Академический Документы
Профессиональный Документы
Культура Документы
Abstract—This paper presents a procedure for calculating the may lead to inaccurate results. Ref. [4] presents an improved
maximum lightning overvoltage along a cable which is protected approach where a regular line model is used for obtaining the
by arresters at both ends. It is shown that the most severe cable voltages and currents at the line ends which are next used in the
overvoltages that can occur (close back-flashover) will appear at a
distance from the remote cable end which is in the order of some calculation at internal points using an off-line time step. How-
hundred meters. The maximum voltage is calculated by adding ever, in the case of steep-fronted lightning surges, the maximum
the peak value of the voltage wave in the forward direction and voltage can only be determined with good accuracy if one of
the peak value of the voltage wave in the backward direction. The the selected positions is sufficiently close to the position of the
location of the maximum voltage is obtained by considering the maximum voltage. In [7] is presented an analysis of the max-
difference in time instants at which the peak value occurs at the
remote end. This procedure only requires to calculate the voltage imum voltage inside distribution cables from lightning strokes
at the cable ends and the surge arrester current. The forward and based on analysis by lattice diagrams. However, that analysis
backward waves can then be calculated by simple expressions. The does not cover the cable attenuation effects found in long trans-
procedure is demonstrated for a 300 kV system, for different cable mission cables and does also not consider the exact position of
lengths. maximum voltage.
Index Terms—Insulated cable, insulation coordination, over- This paper presents an alternative method for calculating the
voltage, transients. maximum voltage along a cable and its location. The analysis
considers the situation of a cable inserted in an overhead line that
I. INTRODUCTION is protected by arresters at both ends and is subjected to light-
ning overvoltages. Such overvoltages are either due to shielding
The arrester current and the voltage at the ends of the cable
can be calculated by an EMTP-type program, but the traveling
waves are normally not available.
It is assumed that no wave enters the cable from the overhead
line at end B (Fig. 1). The following equation is valid when
the characteristic impedances and are assumed constant,
i.e., independent of the frequency:
(2)
Fig. 2. Reflected voltage wave and arrester voltage as function of incoming
voltage wave, in p.u. of arrester protective level.
There are three contributions to the current in (2). The first
one is the current fed into the arrester when is zero
(grounded). This contribution equals twice the incoming cur-
rent wave. The second/third contribution is the current fed into
the cable/line when there is no incoming wave.
The arrester voltage equals if one ignores the voltage
drop along the arrester leads and the ground potential rise, more
about this in Section II-D. With and computed by
EMTP, (2) gives the forward wave . The reflected (back-
ward) wave is further found from (1). The reflected
wave depends on the instantaneous value of the incoming wave
only.
Fig. 2 shows the calculated arrester voltage and the reflected
voltage wave when and . The results
are shown for a selected arrester characteristic (Appendix A)
and for an ideal characteristic. The protective level is 636 kV at
10 kA for both characteristics and that voltage is used as p.u.
reference. It is seen that maximum value of the reflected wave
is significantly higher when applying the ideal characteristic.
It is therefore important to apply the actual characteristic in a Fig. 3. Example of voltage at cable end (top) and at the position where the
computation. maximum voltage occurs (bottom).
The ratio between reflected wave and the incoming wave de-
creases when the incoming wave increases. A maximum value reflected wave. This means that the voltage at the end of the
for the reflected wave is thus obtained for a certain value of the cable becomes less than the sum of the two maxima since they
incoming wave as can be observed in Fig. 2. An incremental in- do not appear simultaneously. However, the two maxima appear
crease in the incoming wave at that point gives zero increment in simultaneously at some distance from the end of the cable. This
the reflected wave. This implies that the maximum value of the is demonstrated in Fig. 3. The peak value of the incoming (for-
reflected wave appears when in parallel with ward) wave at the end of the cable appears at . The re-
corresponds to a reflection-free termination of the cable. That flected (backward) wave is determined from Fig. 2 and its peak
condition occurs when the arrester voltage is 0.83 p.u and the value appears at . The figure shows further the voltage
current is 828 A. It should be noted that the reflected wave is re- at distance from the end of the cable. The travel time corre-
duced if the incoming wave increases above the value that cor- sponding to is 2 and it seen that peak value of the forward
responds to the maximum reflected wave. and the backward wave occurs simultaneously at . This
The incoming voltage wave starts from zero value and reaches position therefore gives the maximum voltage along the cable.
