MED.EL. Srl Technical Manual
CONTENT
1. SAFETY WARNINGS ........................................................................ 1
1.1 INSTALLATION ................................................................................................ 1
1.2 OPERATION ..................................................................................................... 2
1.3 MAINTENANCE ............................................................................................... 3
2. PRODUCT INTRODUCTION ............................................................. 5
2.1 FUNCTIONS DESCRIPTION ............................................................................... 5
2.2 MODE DESCRIPTION ........................................................................................ 6
2.3. DESCRIPTION OF COMMONLY USED SYMBOLS .............................................. 11
2.4 FRONT PANEL ................................................................................................ 11
2.5 TERMINAL .................................................................................................... 14
2.6 PRODUCT SPECIFICATION .............................................................................. 15
3. INSTALLATION ............................................................................... 18
3.1 UNPACKING AND INSPECTION ....................................................................... 18
3.2 INSTALLATION STEPS .................................................................................... 18
4. OPERATION .................................................................................... 19
4.1 START THE UPS WITH MAINS (AC SOURCE) .................................................. 19
4.2 START THE UPS WITH BATTERY (DC SOURCE) ONLY ..................................... 19
4.3 CONNECT LOADS TO UPS ............................................................................. 20
4.4 CHARGE THE BATTERIES ............................................................................... 20
4.5 DISCHARGE THE BATTERIES .......................................................................... 21
4.6 TEST THE BATTERIES ..................................................................................... 21
4.7 TURN OFF THE UPS WITH MAINS (AC SOURCE) ............................................ 21
4.8 TURN OFF THE UPS WITH BATTERY (DC SOURCE) ONLY ............................... 22
4.9 MUTE THE BUZZER ....................................................................................... 22
4.10 OPERATION IN WARNING STATUS ................................................................. 22
4.11 OPERATION IN FAULT MODE ........................................................................ 23
4.12 SETTING BY LCD MODULE ......................................................................... 23
5. MAINTENANCE ............................................................................... 26
5.1 TYPICAL TROUBLE SHOOTING ...................................................................... 26
5.2 BATTERY MAINTENANCE .............................................................................. 28
5.3 CONTACT THE SERVICE CENTER .................................................................... 29
6. TRANSPORT AND STORAGE ........................................................ 29
MED.EL. Srl Technical Manual
1. Safety Warnings
CAUTION:
SEE INSTALLATION INSTRUCTIONS BEFORE CONNECTING TO
THE SUPPLY.
1.1 Installation
Condensation may occur if the UPS is moved directly from a cold to
a warm environment. The UPS must be absolutely dry before being
installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment.
Do not install the UPS where it would be exposed to direct sunlight
or near heat.
Do not block ventilation openings in the UPS’s housing.
Place cables in such a way that no one can step on or trip over
them.
UPS has provided earthed terminal, in the final installed system
configuration, equipotent earth bonding to the external UPS battery
cabinets.
To reduce the risk of fire or electric shock, install this UPS in a
temperature and humidity controlled, indoor environment, free of
conductive contaminants. Ambient temperature must not exceed
40°C (104F). Do not operate near water or excessive humidity
(95% maximum).
Unpacking the cabinet in a low-temperature environment may cause
condensation to occur in and on the cabinet. Do not install the
cabinet until the inside and outside of the cabinet are absolutely dry
(hazard of electric shock).
An appropriate disconnect device as short-circuit backup protection
should be provided in the building wiring installation.
1
MED.EL. Srl Technical Manual
1K 240V, 20 A, 2-pole
2K 240V, 30 A, 2-pole
3K 240V, 40 A, 2-pole
1.2 Operation
Do not disconnect the earth conductor cable from the UPS or the
main wiring terminals in any time since this would cancel the
protective earthing of the UPS system and all connected loads.
This UPS contains its own energy source (batteries). The output
receptacles may carry live voltage even when the UPS is not
connected to an AC supply.
Do not remove or unplug the input cord when the UPS is turned on.
This removes the safety ground from the UPS and the equipment
connected to the UPS.
Ensure that no liquid or other foreign objects can enter the UPS.
2
MED.EL. Srl Technical Manual
1.3 Maintenance
The UPS operates with hazardous voltages. Maintenance should be
carried out only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected
from the mains power supply (building wiring terminal), components
inside the UPS are still connected to the battery which have
potentially dangerous.
Before carrying out any kind of service and/or maintenance, please
disconnect the batteries. Verify that no current is present and no
hazardous voltage exists in the capacitor or BUS capacitor
terminals.
Caution – the risk of electric shock. The battery circuit is not isolated
from the input voltage. Hazardous voltage may occur between the
battery terminals and the ground. Verify that no voltage is present
before servicing.
Batteries must be replaced only by qualified personnel.
When replacing batteries, replace with the same type and number of
batteries or battery packs.
