Академический Документы
Профессиональный Документы
Культура Документы
TECHNICAL SPECIFICATION
FOR
PROPOSAL
Contents
1. SCOPE
4. STANDARDS
5. ELECTRICAL CHARACTERISTICS
6. BASIC CONSTRUCTION
8. CABLE EARTHING
10. FINISH
13. SHIPPING
* ATTACHMENT DATA
1. SCOPE
1.1 This specification describes the assemblies of Medium Voltage Metal enclosed Air
Insulated Switchgear for project: Vung Tau, DMT Factory
1.2 This specification covers only the general requirements of the switchgear. The
specific requirements of each assembly (voltage class, breaker ratings, relaying,
metering, control scheme, etc.) will be shown on the attachment data and drawings.
4. STANDARDS
5. ELECTRICAL CHARACTERISTICS
6. BASIC CONSTRUCTION
6.1 The cubicles shall be fabricated of sheet steel. The thickness of sheet steel shall
not less than 2.0 mm in thickness.
6.2 Each switchgear assembly will consist of metal enclosed, free standing, vermin-
proof, vertical, containing power buses, each bus, circuit breaker, necessary auxiliary
control devices, specified instrument transformers, and other accessories to make a
complete working unit as required by the specification and data sheets.
6.3 Each switchgear cubicle will be divided four (4) compartments as circuit breaker
compartment, busbar compartment, and cable connection compartment including
current transformer and low voltage compartment by metal partition plate. Pressure
relief flaps will be provided to release the abnormal high pressure inside the cubicle
while there is an arc fault. Busbar compartments will be extended through all
switchgear with the partition plate and wall bushing between cubicles.
6.4 Automatic metallic safety shutter shall be provided which cover the busbar and
circuit spouts when the breaker is in the test (isolated position) in the cubicle and
when the breaker is withdrawn. Padlocking facility shall be provided in the closed
6.5 Each cubicle shall be provided with front hinged doors with built in handless and
locks.
6.6 Each switchgear assembly will be suitable for the future addition of units on either
end.
6.8 Each switchgear will be furnished with maintenance power socket outlets for
portable maintenance and test equipment. The outlets will supply 220VAC single
phase, 13A with 3-pin, flat and 2-pin, round socket.
6.9 Grounding
1) Grounding bus
A copper grounding bus of 6x25mm thickness and width shall be provided
for each group of lined switchgears.
2) Grounding of enclosure
Each enclosure will be connected to each earth bus bar. Excepting live parts,
metal parts such as partition plates will be bolted or welded for electrical
connection to the enclosure. Earthing shall be provided between frame and
door by earth cable.
2) Busbars will be rated for the full load current of the switchgear.
3) Horizontal and vertical buses will be isolated such that when the rear cover
of a vertical section is opened. The only exposed bare parts are load terminal of
breaker.
6) The continuous ampere rating of the main power bus will be shown on the
data sheets.
7) Earthing switch will be provided for every bus bar and will be equipped with
with key lock (Not applicable)
2) Neon type voltage indicators shall be provided on each phase of each circuit,
of each circuit, of each breaker show the presence of voltage (Not applicable)
6.12 Suitable LED lamp of single phase 10W , 220VAC 50Hz , controlled by door
switch will be provided inside of the low voltage compartment for the convenience of
access and carrying out maintenance work.
6.13 Space heaters, single - phase 220VAC 50Hz with ON-OFF switch and
humidity controller setting range from 5°C to 35°C will be provided inside of the cable
compartment and C.B compartment.
6.14 Nameplates will be made of Acryl material and fixed with stainless steel
screws or bolts. Wording, in nameplates, instruction signs, instrument scale, etc. will
be in English and metric.
6.15 Internal wiring will be nearly run and adequately supported either saddle or
spiral ties or carried across a hinged portion of a chassis or door will be flexible, and
sufficient slack will be provided to avoid tension. All panel wiring will be copper
conductor, ( KIV ) Vinyl insulation. Minimum size will be 1.5sqmm for control
circuits and 2.5sqmm for PT’s secondary circuit and 4.0sqmm CT’s secondary circuits.
6.16 Terminal blocks will be supplied with clear marking for wiring.
CT Secondary circuit R S T N
Red Yellow Blue Black
2) The enclosure frame will be made of steel plates not less than 2,0mm
thickness and will provide sufficient solidity.
3) Front door will be made of steel plates not less than 3.0mm thickness and
will be provided with a door lock.
4) Rear cover will be made of a steel plate not less than 2.0mm thickness.
5) The cable chamber will have sufficient width for easy cable termination
treatment and for safety maintenance and inspection.
7.1 The power circuit breaker will be electrically operated, vacuum 3 poles,
withdrawable type, provided with self aligning, line side and load side disconnecting
devices.
7.2 The withdrawable mechanism will hold the breakers rigidly in the racked-in and
“test” position / “racked-out” position. When breaker is opened, it is possible to move
the breaker to any of the position.
7.3 Interlock will be provided to prevent the connecting between Circuit breaker and
Bus terminal or disconnecting Circuit breaker and Bus terminal unless Circuit breaker
opened (or trip). In addition, interlock will be also provided between circuit breaker
and door of circuit breaker compartment to prevent dangers due to unlocking the
compartment door while the circuit breaker is located at service position.
7.4 The switchgears shall be provided with a comprehensive system of electrical and
mechanical interlocks to prevent any dangerous or undesirable operations.
7.5 The breaker continuous ampere and nominal short circuit rating will be shown on
the data sheets.
7.6 A metallic shutter which effectively close the bus terminal disconnect openings
when the breakers are test (isolation) and with-drawn position, will be provided.