a maximum after some time. The reflected wave obtains its max- The maximum voltage occurs at a distance given by
imum value before the incoming wave does, if the latter max-
imum value is higher than the value that causes the maximum (3)
HENRIKSEN et al.: MAXIMUM LIGHTNING OVERVOLTAGE ALONG A CABLE PROTECTED BY SURGE ARRESTERS 861
III. APPROACH
From the previous analysis can be summarized the following
approach for calculating the maximum lightning overvoltage
along a cable protected by arresters at both ends.
1) Use an EMTP-type program for computing the arrester
current and the cable voltage at the cable ends.
2) Calculate the incoming and reflected voltage waves at the Fig. 7. Impinging voltage and corresponding arrester current. Infinite cable.
remote cable end using (2) and (1).
3) Calculate the maximum cable voltage in the vicinity of the
remote end as the sum of the peak value for the incoming
wave and the peak value for the reflected wave.
4) Calculate the distance from the remote cable end to
the location of the maximum voltage using (3).
5) Compare the obtained maximum voltage with the voltage
at the exposed end
6) The approach gives a too high value if is greater than
the length of the cable. Such cases must be investigated
individually.
Fig. 9. Voltage waves at remote end and voltage 450 m from remote end. Fig. 11. Voltage at exposed end and voltage 50 m from exposed end.
(Expanded time scale, 9 km cable). (Expanded time scale, 500 m cable).
VI. DISCUSSION
It was shown in Section II-A that the maximum voltage along
the cable can be calculated by adding the peak value of the for-
ward voltage wave and the peak value of the backward voltage
wave. It was further shown that the maximum voltage occurs at
a distance from the remote end given as half the time differ-
ence between the occurrence of the two peak values multiplied
with the propagation velocity in the cable. A high value for
may result in inaccurate results since the proposed approach ne-
glects damping effects within . However, these effects are not
significant when is less than a few kilometers.
The most severe lightning overvoltages in cables result from
back-flashover. It can be shown that the highest overvoltages
occur for a lightning current with a small front time striking the
line close to the cable entrance. In these cases, the front time
of the impinging voltage is in the order of a few , as is evi-
dent in Fig. 7. Therefore, will in general be a small quan-
tity and the maximum voltage will occur within some hundred
meters from the remote end for a short cable. Distortion of the
Fig. 12. Reduction factor k as function of cable length. forward wave causes an increase in , but it is our experience
that will remain less that two kilometers, even for long ca-
bles. One important reason is that becomes zero when the
peak value of the forward voltage wave becomes less or equal
to the value that causes the maximum reflected wave. There-
fore, the approach outlined in this paper will be applicable to
most practical situations of interest. Further results (not shown
in paper) have also verified the applicability of the approach for
close shielding failures.
The approach is not suitable when the cable length becomes
less than . The maximum voltage along such cables depends
strongly on the front steepness of the impinging voltage How-
ever, the most severe cases have a very high steepness and it is
reasonable to assume that the practical lower limit is less than
400 m. When not applicable, one has to use alternative proce-
dures, for instance the model in [4].
VII. CONCLUSIONS
This paper has analyzed lightning overvoltages in a cable
which is inserted in an overhead line and protected by surge ar-
resters at both ends. A procedure is shown for calculating the
Fig. 13. Maximum cable voltage as function of cable length. maximum voltage and its location:
1) The maximum voltage along the cable is calculated by
model was for all cable lengths found to occur within 1.5 km adding the peak value of the forward voltage wave at the
from the remote end. remote end with the peak value of the backward voltage
The approach based on (4) does not take into account the in- wave at the same location.
crease in the maximum value of the forward wave demonstrated 2) The maximum occurs at a distance from the remote
in Fig. 10. That increase is due to the reflection at the exposed end, given as half the time difference between the occur-
end of the backward wave generated at the remote end. The re- rence of the two peak values at the remote end, multiplied
flection appears with a time delay equal to twice the travel time with the propagation velocity in the cable.