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
A battery can present a risk of electrical shock and high short circuit
current. The following precautions should be observed when
working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
3
MED.EL. Srl Technical Manual
4
MED.EL. Srl Technical Manual
2. Product introduction
5
MED.EL. Srl Technical Manual
No output mode
The LCD display in No output mode is shown in the following
diagram. The information about the utility power, the battery level,
the UPS output and the load level could be displayed. The “STbY”
string indicates the UPS is working in the No output mode.
6
MED.EL. Srl Technical Manual
Bypass mode
Bypass mode means that the UPS provides the power through the
internal bypass way to load directly without any regulation. If the
controller detects the mains is abnormal, it will shut off the output to
protect the load. The bypass voltage/frequency range and default
output status (on/off) could be set by communication software.
The LCD display in bypass mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and
the load level could be displayed. The UPS will beep once every 2
minutes in bypass mode. The “bYPA” string indicates the UPS is
working in the bypass mode.
7
MED.EL. Srl Technical Manual
Line mode
Line mode means that the mains input is rectified/converted by the
AC/DC section and then inverted to stable output by DC/AC section.
In line mode, the output is clean and good to the loads. If the mains
get abnormal, the UPS will transfer to battery mode without interrupt.
The LCD display in Line mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and
the load level could be displayed. The “LINE” string indicates the UPS is
working in Line mode.
Battery mode
Battery mode means that the battery power goes through the DC/DC
section to the inverter (DC/AC) and get a stable backup output when
the mains input is not usable. If the mains input recovered, the UPS
will transfer to line mode without interrupt.
The LCD display in battery mode is shown in the following diagram. The
information about the utility power, the battery level, the UPS output and
the load level could be displayed. The “bATT” string indicates the UPS
is working in the battery mode.
When the UPS is running in battery mode, the buzzer beeps once every
4 seconds. If the “ON” button on the front panel is pressed for more than
1 second again, the buzzer will stop beeping (in silence mode). Press
the “ON” button once again for more than 1 second to resume the alarm
function.
8
MED.EL. Srl Technical Manual
ECO mode
It is also called high efficiency mode. In ECO mode, on LCD display,
the mode sting is “ECO”.
After the UPS is turned on, the power used by the load is supplied
from the utility power via internal filter while the utility power is in
normal range, so the high efficiency could be gained in the ECO
mode. Once the mains is loss or abnormal, the UPS would transfer
to battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software
2) It is attention that the transfer time of UPS output from ECO
mode to battery mode is less than 10ms.
The LCD display in ECO mode is same as the Bypass mode, The
“ECO” string indicates the UPS is working in the ECO mode.
9
MED.EL. Srl Technical Manual
Fault mode
If the UPS generates some internal failure and have to stop its
inverter, it will go into fault mode and alarm by display and buzzer.
In fault mode, the loads have the risk of power loss because the
output will come from the bypass after UPS fault.
In fault mode such as Bus fault etc., the corresponding fault string
would be shown to indicate the operating mode of the UPS, and the
background light become red. For example “SHOR” would be shown
when the load or the UPS output is short. The LCD display is shown
in the following diagram.
10
MED.EL. Srl Technical Manual
11
MED.EL. Srl Technical Manual
LCD display
12
MED.EL. Srl Technical Manual
2.4.2 BUTTON
Switch Function
Turn on UPS system: By pressing the ON-Button “I” the UPS
ON-Button
system is turned on.
Deactivate acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in the battery mode.
Do the battery test: By pressing this Button the UPS can do the
battery test in the Line mode or ECO mode.
When mains power is normal, the UPS system switches to No
OFF-Button
output or Bypass mode by pressing OFF-Button “ “, and the
inverter is off. At this moment, if Bypass is enabled, then the
output sockets are supplied with voltage via the bypass if the
mains power is available.
Deactivate acoustic alarm: By pressing this Button an acoustic
alarm can be deactivated in the bypass mode.
Release the UPS from fault mode and EPO status.