7.7 Each breaker will be equipped with the motor operation type. Each will be
possible to open and close the breakers manually.
7.8 Circuit breakers of the same ratings and control voltage can be interchangeable.
7.9 Each breaker has in excess of control circuit auxiliary contact requirement a
minimum of 10NO/10NC auxiliary contacts.
7.10 Each breaker have a position indicator with appropriate description colors, such
as “CLOSED” on red background and “OPEN” on a green background.
7.11 The secondary disconnecting device shall be of automatic and manual plug-in
type.
8.1 The earthing switches of three phases, quick acting, fault making, mechanically
operated type will be provided at the cable side of each circuit breaker cubicle.
8.2 The earthing switches shall be hand operated and spring mechanism.
8.3 The earthing switch operations can be performed without opening the front door.
8.4 The earthing switches shall be mechanically interlocked with their respective
circuit breaker. When circuit breaker is service position, earthing switch cannot be
closed. If the earthing switch is closed, circuit breaker cannot be put-into the service
8.5 Each earthing switches shall be provided with the auxiliary contact (6N.O + 6N.C)
8.6 Earthing switches can be operated by operation handle at the front door and be
drawn-out the circuit breaker to the draw-out/test position for the outgoing cable.
The operation of earthing switch for incoming cable shall be interlocked with
upstream Circuit Breaker or Disconnector switches.
8.7 Earthing switches will be equipped with key lock. Mechanical and Electrical
interlock between earthing switches and adjacent circuit breaker is provided. Electrical
interlocking between earthing switches and remote isolators can be provided.
9. INSTRUMENT TRANSFORMER
2) Accuracy will be in accordance with IEC standard for the metering and relay
applications shown on the data sheets.
2) Each transformer will be protected with current limiting primary fuse and will
be designed to withstand the basic impulse level of the switchgear.
3) Each transformer will be N/A secondary and its classifications meet the
the requirements of the applications as shown on the data sheets and drawings.
10. FINISH
The switchboard enclosures will be cleaned, primed and painted in accordance with
the manufacturer’s standard.
10.1 Scope
This painting procedure will be used on electrical panel for project.
1) Circuit breaker
2) Potential transformers
3) Current transformers
4) Protective relays
11.9 Insulation resistance between electric parts and earth will be measured in
accordance with the following table.
12.1 Each “shipping section” of stationary structures will be furnished with removable
eye bolts suitable for fork or hooks or slings.
12.2 Each “shipping section” will be furnished with removable steel channel base
plates which will permit using pipe rollers of dollies without damaging the frame steel
of the equipment.
12.3 The suitable handling equipments will be provided for convenient removal,
insertion and movements at each switchgear location for all circuit breakers and
withdrawal equipment weighing more than 20 kg gross.
13. SHIPPING
If shipped separately, each power circuit breaker will be individually crated and
tagged with its proper unit number and the equipment number of the assembly to
which it belongs.
* ATTACHMENT DATA
A. STANDARDS
1. The equipment will be rated in accordance with:
C. MAIN EQUIPMENT
3. EARTHING SWITCH
1) Type : N/A
2) Rated voltage : N/A
3) Rated frequency : N/A
4) Short time withstand current : N/A
5) Maker : N/A
4. CURRENT TRANSFORMER
1) Type : Epoxy resin
2) Rated voltage : 24kV
3) Rated frequency : 50Hz
4) Secondary current output : 1A
5) Metering core class : 0.5CL
6) Protection class 1 : 5P20
5. VOLTAGE TRANSFORMER
1) Type : N/A
2) Rated voltage : N/A
3) Rated frequency : N/A
4) Secondary output : N/A
5) Metering core class : N/A
6) Protection core class : N/A
7) Burden : N/A
8) Maker : N/A
7. POWER FUSE
1) Type : N/A
2) Rated voltage : N/A
3) Rated frequency : N/A
4) Rated current : N/A
5) Maker : N/A
8. LIGHTNING ARRESTER.
1) Type : N/A
2) Rated voltage : N/A
3) Rated frequency : N/A
4) Nominal Discharge Current : N/A
5) Line discharge class : N/A
6) Maker : N/A
10. INSTRUMENTS
AMPERE METER
1) Type : N/A
2) Accuracy class : N/A
3) Maker : N/A
VOLT METER
1) Type : N/A
2) Accuracy class : N/A
3) Maker : N/A
MULTI-FUNCTION METER
1) Type : N/A
2) Accuracy class : N/A
3) Maker : N/A
WATTHOUR&VARHOUR METER
1) Type : N/A
2) Accuracy class : N/A
3) Maker : N/A
TRANSDUCER: A, V, P, VAR
1) Type : N/A
2) Output : N/A
2) Accuracy class : N/A
3) Maker : N/A
1. SEMAPHORE
1) Type : N/A
2) Position : N/A
3) Maker : N/A
2. CONTROL SWITCH
1) Type : YS
2) Position : Open-Close
3) Pull turn spring return
4) Maker : YongSung/Korea
3. SELECTOR SWITCH
1) Type : YS
2) Position : Local/Remote
3) Maker : YongSung/Korea
7. AUXILIARY RELAY
1) Type : MR
2) Number of contact : 4 or 8
3) Rated voltage : 110VDC
4) Maker : LS Electric/Korea
E. OTHERS
1. SPACE HEATER
- 1 Phase, AC 220VAC , 80W
2. LIGHTING FIXTURE
- LED type
- 1 Phase, AC 220VAC , 80W
3. TEST TERMINAL
- 3P 3W, 3P 4W
- Plug-in type