Вы находитесь на странице: 1из 1

1. What is an “energy audit”? Describe about its processes and benefits?

(10 pts)
2. How to size a circuit breaker? (10pts)
3. What are the advantages of Capacitor bank? (10pts)
4. The electric zoning of one chemical industrial is supplied electric power by EDC with voltage
level of 22kV. The single line diagram of this zoning is given in the bellowed figure:

S1 S2
18m
20m
15m

S3

a. Find the maximum power for the whole system (Voltage level for this load is 0.4kV)
(20pts)
b. Select the capacitor bank (5pts)
c. Sizing the two transformers and generator(5pts)
S1 ni Pnominal (kW) ku,i cosφ
Oven 4 20 0.80 0.75
Drill machine 8 10 0.15 0.60
Exhaust fan 6 4 0.60 0.80

S2 ni Pnominal (kW) ku,i cosφ


Crane 6 10 0.10 0.50
Special machine 5 15 0.15 0.60
Exhaust fan 8 6 0.60 0.80
Compressor 4 6 0.70 0.80

S3 ni Pnominal (kW) ku,i cosφ


Pumping machine 6 10 0.70 0.80
Furnace 4 6 0.8 0.75
Exhaust fan 10 2.5 0.60 0.80

Given

We select kmax=1.2

Table T5: Standard Transformer to be selected


ST(kVA) 50 100 160 250 630 800 1000 1250 1600 2000 2500

Table T6: Standard Generator to be selected


SGkVA 10.4 16 31 40 60 73 100 128 160 200 300 350 400 536 732 905 1006

mhavifI shBn§½rusSIú RbGb;sMbuRtelx 86 PñMeBBaJ