge Temperature ∅4" / GI Field Indicator Wika 0 -160 0 -160 Deg C - 0
Thermowell-TW15