Вы находитесь на странице: 1из 1

78

ASPE Plumbing Engineering Design Handbook — Volume 2

adequate flow pressures when water is required at the use of two PRVs to reduce high service pressure
fixtures, appliances, or equipment. proportionately and to eliminate an extremely wide
Pressure-Regulating Valves (PRV) variance between the initial and reduced pressure. It
is recommended where the initial pressure is 200 psi
Types of PRV All PRVs fall into the following gen-
(1,379.0 kPa) or more and where the ratio of initial
eral categories:
to reduced pressure is more than 4 to 1 (e.g., 200 to
• Single-seated—direct-operated or pilot-oper- 50 psi [1,379.0 to 344.7 kPa]), or where the initial
ated. pressure fluctuates greatly. The advantage of this
• Double-seated—direct-operated or pilot-oper- installation is that neither valve is subjected to an
ated. excessive range of pressure reductions. This seems
Single-seated PRVs are used for dead-end service to stabilize the final reduced pressure, ensuring close
and when the flow to be regulated is intermittent. and accurate performance. Also, this type of installa-
For dead-end service, the valve must be able to shut tion reduces the velocity of flow (there’s less pressure
tight and not permit the passage of any water when drop across two regulators than across one), providing
there is no demand. Double-seated PRVs are used for longer valve life.
continuous-flow conditions. They are not suited for Selection of PRVs and pressure settings is fairly
dead-end service and should never be used for this simple. The first PRV could reduce from 250 to 150
purpose. psi (1,723.7 to 1,034.2 kPa) and the second from 150
Direct-operated PRVs tend to have a reduction to approximately 50 psi (1,034.2 to 344.7 kPa), or
of the outlet pressure in direct proportion with the there could be some similar division. PRV size can
increase of the flow rate (fall-off pressure). Pilot-op- be selected according to the manufacturer’s capac-
erated PRVs will maintain a close fluctuation of the ity tables if it is remembered that each PRV should
outlet pressure independent of the flow rate assuming exceed the total capacity of the system.
that the valve was sized properly. Where there is a wide variation of demand require-
Sizing, selection, and installation  Initial cost, ments and where it is vital to maintain a continuous
maintenance cost, and specific project requirements water supply as well as provide greater capacity,
regarding flow rates and pressure should determine parallel installation is recommended. Parallel instal-
which PRV is recommended for a particular applica- lation is the use of two or more smaller PRVs serving
tion. a larger supply pipe main. This type of installation
Sizing and selection of a PRV can be performed should be employed wherever there is a wide varia-
after the following criteria are estimated: inlet pres- tion of reduced-pressure requirements and where it
sure, outlet pressure, and capacity (flow rate). Inlet is vital to maintain a continuous water supply. It also
pressure is the maximum pressure expected upstream has the advantage of providing increased capacity
of the regulating valve. Outlet pressure is the pres- beyond that provided by a single valve where needed.
sure required downstream of the regulating valve. Multiple installation improves valve performance for
Fall-off pressure is the pressure drop through the widely variable demands and permits the servicing of
PRV at full flow (subtract from set pressure). For an individual valve without the complete shutdown of
large-capacity systems, which may also experience the line, thus preventing costly shutdowns.
periods of low flow, or when extreme pressure reduc- For a two-valve parallel installation, the total
tions are expected, it is not advisable to have only one capacity of the valves should equal or exceed the
regulating valve. capacity required by the system. One valve should
A PRV sized to accommodate both small and be set at 10 psi (69.0 kPa) higher delivery pressure
large flows has, in general, a high noise level during than the other. For example, assume that the system
operation. In addition, small flows will produce wire- requires 400 gpm (25.2 L/s) and the reduced-flow pres-
drawing of the seat and possible chatter. sure required is 50 psi (344.7 kPa). Select two valves,
In addition to having economic advantages, the each rated at 200 gpm (12.6 L/s), with one valve set
proper application of PRVs can greatly influence the at 50 psi (344.7 kPa) and the other valve set 10 psi
overall performance of the system. Under most cir- (69.0 kPa) higher at 60 psi (413.7 kPa). Thus, when
cumstances, a good application can increase system low volume is required, the higher-set valve operates
performance, reduce operating costs, and ensure a alone. When a larger volume is demanded, both valves
longer life expectancy for regulators. open, delivering full-line capacity.
For example, where initial pressures exceed 200 Another possible choice is to install two PRV com-
psi (1,379.0 kPa) or where there is a wide variation binations of different sizes. This is practical on larger
between the initial pressure and the reduced pressure, installations where supply lines are 2 in. (50 mm) and
or where the initial pressure varies considerably, two- larger and where there are frequent periods of small
stage reduction is beneficial. Two-stage reduction is demand. The smaller PRV would have the 10-psi

Вам также может понравиться