13
MED.EL. Srl Technical Manual
2.5 Terminal
14
MED.EL. Srl Technical Manual
Model name 1K 2K 3K
Model 1K 2K 3K
Model 1K 2K 3K
Dimension (W×H×D)
440×800×700 440×800×700 440×800×700
(mm)
Weight
125 200 200
(Kg)
15
MED.EL. Srl Technical Manual
Model 1K 2K 3K
Power 1000VA/900W 2000VA/1800W 3000VA/2700W
Input
Current (Max.) 10A 20A 30A
Voltage Range 85~150VAC @ full load (55~150VAC @ half load)
Frequency Range 46 ~ 54Hz @ 50Hz system / 56 ~ 64Hz @ 60Hz system
Input Power Factor ≧0.97 @ full load
Output
115/120VAC (sine-wave)
100V Need derating to 90% for 1k/3k
Voltage
100V Need derating to 80% for 2k
110V Need derating to 90% for 2k
Synchronizing mains input @ line mode
Frequency
50/60Hz ± 0.5 Hz @ battery mode
THD ≦5% ( Linear load )
Voltage Regulation ≦2%
Line mode: 60s @ 102%~130%; 1s @ > 130%
Overload Capacity
Battery mode: 10s @ 102%~130%; 1s @ >130%
Efficiency
Line Mode 88%
Battery Mode 83% 83% 83%
Battery & Charger @ 25℃
Total battery rating voltage 36VDC 72VDC 72VDC
Backup Time (Full Load) 60min 60min 60min
Recharge Time (to 90%) 5Hours 5Hours 5Hours
Charging Current (Max.) 1A 0.7A 0.7A
Discharging Current (Max.) 30A 30A 40A
Rated Charging Voltage 41.0Vdc 81.9Vdc 81.9Vdc
16
MED.EL. Srl Technical Manual
2.6.5 Standards
EN 62040-1
Safety
UL1778
17
MED.EL. Srl Technical Manual
3. Installation
18
MED.EL. Srl Technical Manual
4. Operation
4.1 Start the UPS with mains (AC source)
1) Switch on the battery breaker first;
2) If the wiring is correct, turn on the mains breaker in your building.
Then the power supply inside the UPS will be started
automatically, the fans will run, and the LCD will display with
bypass mode or standby mode.
Note 1: If the UPS have been set to enable the bypass output,
the output socket will have the voltage directly from mains after
you turn on the input breaker, and the LCD display “bYPA”, else
the output socket will not have the voltage and the LCD display
“STbY”.
Note 2: In bypass mode, the load is not protected. You should go
on to the next step to turn on the UPS for protecting your load.
3) Press the on-button of the UPS front panel continuously for more
than 1 second. The buzzer will beep once. After a few seconds,
the UPS will be turned on to the normal mode (line mode) and
output the spec voltage.
4) After the UPS is turned on to line mode normally. There is no
beep of buzzer.
Note: If the UPS is shutdown in battery mode automatically, when
the mains power returned to the input, the UPS will start up and
switch to line mode automatically.
19
MED.EL. Srl Technical Manual
1) After the UPS is connected to normal mains, the charger will work
and charge the batteries automatically in bypass mode or line mode.
2) Suggest charging the batteries for 10 hours before use.
Otherwise the backup time may be less than the standard value.
20
MED.EL. Srl Technical Manual
21
MED.EL. Srl Technical Manual
the output socket will have voltage from mains directly after you
turn off the UPS (inverter) to bypass mode.
Note 2: Because there is risk of power loss for the loads if you
turn off the UPS to bypass mode, please make sure the loads
are prepared for your operation.
3) If you want to turn off the output of UPS and shut down the UPS
completely, you have to cut off the mains input of UPS.
Note: please make sure all the loads are prepared or turned off
for your operation before you shut down the UPS system.
4) After you cut off the mains input of UPS to shut down. After a few
seconds, the UPS will be shut down completely and the LCD
extinguish.
4.8 Turn off the UPS with battery (DC source) only
1) To turn off the UPS in battery mode, please press the off-button
continuously for more than 1 second.
2) After you press the button, the buzzer will beep once. After a few
seconds, the UPS will be shut down completely and the LCD
extinguish.
Note: please make sure all the loads are prepared or turned off
for your operation before you shut down the UPS system.
22
MED.EL. Srl Technical Manual
23
MED.EL. Srl Technical Manual
the “Enter” button for more than one second at this time, the output
voltage or frequency or bypass state or mode state setting would be
modified to the selected value. And if no any pressing on the“Select”
or “Enter” button lasting for more than 30 seconds, the setting mode
exit automatically.
Step 2: The flickering figure would change to “120” after pressing the
“Select” button three times again.
24
MED.EL. Srl Technical Manual
Step 3: Pressing the “Enter” button the new setting output voltage
has been confirmed, turn on the UPS and the output is change to
120V.
25
MED.EL. Srl Technical Manual
5. Maintenance
5.1 Typical Trouble Shooting
LCD WARNING
Possible cause Action
CODE
EPO function is
EPO active.
Connect the EPO switch.
26
MED.EL. Srl Technical Manual
Possible
LCD FAULT CODE Action
cause
Internal fault
Contact the distributor or
INVL (inverter
service center.
Voltage low)
Internal fault
Contact the distributor or
INVH (inverter
service center.
Voltage high)
27
MED.EL. Srl Technical Manual
Note 1: when the UPS failed, the Fault/Warning icon will be lightened constantly,
and the buzzer will beep continuously. The backlight become red
Note 2: When the UPS is fault, it will stop the power conversion of mains or
battery.
Note 3: If the fault can’t be shoot, please contact the distributor or service center.