of the cable. The reflection increases the peak value of the for- 3) When the peak value of the forward wave at the remote
ward wave only when the impinging voltage at that time is at a end is smaller than a certain value, the maximum voltage
rather high level. Some additional investigations for the actual occurs at one of the cable ends.
example showed that the increase occurred only when the cable 4) The forward and backward voltage waves are obtained by
is less than 1.5 km. The reflection may influence even when (2) and (1) in the paper, which requires to calculate the
the peak value of is not influenced. Practical experience voltage at the cable ends and the arrester current using an
has however shown that this is not the case. EMTP-type program.
HENRIKSEN et al.: MAXIMUM LIGHTNING OVERVOLTAGE ALONG A CABLE PROTECTED BY SURGE ARRESTERS 865
5) The method allows easy calculation of the maximum impedance is and the resistance and
cable voltage as function of the cable length. propagation velocity is 0.316 and 174 , respec-
tively. These values apply to Figs. 7–11.
No flashover occurs in the right part of the line and the ground
APPENDIX wires are neglected in that part of the line. The arrester charac-
teristic is the same as in appendix A and the leads are repre-
A. Surge Arrester Current-Voltage Characteristic sented by inductances based on 1 and 8 m length.
The common grounding resistance for the cable screen, the
arrester and the adjacent tower is 1 . This low value was chosen
because the overvoltage along the cable increases when the re-
sistance decreases.
REFERENCES
[1] E. W. Greenfield, “Transient behavior of short and long cables,” IEEE
Trans. Power Apparat. Syst., vol. 103, no. 11, pp. 3193–3204, Nov. 1984.
[2] S. A. Probert, Y. Song, P. K. Basac, and C. P. Ferguson, “Re-appraisal
of the basic impulse level (BIL) for 400 kV underground cables using
EMTP/ATP,” in Proc. Int. Conf. Power System Transients (IPST), Rio de
Janeiro, Brazil, 2001, paper 011.
[3] J. Huse, K. Olsen, and T. Ulriksen, “Lightning overvoltages in cable
connections,” Electra, no. 58, pp. 81–93, 1978.
[4] L. Marti and H. W. Dommel, “Calculation of voltage profiles along trans-
mission lines,” IEEE Trans. Power Del., vol. 12, no. 2, pp. 993–998, Apr.
1997.
B. Simulation Model [5] B. Gustavsen and J. Mahseredjian, “A wide band voltage profile trans-
mission line component for the EMTP,” IEEE Trans. Power Del., to be
Fig. 14 shows the basic configuration. Four spans of the ex- published.
posed overhead line are assumed lossless and they are repre- [6] “Guide to Procedures for Estimating the Lightning Performance of
sented by a two conductor distributed parameter model (phase Transmission Lines,” CIGRE Tech. Rep. 63, WG33-01, Oct. 1991.
[7] J. A. Martinez and F. Gonzalez-Molina, “Surge protection of under-
conductor and two ground wires in parallel). The associated ground distribution cables,” IEEE Trans. Power Del., vol. 15, no. 2, pp.
characteristic impedance is 756–763, Apr. 2000.
(B.1)
Georg Balog was born in Budapest, Hungary, in 1941. He received the M.Sc. Ulf Baur was born in Göteborg, Sweden, in 1952. He received the M.Sc. degree
degree in electrical engineering at the Norwegian Institute of Technology, in electrical engineering from Chalmers University of Technology, Göteborg, in
Trondheim, in 1969. 1976.
He was with SINTEF Energy Research from 1970 to 1972, working with in- He joined the Swedish State Power Board. From 1980 to 1985, he worked
sulation related technical projects. Since 1972 he has been with Nexans working with high voltage power applications at the Joint European Torus, Oxfordshire,
with the development of HVAC and HVDC submarine cables. Currently he is U.K., after which he joined ABB, Ludvika, Sweden. Among other positions at
the Manager of Nexan’s Competence Centre for Submarine Cables and Umbil- ABB, he headed the Office for Insulation Coordination of HVDC Links. He is
icals, Norway. currently mainly working with HVDC and system related questions at Statnett,
Oslo, Norway.